Technical data

SGBL Series (Electronic)
Residual Current Operated Circuit Breaker(RCBO)
14
Technical data
Standard
EN / IEC 61009 -1
Breaking capacity
6kA
Protection
Ground fault, overcurrent and short circuit
Rated current, In
3, 6, 10, 16, 20, 25, 32, 40A
Operating, IƸn
10,30, 100, 300mA
Characteristic
B.C
Rated residual current operated making &
breaking capacity IƸm
500A
Rated residual non-operated current IƸno
0.5IƸn
Rated impulse withstand voltage Uimp
4000V
Number of poles
1P+N
Rated voltage
230VAC
Ambient temperature
-25oC~+45oC,Max. 95%humidity
Residual current off-time
İ 0.1 sec.
Type of trip
Ground fault
Electronic
Over current
Thermal-magnetic
Protection degree
IP20
Installation
35mm DIN rail
Width
2 modules
Type of terminal
Lug type and Pin type
SGBL RCBO
Rated
current (A)
curve
C
curve
Packing
unit
3
SGBL-B3/10
SGBL-C3/10
1
6
SGBL-B6/10
SGBL-C6/10
1
10
SGBL-B10/10
SGBL-C10/10
1
SGBL-B16/10
SGBL-C16/10
1
SGBL-B20/10
SGBL-C20/10
1
25
SGBL-B25/10
SGBL-C25/10
1
32
SGBL-B32/10
SGBL-C32/10
1
40
SGBL-B40/10
SGBL-C40/10
1
3
SGBL-B3/30
SGBL-C3/30
1
6
SGBL-B6/30
SGBL-C6/30
1
10
SGBL-B10/30
SGBL-C10/30
1
SGBL-B16/30
SGBL-C16/30
1
SGBL-B20/30
SGBL-C20/30
1
25
SGBL-B25/30
SGBL-C25/30
1
32
SGBL-B32/30
SGBL-C32/30
1
40
SGBL-B40/30
SGBL-C40/30
1
3
SGBL-B3/100
SGBL-C3/100
1
6
SGBL-B6/100
SGBL-C6/100
1
10
SGBL-B10/100
SGBL-C10/100
1
SGBL-B16/100
SGBL-C16/100
1
SGBL-B20/100
SGBL-C20/100
1
25
SGBL-B25/100
SGBL-C25/100
1
32
SGBL-B32/100
SGBL-C32/100
1
40
SGBL-B40/100
SGBL-C40/100
1
3
SGBL-B3/300
SGBL-C3/300
1
6
SGBL-B6/300
SGBL-C6/300
1
10
SGBL-B10/300
SGBL-C10/300
1
SGBL-B16/300
SGBL-C16/300
1
SGBL-B20/300
SGBL-C20/300
1
25
SGBL-B25/300
SGBL-C25/300
1
32
SGBL-B32/300
SGBL-C32/300
1
40
SGBL-B40/300
SGBL-C40/300
1
16
20
16
20
Type AC
B
16
20
16
20
10mA
30mA
100mA
300mA
15
SGBL RCBO
16
Rated
current (A)
curve
C
curve
Packing
unit
3
SGBL-B3/10-A
SGBL-C3/10-A
1
6
SGBL-B6/10-A
SGBL-C6/10-A
1
10
SGBL-B10/10-A
SGBL-C10/10-A
1
SGBL-B16/10-A
SGBL-C16/10-A
1
SGBL-B20/10-A
SGBL-C20/10-A
1
25
SGBL-B25/10-A
SGBL-C25/10-A
1
32
SGBL-B32/10-A
SGBL-C32/10-A
1
40
SGBL-B40/10-A
SGBL-C40/10-A
1
3
SGBL-B3/30-A
SGBL-C3/30-A
1
6
SGBL-B6/30-A
SGBL-C6/30-A
1
10
SGBL-B10/30-A
SGBL-C10/30-A
1
SGBL-B16/30-A
SGBL-C16/30-A
1
SGBL-B20/30-A
SGBL-C20/30-A
1
25
SGBL-B25/30-A
SGBL-C25/30-A
1
32
SGBL-B32/30-A
SGBL-C32/30-A
1
40
SGBL-B40/30-A
SGBL-C40/30-A
1
3
SGBL-B3/100-A
SGBL-C3/100-A
1
6
SGBL-B6/100-A
SGBL-C6/100-A
1
10
SGBL-B10/100-A
SGBL-C10/100-A
1
SGBL-B16/100-A
SGBL-C16/100-A
1
SGBL-B20/100-A
SGBL-C20/100-A
1
25
SGBL-B25/100-A
SGBL-C25/100-A
1
32
SGBL-B32/100-A
SGBL-C32/100-A
1
40
SGBL-B40/100-A
SGBL-C40/100-A
1
3
SGBL-B3/300-A
SGBL-C3/300-A
1
6
SGBL-B6/300-A
SGBL-C6/300-A
1
10
SGBL-B10/300-A
SGBL-C10/300-A
1
SGBL-B16/300-A
SGBL-C16/300-A
1
SGBL-B20/300-A
SGBL-C20/300-A
1
25
SGBL-B25/300-A
SGBL-C25/300-A
1
32
SGBL-B32/300-A
SGBL-C32/300-A
1
40
SGBL-B40/300-A
SGBL-C40/300-A
1
16
20
16
20
Type A
B
16
20
16
20
10mA
30mA
100mA
300mA
1. Curves
17
2. Breaking time of residual current
In (A)
IƸn (A)
3~40
0.01,0.03,0.1,0.3
Max. Breaking times
IƸn
2IƸn
5IƸn
5A, 10A, 20A, 50A, 100A, 200A, 500A
0.1s
0.08s
0.04s
0.04s
3. Wiring
The suitable conductors should be used for connection,see table below for relative parameters.
Rated current In (A)
Cross section area S (mm2)
Tightening torque (N . m)
3~6
1
2
10
1.5
2
16~20
2.5
2
25
4
2
32
6
2
40
10
2
4. Types
Both RCCBs and RCBOs are devided into types depending on the operating function:
Type AC : For which tripping is ensured for residual sinusoidal alternating currents, whether suddenly applied or slowly rising.
Type A :For which tripping is ensued for residual sinusoidal alternating currents and residual pulsating direct currents, whether
suddenly applied or slowly rising.
5. Overall and mounting dimensions
75±0.5
45±0.5
50±0.5
36±0.5
81.5±0.5
36±0.5
34±0.5
5