ST9120U Universal Electronic Fan Timers INSTALLATION INSTRUCTIONS APPLICATION The ST9120U Universal Electronic Fan Timers integrate control of all combustion blower and circulating fan operations in a gas warm air appliance. This control is the central wiring point for most of the electrical components in the furnace. The basic purposes of the ST9120U are to monitor the thermostat for heat, cool and fan demands, run the induced draft blower motor and run a circulating fan (up to two speeds) as required. The electronic fan timers also monitor limit switch strings and energize separate ignition control systems through spst pressure switches. The ST9120U can replace any ST9101 or ST9120 listed in Table 2 below. The electronic fan timers feature a field-adjustable heat fan-on delay, a field-adjustable heat fan-off delay, a field-adjustable cool fan-on delay and a fixed cool fan-off delay. Electronic air cleaner (EAC) and humidifier (HUM) convenience terminal connections are provided as an option. Continuous low speed indoor air circulation is also provided. SPECIFICATIONS Electrical Ratings: Power Voltage Requirements: 18 to 30 Vac, 60 Hz. Contact Ratings: Combustion Blower: 1.5A full load, 10A locked rotor at 115 Vac. 0.75A full load, 5A locked rotor at 230 Vac. (Reduce full load rating by humidifier [HUM] load.) Circulating Fan: Heat-Cool speed: 15A full load, 30A locked rotor at 115 Vac. 7.5A full load, 15A locked rotor at 230 Vac. (Reduce full load rating by electronic air cleaner [EAC] load.) Continuous speed (optional): 8A full load, 16A locked rotor at 115 Vac. 4A full load, 8A locked rotor at 230 Vac. EAC and HUM: 0.8A maximum combined load at 115 Vac. Thermostat Load: 0.10A plus ignition system load. On/Off Delay Settings: Heat Speed: Delay On: Field-adjustable, 30 or 60 seconds. Delay timing starts when gas valve is energized. Delay Off: Field-adjustable, 60, 100, 140 or 180 seconds. Delay timing starts when gas valve is deenergized. Cool Speed: Delay On: Field Adjustable, 4 or 30 seconds. Delay Off: Fixed, 30 seconds. Timing Tolerance: Larger of ±5% or ±2 seconds. Post Purge Timing: 5 seconds. Environmental Ratings: Temperature: -40°F (-40°C) to +175°F (+79°C). Humidity: 5 to 95 percent, noncondensing. Approvals: Underwriters Laboratories Inc. File No.: MP466. Canadian Standards Association File No.: LR95329. INSTALLATION When Installing this Product... 1. 2. 3. 4. Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition. Check the ratings and specifications given in the instructions and on the product to make sure the product is suitable for your application. Installer must be a trained, experienced service technician. After installation is complete, check out the product operation as provided in these instructions. WARNING Electrical Shock Hazard. Can cause severe injury, death or property damage. Disconnect power supply before wiring to prevent electrical shock or equipment damage. More than one disconnection can be required. ® 69-0644-1 ST9120U UNIVERSAL ELECTRONIC FAN TIMERS Location and Mounting board. Be careful to directly connect to the new terminal or label each wire prior to removal from original board. Mount the ST9120U Electronic Fan Timer in the appliance wiring compartment using the four provided No. 6 selftapping screws. Table 1. ST9101 to ST9120U Wiring Conversions Wiring Make sure that all wiring complies with local codes and ordinances. Disconnect power