Open Protocol Data Information Packet Version 5.0 Group: Controls Date: April, 96 MicroTech® Reciprocating Chiller (Italian Manufacture) Open Protocol™ Data Communications © 2002 McQuay International -CONFIDENTIALThis Document may not be copied or reproduced in any way without the express written consent of McQuay International. NOTICE Copyright © 1996 McQuay International, Minneapolis MN All rights reserved throughout the world. McQuay International reserves the right to change any information contained herein without prior notice. No guarantees are given as to the accuracy of information provided. Version 5.0 2 Contents Revision History ....................................................................................................................4 Version 5.0............................................................................................................................................ 4 Functional Goals of the Open Protocol for Recip. Chillers...............................................5 Overview............................................................................................................................................... 5 Reciprocating Chillers Included in this Open Protocol Document ....................................................... 5 Typical Open Protocol Control Functions ............................................................................................ 5 Remote Start/Stop of the Chiller ....................................................................................................... 5 Chilled Water Reset .......................................................................................................................... 5 Demand Limit ................................................................................................................................... 6 Remote Alarm Clearing .................................................................................................................... 6 Network Configuration ......................................................................................................................... 6 Communications to a Single Chiller ................................................................................................. 6 Communications to Two or More Chillers........................................................................................ 7 OPM - Open Protocol Master Panel .....................................................................................9 Input/Output Configuration (CR1 Chillers) .......................................................................10 Analog Inputs...................................................................................................................................... 10 Digital Inputs....................................................................................................................................... 10 Digital Outputs.................................................................................................................................... 11 Input/Output Configuration (CR2 Chillers) .......................................................................12 Analog Inputs...................................................................................................................................... 12 Digital Inputs....................................................................................................................................... 12 Digital Outputs.................................................................................................................................... 13 Input/Output Configuration (CR4 Chillers) .......................................................................14 Analog Inputs...................................................................................................................................... 14 Digital Inputs....................................................................................................................................... 15 Digital Outputs.................................................................................................................................... 