Energy- and Power Cable / Medium Voltage Power Cables N2XS(FL)2Y 6/10kV, 12/20kV, 18/30kV XLPE-insulated, Cu-conductor, single core, longitudinally and crosswise water-tight, screened, PE-sheath Technical data Ⴠ XLPE-insulated power cables to DIN VDE 0276 part 620, HD 620 S2 and IEC 60502 Ⴠ Temperature range during installation up to -20°C Ⴠ Operating temperature max. +90°C Ⴠ Short circuit temperature +250°C (short circuit duration max. 5 s) Ⴠ Nominal voltages U0/U 6/10 kV, 12/20 kV, 18/30 kV Ⴠ Operating voltages for 6/10 kV = max. 12 kV for 12/20 kV = max. 24 kV for 18/30 kV = max. 36 kV Ⴠ Test voltages for 6/10 kV = 15 kV for 12/20 kV = 30 kV for 18/30 kV = 45 kV Ⴠ Minimum bending radius 15x cable Ø Ⴠ Power ratings see Technical Informations Cable structure Ⴠ Bare copper-conductor, to DIN VDE 0295 cl.2, multi-wire, BS 6360 cl.2, IEC 60228 cl.2 Ⴠ Inner semi-conducting coating Ⴠ Core insulation of cross-linked polyethylene (XLPE), compound type DIX8 to HD 620 S2 Ⴠ Outer extrusion of semi-conducting coating spliced with the XLPE-insulation Ⴠ Longitudinally water-tight, conductive wrapping Ⴠ Screen: Braiding of copper wires with one or two tapes applied helically Ⴠ Longitudinally water-tight wrapping Ⴠ Aluminium tape spliced with PE sheath Ⴠ Outer sheath of PE compound type DMP2 to HD 620 S2 Ⴠ Sheath colour black Properties Ⴠ The materials used in manufacture are cadmium-free and contain no silicone and free from substances harmful to the wetting properties of lacquers Ⴠ Installation notes To guarantee an optimum on operating reliability the extruded semi-conductive layer is spliced with the insulation for long duration. For this reason we recommend a peeling tool for installation Note Ⴠ rm = round conductor, multi-wire Ⴠ Further types and dimensions on request. Ⴠ AWG sizes are approximate equivalent values. The actual cross-section is in mm². Application Installation primarily for power utility grids and in cable ducts, outdoors, underground and in water, and also on pallets for manufacturing plants, switchgear and power stations. The resistant Al/PE-laminated sheathing acts as a cross water barrier. It inhibits the diffusion of water. In case of sheathing damage, water impact is contained at the flaw. The cable can be severely mechanically stressed during installation and operation. The PE sheathing is not flame-retardant to DIN EN 60332-1-2. The internal conductive layer between conductor and VPE insulation and the adherent external conductive layer on the VPE insulation guarantees a design with high operational safety and no partial discharge. Part no. 33054 33055 33056 33057 33058 33059 33060 33061 38049 38050 38051 38052 38053 33066 33067 33083 33069 33070 33071 33072 33073 33074 33075 38054 No.cores x cross-sec. mm² 1 x 35 1 x 50 1 x 70 1 x 95 1 x 120 1 x 150 1 x 185 1 x 240 1 x 300 1 x 400 1 x 500 1 x 630 1 x 35 