before making wiring connections. Refer to Figs. 1, 2, 3 and 4 for standard wiring connections. Refer to Figs. 5 and 6 for internal schematics. Refer to Fig. 7 for schematic of provided ST9101 wiring adapter. Setting Adjustable Heat Fan DIP Switches Set the heat fan-on delay and cool fan-on delay DIP switches as shown in Fig. 8. The heat-on delay time starts when the main gas valve is energized at the start of a thermostat call for heat; the heat-off delay time starts when the main gas valve is de-energized at the end of a thermostat call for heat. The cool fan-on delay time starts when the compressor is energized at the start of a thermostat call for cool. ST9120 to ST9120U Wiring Conversion Instructions 1. 2. Turn off power to appliance. Carefully remove each wire and connect directly to the corresponding location on the new ST9120U control board. Be careful to directly connect to the new terminal with the same labeled identity or label each wire prior to removing from the original board. If original thermostat connection was a quick connect, cut off quick connect, strip wire and insert into terminal block. Identify the model number of the board being replaced and set the dip switches based on Table 2. ST9101 to ST9120U Wiring Conversion Instructions 1. Turn off power to appliance and carefully remove each wire and connect directly to the new ST9120U control board before removing the existing control. Use Table 1 to determine the proper ST9120U terminal for each corresponding ST9101 connection. Terminal Terminal ST9101 ST9120U heat heat cool cool S S M1 Unused Motor Leads M2 Unused Motor Leads N Neutral 1 N Neutral 2 ACC * for systems with one on fan speed (see note below) X X sec C C xfmr thermostat terminals R R Y Y C C W W G G * ACC terminal is used in ST9101 systems, which use the same fan speed for both heating and cooling. In order to use the ST9120 to replace ST9101 devices in this type of system, the fan connection that originally was connected to ACC on the ST9101 needs to be connected to both heat and cool connections on the ST9120U. 2. Unplug the 9-pin connector and plug existing wiring harness directly into the 9-pin connector found on the ST9101 wiring adapter. 3. Plug the 6-pin connector found on the ST9101 wiring adapter directly to the open 6-pin connector on the new ST9120U control board. 4. Take the two remaining white wires on the ST9101 wiring adapter and connect to Neutral quick connect terminals 3 and 4 on the ST9120U 5. Take the black wire on the ST9101 wiring adapter and connect to the S1 quick connect terminal on the ST9120U 6. Take the blue wire on the ST9101 wiring adapter and connect to the D1 quick connect terminal on the ST9120U 7. Identify the model number of the board being replaced and set the dip switches based on Table 2. 69-0644—1 2 ST9120U UNIVERSAL ELECTRONIC FAN TIMERS Table 2. Recommended Default Dip Switch Settings Model Number Original OEM Appliance 1 2 3 4 ST9101A1006 Rheem off on off on ST9101A1014 Rheem off on off on ST9101A1022 Trade off on off on ST9120A1006 Armstrong off on off on ST9120A2004 Armstrong off off on off ST9120B1005 Ducane off off off on ST9120C1012 Snyder General off on off off ST9120C1020 Nordyne off on off off ST9120C2002 York off on off on ST9120C2010 Ducane off on off on ST9120C2028 Armstrong off on off on ST9120C3000 ICP on off on on ST9120C3018 Bard off on off off ST9120C4008 ICP on off on on ST9120C4016 ICP on off