15 Read Only Memory Locations (CR1 Chillers) ...................................................................17 Read Only Memory Locations (CR2 Chillers) ...................................................................24 Read Only Memory Locations (CR4 Chillers) ...................................................................33 Read and Write Memory Locations ...................................................................................51 Memory locations common to all types of chillers - CR1, CR2, and CR4 ..................................... 51 Memory locations applicable only to CR1 and CR2 chillers .......................................................... 52 Memory locations applicable only to CR4 chillers ......................................................................... 53 Reciprocating Chiller Simulator Package .........................................................................55 Required Development Testing Tools................................................................................................. 55 Setup of Hardware for Testing............................................................................................................ 55 Appendix A - Notes on Read Only Memory Locations ....................................................57 Note on Alarms and Alarm Related Data............................................................................................ 57 Note on Temperatures ......................................................................................................................... 57 Note on Pressures................................................................................................................................ 58 Note on Compressor Operating Hours and Starts ............................................................................... 58 Appendix B - Monitor Screens ...........................................................................................59 Appendix C - Chiller Models...............................................................................................63 GROUP 1 - CR1 Chillers.................................................................................................................... 63 GROUP 2 - CR2 Chillers.................................................................................................................... 63 GROUP 3 - CR4 Chillers.................................................................................................................... 64 Glossary of Terms ...............................................................................................................65 Rated Load AmpsIndex.......................................................................................................66 3 Version 5.0 Revision History Version 5.0 This is a general upgrade and format change of the document. Formerly, there was a single Open Protocol™ Data Communications Information Packet (Version 4.1 dated May 26, 1992) that covered all McQuay® reciprocating chillers of American and Italian manufacture. There is now a separate document for American-made reciprocating chillers and this document, for Italian-made reciprocating chillers. Correction and changes from 4.1 include: Version 5.0 • References to SnyderGeneral changed to McQuay International. • Reformatting of tables and text concerning controller memory locations. • Corrections to the addresses of read/write memory locations for Group 3 chillers. • Modification of Circuit Status and Circuit Alarms for Group 2 chillers. Formerly, there was a single set of Circuit Status values for all Group 2 chillers; there are now different sets of values for CR2-M1xx series and CR2-M2xx chillers. The same is true of Circuit Alarms. • Modification of Circuit Status and Circuit Alarms for Group 3 chillers. Formerly, there was a single set of Circuit Status values for all Group 3 chillers; there are now different sets of values for CR4-M1xx series and CR4-M2xx series. The same is true of Circuit Alarms. 