1 x 50 1 x 70 1 x 95 1 x 120 1 x 150 1 x 185 1 x 240 1 x 300 1 x 400 1 x 500 1 x 630 Operation voltage max. rm / 16 rm / 16 rm / 16 rm / 16 rm / 16 rm / 25 rm / 25 rm / 25 rm / 25 rm / 35 rm / 35 rm / 35 rm / 16 rm / 16 rm / 16 rm / 16 rm / 16 rm / 25 rm / 25 rm / 25 rm / 25 rm / 35 rm / 35 rm / 35 12 12 12 12 12 12 12 12 12 12 12 12 24 24 24 24 24 24 24 24 24 24 24 24 Nominal voltage kV 6 / 10 6 / 10 6 / 10 6 / 10 6 / 10 6 / 10 6 / 10 6 / 10 6 / 10 6 / 10 6 / 10 6 / 10 12 / 20 12 / 20 12 / 20 12 / 20 12 / 20 12 / 20 12 / 20 12 / 20 12 / 20 12 / 20 12 / 20 12 / 20 Insulation thickness mm 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 5,5 5,5 5,5 5,5 5,5 5,5 5,5 5,5 5,5 5,5 5,5 5,5 Screen cross-sec. mm² 16 16 16 16 16 25 25 25 25 35 35 35 16 16 16 16 16 25 25 25 25 35 35 35 Sheath thickness Nominal value mm 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 Outer Ø app. mm 28,0 30,0 32,0 33,0 34,0 36,0 38,0 40,0 42,0 46,0 49,0 51,0 33,0 35,0 36,0 38,0 39,0 41,0 43,0 45,0 47,0 50,0 54,0 55,0 Cop. weight kg / km 518,0 662,0 854,0 1094,0 1334,0 1723,0 2059,0 2587,0 3163,0 4234,0 5194,0 6442,0 518,0 662,0 854,0 1094,0 1334,0 1723,0 2059,0 2587,0 3163,0 4234,0 5194,0 6442,0 Weight AWG-No. app. kg / km 860,0 1000,0 1350,0 1680,0 2070,0 2350,0 2710,0 3260,0 3850,0 4740,0 5800,0 7120,0 1020,0 1170,0 1470,0 1860,0 2260,0 2550,0 2920,0 3490,0 4090,0 5010,0 6090,0 7440,0 2 1 2/0 3/0 4/0 300 kcmil 350 kcmil 500 kcmil 600 kcmil 750 kcmil 1000 kcmil 1250 kcmil 2 1 2/0 3/0 4/0 300 kcmil 350 kcmil 500 kcmil 600 kcmil 750 kcmil 1000 kcmil 1250 kcmil Q Continuation Ⴇ 591 Energy- and Power Cable / Medium Voltage Power Cables N2XS(FL)2Y 6/10kV, 12/20kV, 18/30kV XLPE-insulated, Cu-conductor, single core, longitudinally and crosswise water-tight, screened, PE-sheath Part no. 34312 38055 38056 38057 38058 34313 38059 34314 34315 38060 38061 No.cores x cross-sec. mm² 1 x 50 1 x 70 1 x 95 1 x 120 1 x 150 1 x 185 1 x 240 1 x 300 1 x 400 1 x 500 1 x 630 Operation voltage max. rm / 16 rm / 16 rm / 16 rm / 16 rm / 25 rm / 25 rm / 25 rm / 25 rm / 35 rm / 35 rm / 35 36 36 36 36 36 36 36 36 36 36 36 Nominal voltage kV 18 / 30 18 / 30 18 / 30 18 / 30 18 / 30 18 / 30 18 / 30 18 / 30 18 / 30 18 / 30 18 / 30 Insulation thickness mm 8 8 8 8 8 8 8 8 8 8 8 Screen cross-sec. mm² 16 16 16 16 25 25 25 25 35 35 35 Dimensions and specifications may be changed without prior notice. (RQ03) 592 Sheath thickness Nominal value mm 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 Outer Ø app. mm 36,0 40,0 42,0 44,0 45,0 47,0 49,0 52,0 55,0 58,0 60,0 Cop. weight kg / km 662,0 854,0 1094,0 1334,0 1723,0 2059,0 2587,0 3163,0 4234,0 5194,0 6442,0 Weight AWG-No. app. kg / km 1400,0 1710,0 2110,0 2520,0 2830,0 3210,0 3790,0 4430,0 5390,0 6500,0 7870,0 1 2/0 3/0 4/0 300 kcmil 350 kcmil 500 kcmil 600 kcmil 750 kcmil 1000 kcmil 1250 kcmil
© Copyright 2025 Paperzz