on on ST9120C4040 ICP on off on on ST9120C4057 ICP on off on on *ST9120C5005 ICP off off on on *ST9120C5013 ICP off off on on *ST9120D3009 Goodman off off on on ST9120G2008 ICP on on off off ST9120G2016 ICP on on off on ST9120G2024 Skymark on off off on ST9120G2032 Skymark off off off on ST9120G4004 ICP on off on on ST9120G4012 ICP on off on on ST9120G4038 Trade on off on on ST9120U1003 Trade off off on on *ST9120U Factory Default Setting *Heat fan off delay setting may need adjustment based on performance. See Figure 8 to adjust timings. 3 69-0644—1 ST9120U UNIVERSAL ELECTRONIC FAN TIMERS L1 (H) FUSE L2 (N) TO 115/230 VAC POWER SUPPLY 115/230 VAC HUMIDIFIER TRANSFORMER 24 VAC MV LO ML MH HI 4 NEUTRAL N N CIR 2 C X S8600 INTERMITTENT PILOT IGNITION MODULE GND 24V GND 24V SPARK MV/PV PV (BURNER) LIMIT CONTROL SEC 3 XFMR 2 VR8204 COMBINATION GAS CONTROL X ROLL-OUT SWITCH BLWR HEAT EAC 1 N CONT COOL HUM 1 2 LEADS DI MOTOR 3 UNUSED INDUCER MOTOR STARTING CAP MV MV/PV PV 3 AIR CLEANER 1 CIRCULATING FAN Z1 PRESSURE SWITCH ST9120 Z2 THERMOSTAT 4 W Y G R DELAY 1 2 OFF SPEED UP C Y C G COOLING CONTACTOR Y W R PILOT BURNER 1 CONNECT ONLY IF CONTINUOUS SPEED IS AVAILABLE AND USED. 2 CONNECT ONLY IF CONTINUOUS SPEED IS NOT USED. 3 CONNECT IF EAC AND HUM TERMINALS ARE AVAILABLE AND USED. 4 SOME MODELS USE MALE 1/4-INCH QUICK-CONNECTS INSTEAD OF SCREW TERMINALS FOR THERMOSTAT CONNECTIONS. NOTE: = DENOTES STANDARD TERMINAL. DENOTES LINE VOLTAGE WIRING. = DENOTES OPTIONAL TERMINAL. DENOTES LOW VOLTAGE WIRING. PILOT BURNER GROUND Fig. 1. Typical ST9120U wiring connections with S8600 Intermittent Pilot Ignition Module. 69-0644—1 4 M5605A ST9120U UNIVERSAL ELECTRONIC FAN TIMERS HUMIDIFIER FUSE L1(H) L2(N) TO 115/230 VAC POWER SUPPLY 3 AIR CLEANER 115/230 VAC TRANSFORMER ROLL-OUT SWITCH 24 VAC INDUCER MOTOR LIMIT CONTROL HUM 2 EAC N CIR 2 X X SEC C XFMR LEADS 4 NEUTRAL N LO ML MH HI BLWR 1 CIRCULATING FAN Z1 Y G PRESSURE SWITCH ST9120 Z2 4 THERMOSTAT W 3 HEAT 1 2 1 N CONT COOL STARTING CAP DI MOTOR 3 UNUSED SV9500 SMARTVALVE™ SYSTEM CONTROL DELAY R 1 2 OFF SPEED UP C Y C G COOLING CONTACTOR Y W R 24 VOLT COMMON 24 VOLT HOT EFT OUTPUT 1 CONNECT ONLY IF CONTINUOUS SPEED IS AVAILABLE AND USED. 2 CONNECT ONLY IF CONTINUOUS SPEED IS NOT USED. 3 CONNECT IF EAC AND HUM TERMINALS ARE AVAILABLE AND USED. 4 SOME MODELS USE MALE 1/4-INCH QUICK-CONNECTS INSTEAD OF SCREW TERMINALS FOR THERMOSTAT CONNECTIONS. NOTE: = DENOTES STANDARD TERMINAL. = DENOTES OPTIONAL TERMINAL. 24 VOLT THERMOSTAT OR PRESSURE SWITCH DENOTES LOW VOLTAGE WIRING. DENOTES LINE VOLTAGE WIRING. M5603A Fig. 2. Typical ST9120U wiring connections with SV9500/SV9501 SmartValve™ System Control. 5 69-0644—1 ST9120U UNIVERSAL ELECTRONIC FAN TIMERS THERMOSTAT W Y R G W G Y C R AUX VENT MV MV ROLLOUT PRESSURE SWITCH STARTER CAP GAS VALVE LO HL HH HI MAIN LIMIT X S A C C H E A T C O O L CIRCULATING FAN C N M1 M2 CW23 24 VAC 120 VAC TRANSFORMER COMBUSTION AIR BLOWER N TO 120 VAC POWER SUPPLY M2547A L INTERLOCK Fig. 3. Typical ST9101 wiring connection in standing pilot system. 69-0644—1 6 ST9120U UNIVERSAL ELECTRONIC FAN TIMERS COMBUSTION AIR BLOWER WIRE HARNESS ADAPTER AUX P1 L2 WHITE L2 WHITE 2 PS/MV DRIVE ORANGE 3 LIMIT RED 4 LIMIT RED 5 L1 BLACK 6 24V GND YELLOW 7 MV SENSE VIOLET 8 1 VENT MV MV GAS VALVE PRESSURE SWITCH ROLLOUT 3 6 1 4 NC 2 5 9 INDUCER BLUE MAIN LIMIT 120 VAC N TO 120 VAC POWER SUPPLY 24 VAC TRANSFORMER 2 4 N NEUTRAL N N CIR 2 C SEC XFMR 3 X X BLWR HEAT 1 EAC 1 CONT COOL DI HUM LEADS 3 MOTOR INTERLOCK UNUSED L STARTER CAP 1 LO HL HH HI Z1 ST9120 Z2 CIRCULATING FAN 4 DELAY 1 2 OFF SPEED UP C Y C G Y R W CW23 THERMOSTAT W Y G R M24001 Fig. 4. Typical ST9120U wiring connections with wire adapter for replacing ST9101. 