4 Functional Goals of the Open Protocol for Recip. Chillers Overview The McQuay Open Protocol for reciprocating chillers allows other automation integrators the ability to communicate to a network of reciprocating chillers or to a single reciprocating chiller and obtain useful operating information through communication "reads" to the controller. In addition, remote control of the reciprocating chiller is possible by communication "writes" to the controller of new setpoints and commands. Reciprocating Chillers Included in this Open Protocol Document McQuay International manufactures MicroTech® European chillers using one of three software (and hardware) configurations. The configurations are summarized as follows: The asterisk "*" is a wildcard; characters may vary. Configuration Software IDENT Usage Group 3 *R4***** European chillers above 200 tons. Group 1 *R1***** European chillers below 100 tons. Group 2 *R2***** European chillers 100 to 200 tons. Typical Open Protocol Control Functions Hexadecimal values are indicated by a preceding ‘$’. The Open Protocol allows automation integrators to achieve many control functions which in the past would require hardwired interfaces between the building automation system (BAS) and the chiller. Using Open Protocol, it is possible to eliminate much of the expensive field wiring and provide the interface through communications. These are the typical Open Protocol control functions: • Remote start/stop of the chiller • Chilled water reset • Demand limit • Remote alarm clearing Remote Start/Stop of the Chiller Using communication "writes" to the "Network Command" memory location, the McQuay MicroTech chiller may be commanded to be enabled or disabled. This is the preferred method of remotely turning the chiller on or off. When the "Network Command" is "Disable," the LCD display on the chiller will show "Off:RemoteComm." The memory for "Network Command" is a RAM location that, upon loss and subsequent restoration of power, is initialized to "Enable." Thus the automation system should refresh this memory location to the desired state on a frequent basis, such as every minute. A standard feature of the MicroTech controller is an output dedicated to control of the chiller's evaporator pump. We recommend using this output to control the pump. Chilled Water Reset Chilled water reset is achieved quite easily through communications. See the Network Evaporator Leaving Chilled Water Temperature Reset. 5 Version 5.0 Demand Limit An automation system can establish the maximum number of cooling stages that can be active for the chiller through the "Network Demand Limit" setpoint. This is vital for systems that seek to reduce chiller capacity at certain times to avoid peak electrical demand charges. Remote Alarm Clearing The automation system can clear an active alarm in the MicroTech chiller through communications. Care should be exercised so that alarms are cleared only by authorized individuals and only when the cause of the alarm has been corrected and/or repaired. Network Configuration This section explains how the McQuay International Open Protocol Reciprocating Chiller Network works so that you can choose the correct equipment and program your system to communicate through McQuay International's MicroTech Open Protocol. There are two scenarios for connecting to the controllers that are used to make an Open Protocol Reciprocating Chiller Network. They are as follows: • Communications to a single chiller • Communications to two or more chillers Communications to a Single Chiller One port is configured for RS-232, 1200 baud All McQuay MicroTech Reciprocating Chillers are shipped from the factory with one communications port factory-configured for RS-232, 1200 baud. The port is located on the Control EnGinn and is designated Port A. This communications port is normally used in conjunction with an optional factory installed modem. Since high communication baud rates are usually desirable, it is possible to change the Port A baud rate in the field using a personal computer and the Reciprocal Chiller Monitor software program. The following diagram shows the chiller-to-network connections on Port B; communications between the chiller and a personal computer are established on Port A. Reciprocating MCB Version 5.0 6 Communications to Two or More Chillers The OPM provides a single communications port entry into the McQuay Reciprocating Chiller Network. The OPM panel consists of a McQuay model 120 controller. The automation integrator connects to Comm Port A, which is configured for RS-232, 9600 baud. Port A is the automation control integrator's Open Protocol communications port. Comm Port B is a daisy chained, multidrop, 9600 baud, RS-485 proprietary McQuay protocol. The main function of the OPM is to provide the network communications interface for up to 64 reciprocating chiller controllers. The reciprocating chiller controller is factory mounted. The unit controller provides preprogrammed, pre-engineered and pre-tested stand-alone control. There is one controller for each reciprocating chiller. In addition to this hardware you must have McQuay's Open Protocol Simulator Monitor software package for the reciprocating chiller. This software is used to configure, commission and troubleshoot the McQuay communications system. The software contains diagnostic routines that can be used to troubleshoot the McQuay network. This software is MS-DOS compatible, to be used in all IBM PC's or 100% true compatibles. The monitor software is installed in the IBM or compatible PC, and the PC is connected to the OPM Port A. Once the McQuay communication network has been commissioned and is totally functional, the BAS vendor can disconnect the monitor software PC and connect a communicating device from the BAS vendor’s network. The reciprocating chillers will continue to operate when communications are lost. However, the network must be intact for read and write requests from the BAS vendor’s communication device to be passed along to the reciprocating chillers. When the BAS communicating device is connected to the OPM panel, the communications configuration is as follows: 7 Version 5.0 Version 5.0 8 OPM MCB and Reciprocating MCB OPM - Open Protocol Master Panel There is only one memory location that can be read in the Open Protocol Master panel. It is used to verify that the OPM is powered and communicating, and that the applications code is intact. Open Protocol Master Status 0-254 = Program is running 255 = 9 $0400 Program is not running Version 5.0 Input/Output Configuration (CR1 Chillers) Analog Inputs Input Number Description 0 Evaporator Leaving Water Temperature 1 Circuit #1 Evaporator Pressure 2 Circuit #2 Evaporator Pressure 3 Circuit #1 Condenser Pressure 4 Circuit #2 Condenser Pressure 5 Voltage Ratio 6 Evaporator Leaving Water Reset 7 4 - 20 mA Demand Limit 8 Evaporator Entering Water Temperature 9 Condenser Entering Water Temperature (water cooled units) / Outdoor Air Temperature (air cooled units) 10 Condenser Leaving Water Temperature (water cooled units; not used in air cooled units) 11 Unit % RLA 12 Circuit #1 Suction Temperature 13 Circuit #2 Suction Temperature 14 Circuit #1 Liquid Line Temperature 15 Circuit #2 Liquid Line Temperature Note: The following analog inputs are optional; consult the local McQuay sales representative to find out which sensors have been installed. • Condenser Entering and Leaving Water Temperatures • Evaporator Entering Water Temperature • Outdoor Air Temperature • Unit % RLA • Circuit #1 and #2 Suction Temperatures • Circuit #1 and #2 Liquid Line Temperatures Digital Inputs Input Number Version 5.0 Description 0 Circuit #1 High Pressure Switch 1 Compressor #1 Oil Differential Switch 2 Compressor #1 Motor Protect Relay 3 Compressor #3 Oil Differential Switch 4 Compressor #3 Motor Protect Relay 10 Input Number Description 5 System Shutdown Switch 6 Phase Voltage Switch 7 Circuit #1 Auto/Pumpdown & Stop 8 Circuit #2 High Pressure Switch 9 Compressor #2 Oil Differential Switch 10 Compressor #2 Motor Protect Relay 11 Compressor #4 Oil Differential Switch 12 Compressor #4 Motor Protect Relay 13 Remote Start/Stop 14 Chilled Water Flow 15 Circuit #2 Auto/Pumpdown & Stop Digital Outputs Input Number 11 Description 0 Alarm Output 1 Chilled Water Pump 2 Circuit #1 Solenoid 3 Circuit #2 Solenoid 4 Compressor #1 Enable 5 Compressor #2 Enable 6 Programmable 7 Programmable 8 Programmable 9 Programmable 10 Circuit #1 Condenser Fan 1 11 Circuit #1 Condenser Fan 2 12 Circuit #1 Condenser Fan 3 13 Circuit #2 Condenser Fan 1 14 Circuit #2 Condenser Fan 2 15 Circuit #3 Condenser Fan 3 Version 5.0 Input/Output Configuration (CR2 Chillers) Analog Inputs Input Number 0 Evaporator Leaving Water Temperature 1 Circuit #1 Evaporator Pressure 2 Circuit #2 Evaporator Pressure 3 Circuit #1 Condenser