7 69-0644—1 ST9120U UNIVERSAL ELECTRONIC FAN TIMERS L1 (H) L2 (N) TO 115/230 VAC POWER SUPPLY FUSE 1 S1 INTERLOCK S3 N/C 1 N1 EAC (N) EAC (S) ELECTRONIC AIR CLEANER N1 1 K1 CONSTANT LOW 2 M2 K1 K2 HEAT K2 COOL MED-LOW CIRCULATION BLOWER MED-HIGH M1 N2 HIGH 1 HUM (S) HUM (N) HUMIDIFIER DI K3 N3 INDUCER MOTOR N4 115/230 VAC S2 TRANSFORMER 1 CN1 X C 24 VAC X-OT X LIMIT CONTROL 1 C 1 Y ST9120 ELECTRONIC FAN TIMER ROLL-OUT SWITCH 6 3 R-OT C THERMOSTAT G PS1 Y W PRESSURE SWITCH R FT C 5 2 INTERMITTENT PILOT COMBINATION GAS CONTROL MV SPARK TSTAT 1 2 MV/PV PV S8600 INTERMITTENT PILOT IGNITION MODULE 24V (GND) DENOTES OPTIONAL CONNECTIONS, COMPONENTS AND ACCESSORIES. CIRCULATION BLOWER LOW SPEED TAP CONNECTED TO OPTIONAL CONTINUOUS FAN SPEED TERMINAL IS SHOWN. CONNECT CIRCULATION BLOWER LOW SPEED TAP TO M2 IF CONTINUOUS FAN OPTION NOT PROVIDED. NOTE: DOTTED LINES REPRESENT PRINTED CIRCUIT BOARD WIRING. Fig. 5. ST9120U internal schematic for Intermittent Pilot application. 69-0644—1 COOLING CONTACTOR 8 M5606 ST9120U UNIVERSAL ELECTRONIC FAN TIMERS FUSE L1 (H) TO 115/230 VAC POWER SUPPLY 1 S1 S3 L2 (N) INTERLOCK EAC (N) EAC (S) K1 ELECTRONIC AIR CLEANER CONSTANT 2 K1 N1 1 N/C K2 HEAT K2 COOL MED-LOW MED-HIGH M1 CIRCULATING FAN HIGH HUM (S) K3 LOW M2 1 HUM (N) HUMIDIFIER DI N2 N3 INDUCER MOTOR N4 S2 115/230 VAC TRANSFORMER CN1 X 1 C 24 VAC X-OT X LIMIT CONTROL C 1 1 Y ST9120 ELECTRONIC FAN TIMER ROLL-OUT SWITCH 6 3 R-OT THERMOSTAT C G PS1 Y W PRESSURE SWITCH R 4 FT C 5 2 COOLING CONTACTOR SV9500 SMARTVALVE™ SYSTEM CONTROL 24V 1 2 TSTAT FT GND DENOTES OPTIONAL CONNECTIONS, COMPONENTS AND ACCESSORIES. CIRCULATION BLOWER LOW SPEED TAP CONNECTED TO OPTIONAL CONTINUOUS FAN SPEED TERMINAL IS SHOWN. CONNECT CIRCULATION LOW SPEED TAP TO M2 IF CONTINUOUS FAN SPEED OPTION IS NOT PROVIDED. NOTE: DOTTED LINES REPRESENT PRINTED CIRCUIT BOARD WIRING. M5604 Fig. 6. ST9120U internal schematic for SmartValve™ System applications. 9 69-0644—1 ST9120U UNIVERSAL ELECTRONIC FAN TIMERS Table 3. ST9101 Wire Adapter Connections Color Function 6pin Connector Pin Number 9pin Connector Pin Number White L2 Neutral QC 1 White L2 Neutral QC 2 Orange pressure switch to main valve 3 3 Red limit 6 4 Red limit 1 5 - open 4 - Black L1 Hot QC 6 Yellow 24V ground 2 7 Violet main valve sense 5 8 Blue inducer QC 9 P1 1 2 L2 WHITE L2 WHITE 3 PS/MV DRIVE ORANGE LIMIT RED 4 LIMIT RED 5 L1 BLACK 6 24V GND YELLOW 7 MV SENSE VIOLET 8 3 8 1 4 NC 2 5 9 INDUCER BLUE 7 8 9 6 4 5 6 5 2 1 2 3 4 3 1 M23117 Fig. 7. ST9101 Wire Adapter Schematic 69-0644—1 10 ST9120U UNIVERSAL ELECTRONIC FAN TIMERS CHECKOUT C N N CIR X X Operate the system through at least one complete heating cycle and cooling cycle to make sure the system operates properly. Troubleshoot by checking for appropriate voltages at the ST9120U terminals controlling the combustion blower and heat and cool speed circulating fan. The ST9120U schematics show internal switching to clarify operation and assist in troubleshooting. See Figs. 5 and 6. SEC 4 XFMR LEADS EAC 3 2 NEUTRAL BLWR HEAT HUM 2 1 N CONT COOL 1 DI MOTOR 3 UNUSED ST9120 Z1 Z2 DELAY UP OFF G C SPEED 1 2 3 4 C Y R W Y DELAY ON DIP SWITCH (4) DELAY OFF DIP SWITCHES (2 & 3) COOL DELAY ON DIP SWITCH (1) COOL ON DELAY 1 1 4 SECONDS 30 SECONDS HEAT ON DELAY 1 2 3 4 4 60 SECONDS 30 SECONDS HEAT OFF DELAY 2 3 2 3 2 3 2 3 140 60 100 180 SECONDS SECONDS SECONDS SECONDS FAN DELAY ON/OFF DIP SWITCH SETTINGS M11990 Fig. 8. Setting heat fan-on, heat fan-off and cool fanon delay DIP switches. Table 4. ST9120U Operating Sequence. Action System Response Thermostat calls for heat. (Terminal W is energized.) 