Pressure 4 Circuit #2 Condenser Pressure 5 Voltage Ratio 6 Evaporator Leaving Water Reset 7 4 - 20 mA Demand Limit 8 Evaporator Entering Water Temperature 9 Condenser Entering Water Temperature (water cooled units) / Outdoor Air Temperature (air cooled units) 10 Condenser Leaving Water Temperature (water cooled units; not used in air cooled units) 11 Unit % RLA 12 Circuit #1 Suction Temperature 13 Circuit #2 Suction Temperature 14 Circuit #1 Liquid Line Temperature 15 Circuit #2 Liquid Line Temperature Note: • Description The following analog inputs are optional; consult the local McQuay sales representative to find out which sensors have been installed. Unit % RLA Digital Inputs Input Number Version 5.0 Description 0 Circuit #1 High Pressure Switch 1 Compressor #1 Oil Differential Switch 2 Compressor #1 Motor Protect Relay 3 (unused) 4 (unused) 5 System Shutdown Switch 6 Phase Voltage Switch 7 Circuit #1 Auto/Pumpdown & Stop 8 Circuit #2 High Pressure Switch 12 Input Number Description 9 Compressor #2 Oil Differential Switch 10 Compressor #2 Motor Protect Relay 11 (unused) 12 (unused) 13 Remote Start/Stop 14 Chilled Water Flow 15 Circuit #2 Auto/Pumpdown & Stop Digital Outputs Input Number 13 Description 0 Alarm Output 1 Chilled Water Pump 2 Circuit #1 Solenoid 3 Circuit #2 Solenoid 4 Programmable 5 Programmable 6 Programmable 7 Programmable 8 Programmable 9 Programmable 10 Circuit #1 Condenser Fan 1 11 Circuit #1 Condenser Fan 2 12 Circuit #1 Condenser Fan 3 13 Circuit #2 Condenser Fan 1 14 Circuit #2 Condenser Fan 2 15 Circuit #3 Condenser Fan 3 Version 5.0 Input/Output Configuration (CR4 Chillers) Analog Inputs Input Number Note: • Version 5.0 Description 0 Evaporator Leaving Water Temperature 1 Circuit #1 Evaporator Pressure 2 Circuit #2 Evaporator Pressure 3 Circuit #1 Condenser Pressure 4 Circuit #2 Condenser Pressure 5 Voltage Ratio 6 Evaporator Leaving Water Reset 7 4 - 20 mA Demand Limit 8 Evaporator Entering Water Temperature 9 Condenser Entering Water Temperature (water cooled units) / Outdoor Air Temperature (air cooled units) 10 Condenser Leaving Water Temperature (water cooled units; not used in air cooled units) 11 Unit % RLA 12 Circuit #1 Suction Temperature 13 Circuit #2 Suction Temperature 14 Circuit #1 Liquid Line Temperature 15 Circuit #2 Liquid Line Temperature 16 Circuit #3 Evaporator Pressure 17 Circuit #4 Evaporator Pressure 18 Circuit #3 Condenser Pressure 19 Circuit #4 Condenser Pressure 20 Circuit #3 Suction Temperature 21 Circuit #4 Suction Temperature 22 Circuit #3 Liquid Line Temperature 23 Circuit #4 Liquid Line Temperature The following analog inputs are optional; consult the local McQuay sales representative to find out which sensors have been installed. Unit % RLA 14 Digital Inputs Input Number 15 Description 0 Circuit #1 High Pressure Switch 1 Compressor #1 Oil Differential Switch 2 Compressor #1 Motor Protect Relay 3 Compressor #3 Oil Differential Switch 4 Compressor #3 Motor Protect Relay 5 System Shutdown Switch 6 Phase Voltage Switch 7 Circuit #1 Auto/Pumpdown & Stop 8 Circuit #2 High Pressure Switch 9 Compressor #2 Oil Differential Switch 10 Compressor #2 Motor Protect Relay 11 Compressor #4 Oil Differential Switch 12 Compressor #4 Motor Protect Relay 13 Remote Start/Stop 14 Chilled Water Flow 15 Circuit #2 Auto/Pumpdown & Stop 16 Circuit #3 High Pressure Switch 17 Circuit #3 Auto/Pumpdown & Stop 18 Circuit #4 High Pressure Switch 19 Circuit #4 Auto/Pumpdown & Stop 20 Compressor #1 Thermal Overload 21 Compressor #2 Thermal Overload 22 Compressor #3 Thermal Overload 23 Compressor #4 Thermal Overload Version 5.0 Digital Outputs Input Number Version 5.0 Description 0 Alarm Output 1 Chilled Water Pump 2 Circuit #1 Solenoid 3 Programmable 4 Programmable 5 Circuit #2 Solenoid 6 Programmable 7 Programmable 8 Circuit #3 Solenoid 9 Programmable 10 Programmable 11 Circuit #4 Solenoid 12 Programmable 13 Programmable 14 Circuit #1 Condenser Fan 1 15 Circuit #1 Condenser Fan 2 16 Circuit #1 Condenser Fan 3 17 Circuit #2 Condenser Fan 1 18 Circuit #2 Condenser Fan 2 19 Circuit #2 Condenser Fan 3 20 Circuit #3 Condenser Fan 1 21 Circuit #3 Condenser Fan 2 22 Circuit #3 Condenser Fan 3 23 Circuit #4 Condenser Fan 1 24 Circuit #4 Condenser Fan 2 25 Circuit #4 Condenser Fan 3 16 Read Only Memory Locations (CR1 Chillers) Variable Name 17 Address Range Units Circuit #1 Condenser Approach Temperature $0497 (hi byte) $0498 (lo byte) 0 to 263°F °F * 10 Circuit #1 Condenser Pressure $0467 (hi byte) $0468 (lo byte) 0-450 PSI * 10 Circuit #1 Conditions at Time of Alarm: Condenser Pressure $0822 (hi byte) $0823 (lo byte) 0-450 PSI * 10 Circuit #1 Conditions at Time of Alarm: Evaporator Pressure $0820 (hi byte) $0821 (lo byte) 0-145 PSI * 10 Circuit #1 Conditions at Time of Alarm: Liquid Line Temperature $0826 (hi byte) $0827 (lo byte) -40 to 263°F (°F+100) * 10 Circuit #1 Conditions at Time of Alarm: Suction Temperature $0824 (hi byte) $0825 (lo byte) -40 to 263°F (°F+100) * 10 Circuit #1 Current Alarm $0831 1 - 23; 129 - 151 See alarm list below Circuit #1 Evaporator Pressure $0463 (hi byte) $0464 (lo byte) 0-145 PSI * 10 Circuit #1 Liquid Line Temperature $0479 (hi byte) $047A (lo byte) -40 to 263°F (°F+100) * 10 Circuit #1 Previous Alarm $0833 1 - 23; 129 - 151 See alarm list below Circuit #1 Status $0428 0-9 See status list below Circuit #1 Subcooling Temperature $049B (hi byte) $049C (lo byte) 0 to 263°F °F * 10 Circuit #1 Suction Temperature $0475 (hi byte) $0476 (lo byte) -40 to 263°F (°F+100) * 10 Circuit #1 Superheat Temperature $0493 (hi byte) $0494 (lo byte) 0 to 263°F °F * 10 Circuit #2 Condenser Approach Temperature $0499 (hi byte) $049A (lo byte) 0 to 263°F °F * 10 Circuit #2 Condenser Pressure $0469 (hi byte) $046A (lo byte) 0-450 PSI * 10 Circuit #2 Conditions at Time of Alarm: Condenser Pressure $082A (hi byte) $082B (lo byte) 0-450 PSI * 10 Circuit #2 Conditions at Time of Alarm: Evaporator Pressure $0828 (hi byte) $0829 (lo byte) 0-145 PSI * 10 Circuit #2 Conditions at Time of Alarm: Liquid Line Temperature $082E (hi byte) $082F (lo byte) -40 to 263°F (°F+100) * 10 Circuit #2 Conditions at Time of Alarm: Suction Temperature $082C (hi byte) $082D (lo byte) -40 to 263°F (°F+100) * 10 Circuit #2 Current Alarm $0832 1 - 23; 129 - 151 See alarm list below Circuit #2 Evaporator Pressure $0465 (hi byte) $0466 (lo byte) 0-145 PSI * 10 Version 5.0 Variable Name Range Units Circuit #2 Liquid Line Temperature $047B (hi byte) $047C (lo byte) -40 to 263°F (°F+100) * 10 Circuit #2 Previous Alarm $0834 1 - 23; 129 - 151 See alarm list below Circuit #2 Status $0429 0-9 See status list below Circuit #2 Subcooling Temperature $049D (hi byte) $049E (lo byte) 0 to 263°F °F * 10 Circuit #2 Suction Temperature $0477 (hi byte) $0478 (lo byte) -40 to 263°F (°F+100) * 10 Circuit #2 Superheat Temperature $0495 (hi byte) $0496 (lo byte) 0 to 263°F °F * 10 Compressor #1 Operating Hours $0862 (hi byte) $0863 (lo byte) 0 - 65279 (hi byte*256) + lo byte Compressor #1 Starts $086A (hi byte) $086B (lo byte) 0 - 65279 (hi byte*256) + lo byte Compressor #2 Operating Hours $0864 (hi byte) $0865 (lo byte) 0 - 65279 (hi byte*256) + lo byte Compressor #2 Starts $086C (hi byte) $086D (lo byte) 0 - 65279 (hi byte*256) + lo byte Compressor #3 Operating Hours $0866 (hi byte) $0867 (lo byte) 0 - 65279 (hi byte*256) + lo byte Compressor #3 Starts $086E (hi byte) $086F (lo byte) 0 - 65279 (hi byte*256) + lo byte Compressor #4 Operating Hours $0868 (hi byte) $0869 (lo byte) 0 - 65279 (hi byte*256) + lo byte Compressor #4 Starts $0870 (hi byte) $0871 (lo byte) 0 - 65279 (hi byte*256) + lo byte Condenser Entering Water Temperature $0470 (hi byte) $0471 (lo byte) -40 to 263°F (°F+100) * 10 Condenser Leaving Water Temperature $0472 (hi byte) $0473 (lo byte) -40 to 263°F (°F+100) * 10 Evaporator Entering Water Temperature $046E (hi byte) $046F (lo byte) -40 to 263°F (°F+100) * 10 Evaporator Leaving Water Temperature $0461 (hi byte) $0462 (lo byte) -40 to 263°F (°F+100) * 10 OaT $047D (hi byte) $047E (lo byte) -40 to 263°F (°F+100) * 10 Stage of Cooling $042B 0-8 Unit % RLA $0474 0 - 100 Percent Unit Status $0427 0 - 14 See unit status list below Note: Version 5.0 Address For notes on alarms and alarm related data, temperatures, pressures, compressor operating hours and starts, see Appendix A. 18 Circuit #1 Condenser Approach Temperature $0497/$0498 This location contains the Condenser Approach Temperature in °F. The approach temperature is calculated by subtracting the Condenser Leaving Water Temperature from the condenser refrigerant temperature. Circuit #1 Condenser Pressure Measured pressure in circuit #1 condenser. $0467/$0468 Circuit #1 Conditions at Time of Alarm: Condenser Pressure Condenser pressure at time of circuit #1 alarm occurrence. $0822/$0823 Circuit #1 Conditions at Time of Alarm: Evaporator Pressure Evaporator pressure at time of circuit #1 alarm occurrence. $0820/$0821 Circuit #1 Conditions at Time of Alarm: Liquid Line Temperature Measured temperature in circuit #1 liquid line at time of alarm occurrence. $0826/$0827 Circuit #1 Conditions at Time of Alarm: Suction Temperature Measured temperature in circuit #1 suction line at time of alarm occurrence. $0824/$0825 Circuit #1 Current Alarm $0831 Alarm Name Cleared Active Hi Condenser Pre-Alarm Hold Stage 1 129 Hi Condenser Pre-Alarm Stage Down 2 130 Freeze Refrigerant Pre-Alarm Stage Down 3 131 Loss Of Chilled Water Flow 4 132 No Pump Down 5 133 Refrigerant Freeze Protect 6 134 Low Evap Pressure 7 135 Comp4 Motor Protect 8 136 Comp3 Motor Protect 9 137 Comp2 Motor Protect 10 138 Comp1 Motor Protect 11 139 Comp4 Low Oil Pressure 12 140 Comp3 Low Oil Pressure 13 141 Comp2 Low Oil Pressure 14 142 Comp1 Low Oil Pressure 15 143 High Cond Pressure 16 144 Mech. High Pressure 17 145 Bad Evap Pressure Sensor 18 146 Bad Cond Pressure Sensor 19 147 Bad Phase/Volts 20 148 Chilled Water Freeze Protect 21 149 Bad Voltage Ratio Sensor 22 150 Bad Evap Lvg T Sensor 23 151 A value of zero indicates "no alarm." Circuit #1 Evaporator Pressure Measured pressure in circuit #1 evaporator. 19 $0463/$0464 Version 5.0 Circuit #1 Liquid Line Temperature $0479/$047A This location contains the temperature, in °F, of the liquid refrigerant entering the expansion valve. Circuit #1 Previous Alarm See list for circuit #1 Current Alarm, above. $0833 Circuit #1 Status Defined values: $0428 0= Off, S-1 Switch 1= Off, Manual Setpoint 2= Off, Alarm 3= Off, Pump Down Switch 4= Off, Wait For Cycle 5= Off, Ready to Start 6= Start Pump Down 7= Pump Down 8= Wait For Cooling Pressure 9= Cooling Circuit #1 Subcooling Temperature $049B/$049C This location contains the Subcooling Temperature in °F. The subcooling temperature is calculated by subtracting the Liquid Line Temperature from the condenser refrigerant temperature. Circuit #1 Suction Temperature $0475/$0476 This location contains the temperature, in °F, of the low-pressure vaporized refrigerant entering the compressor. Circuit #1 Superheat Temperature $0493/$0494 This location contains the Superheat Temperature in °F. The superheat temperature is calculated by subtracting the evaporator refrigerant temperature from the Suction Temperature. Circuit #2 Condenser Approach Temperature $0499/$049A This location contains the Condenser Approach Temperature in °F. The approach temperature is calculated by subtracting the Condenser Leaving Water Temperature from the condenser refrigerant temperature. Circuit #2 Condenser Pressure Measured pressure in circuit #2 condenser. $0469/$046A Circuit #2 Conditions at Time of Alarm: Condenser Pressure Condenser pressure at time of circuit #2 alarm occurrence. $082A/$082B Circuit #2 Conditions at Time of Alarm: Evaporator Pressure Evaporator pressure at time of circuit #2 alarm occurrence. $0828/$0829 Circuit #2 Conditions at Time of Alarm: Liquid Line Temperature Measured temperature in circuit #2 liquid line at time of alarm occurrence. $082E/$082F Circuit #2 Conditions at Time of Alarm: Suction Temperature Measured temperature in circuit #2 suction line at time of alarm occurrence. $082C/$082D Circuit #2 Current Alarm Version 5.0 $0832 Alarm Name Cleared Active Hi Condenser Pre-Alarm Hold Stage 1 129 Hi Condenser Pre-Alarm Stage Down 2 130 20 Freeze Refrigerant Pre-Alarm Stage Down 3 131 Loss Of Chilled Water Flow 4 132 No Pump Down 5 133 Refrigerant Freeze Protect 6 134 Low Evap Pressure 7 135 Comp4 Motor Protect 8 136 Comp3 Motor Protect 9 137 Comp2 Motor Protect 10 138 Comp1 Motor Protect 11 139 Comp4 Low Oil Pressure 12 140 Comp3 Low Oil Pressure 13 141 Comp2 Low Oil Pressure 14 142 Comp1 Low Oil Pressure 15 143 High Cond Pressure 16 144 Mech. High Pressure 17 145 Bad Evap Pressure Sensor 18 146 Bad Cond Pressure Sensor 19 147 Bad Phase/Volts 20 148 Chilled Water Freeze Protect 21 149 Bad Voltage Ratio Sensor 22 150 Bad Evap Lvg T Sensor 23 151 A value of zero indicates "no alarm." Circuit #2 Evaporator Pressure Measured pressure in circuit #2 evaporator. $0465/$0466 Circuit #2 Liquid Line Temperature $047B/$047C This location contains the temperature, in °F, of the liquid refrigerant entering the expansion valve. Circuit #2 Previous Alarm See list for circuit #2 Current Alarm, above. 