1. 2. 3. 4. 5. Combustion air blower is energized. Air proving switch makes (air flow is established) Ignition system is energized. Gas valve opens and main burner lights. Heat fan-on delay timing begins. When timing is complete, circulating fan is energized at heat speed. Thermostat ends call for heat. (Terminal W is de-energized.) 1. 2. 3. Ignition system is de-energized and gas valve closes. Combustion air blower is de-energized after postpurge timing. Heat fan-off delay timing begins. When timing is complete, the circulating fan is de-energized. Thermostat begins call for cool. (Terminals G and Y are energized.) 1. 2. Cooling contactor is energized. Circulating fan is energized at cool speed after cool fan-on delay timing. Thermostat ends call for cool. (Terminals G and Y are de-energized.) 1. 2. Cooling contactor is de-energized. Circulating fan is de-energized after cool fan-off delay timing. Thermostat begins call for fan. (Terminal G is energized.) 1. Circulating fan is energized at heat speed two seconds after G terminal is energized. If a call for heat occurs, circulating fan continues to run at heat speed.] If a call for cool occurs, circulating fan switches to cool speed after four-second delay. 2. 3. NOTE: Circulating fan can be switched off for several seconds during the transition between fan speeds. Thermostat ends call for fan. (Terminal G is de-energized.) Circulating fan is de-energized. 11 69-0644—1 ST9120U UNIVERSAL ELECTRONIC FAN TIMERS Action System Response Limit switch string opens. 1. 2. Limit switch string remakes. 1. 2. 3. Continuous circulating fan is connected. (Optional connection to circulating fan low speed tap.) 1. Electronic air cleaner is connected. (Optional connection to 120 Vac electronic air cleaner.) 1. 2. 2. Thermostat and ignition system are de-energized and gas valve closes. Combustion air blower and circulating fan heat speed are energized. Combustion air blower remains energized for postpurge timing. The circulating fan remains energized for the selected delay-off timing. Normal operation resumes. Circulating fan low speed is energized when there is no call for heat, cool, or fan. If fan operation is required by a call for heat, cool, or fan, ST9120U switches circulating fan to appropriate speed. In two-speed systems, the electronic air cleaner is energized when the heat or cool speed of the circulating fan is energized. If continuous fan option is used, connect EAC to line voltage input S1. Line voltage hot lead is also connected in input S1. Humidity control is connected. Humidifier is energized when combustion air blower is energized. (Optional connection to 120 Vac humidifier.) Automation and Control Solutions Honeywell International Inc. Honeywell Limited-Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley, MN 55422 Scarborough, Ontario M1V 4Z9 customer.honeywell.com ® U.S. Registered Trademark © 2005 Honeywell International Inc. 69-0644—1 M.S. Rev. 11-05
© Copyright 2026 Paperzz