21 $0834 Version 5.0 Circuit #2 Status Defined values: 0= Off, S-1 System Switch 1= Off, Manual Setpoint 2= Off, Alarm 3= Off, Pump Down Switch 4= Off, Wait For Cycle 5= Off, Ready to Start 6= Start Pump Down 7= Pump Down 8= Wait For Cooling Pressure 9= Cooling $0429 Circuit #2 Subcooling Temperature $049D/$049E This location contains the Subcooling Temperature in °F. The subcooling temperature is calculated by subtracting the Liquid Line Temperature from the condenser refrigerant temperature. Circuit #2 Suction Temperature $0477/$0478 This location contains the temperature, in °F, of the low-pressure vaporized refrigerant entering the compressor. Circuit #2 Superheat Temperature $0495/$0496 This location contains the Superheat Temperature in °F. The superheat temperature is calculated by subtracting the evaporator refrigerant temperature from the Suction Temperature. Compressor #1 Operating Hours Cumulative total of operating hours for compressor #1. Compressor #1 Starts Running total of starts for compressor #1. Compressor #2 Operating Hours Cumulative total of operating hours for compressor #2. Compressor #2 Starts Running total of starts for compressor #2. $0862/$0863 $086A/$086B $0864/$0865 $086C/$086D Compressor #3 Operating Hours Cumulative total of operating hours for compressor #3. $0866/$0867 Compressor #3 Starts Running total of starts for compressor #3. $086E/$086F Compressor #4 Operating Hours Cumulative total of operating hours for compressor #4. $0868/$0869 Compressor #4 Starts Running total of starts for compressor #4. $0870/$0871 Condenser Entering Water Temperature $0470/$0471 This location contains the temperature, in °F, of water entering the condenser. (Applies to water cooled units only.) Condenser Leaving Water Temperature $0472/$0473 This location contains the temperature, in °F, of water leaving the condenser. (Applies to water cooled units only.) Evaporator Entering Water Temperature $046E/$046F This location contains the temperature, in °F, of the chilled water entering the evaporator. Version 5.0 22 Evaporator Leaving Water Temperature $0461/$0462 This location contains the temperature, in °F, of the chilled water leaving the evaporator. OAT This location contains the Outdoor Air Temperature. Stage of Cooling Stage of cooling capacity at which the chiller is currently operating. $047D/$047E $042B Unit % RLA $0474 This location contains the percentage of Rated Load Amps being drawn by the unit. If the input from the transducer for % RLA drops below 0.1VDC, a value of 254 (decimal) will be placed in this location, in order to differentiate between noise and low current draw. Unit Status Defined values: 23 0= Off, Manual Setpoint 1= Off, S-1 System Switch 2= Off, Remote Communication 3= Off, Remote Switch 4= Off, Time Schedule 5= Off, Alarm 6= Off, Pump Down Switches 7= Off, Ready to Start 8= Starting 9= Waiting For Flow 10 = Waiting For Load 11 = Cool Stage Up 12 = Cool Stage Down 13 = Cool Staging 14 = Manual Cool Staging $0427 Version 5.0 Read Only Memory Locations (CR2 Chillers) Variable Name Version 5.0 Address Range Units Circuit #1 Condenser Approach Temperature $0497 (hi byte) $0498 (lo byte) 0 to 263°F °F * 10 Circuit #1 Condenser Pressure $0467 (hi byte) $0468 (lo byte) 0-450 PSI * 10 Circuit #1 Conditions at Time of Alarm: Condenser Pressure $0822 (hi byte) $0823 (lo byte) 0-450 PSI * 10 Circuit #1 Conditions at Time of Alarm: Evaporator Pressure $0820 (hi byte) $0821 (lo byte) 0-145 PSI * 10 Circuit #1 Conditions at Time of Alarm: Liquid Line Temperature $0826 (hi byte) $0827 (lo byte) -40 to 263°F (°F+100) * 10 Circuit #1 Conditions at Time of Alarm: Suction Temperature $0824 (hi byte) $0825 (lo byte) -40 to 263°F (°F+100) * 10 Circuit #1 Current Alarm $0831 1 - 23; 129 - 151 See alarm list below Circuit #1 Evaporator Pressure $0463 (hi byte) $0464 (lo byte) 0-145 PSI * 10 Circuit #1 Liquid Line Temperature $0479 (hi byte) $047A (lo byte) -40 to 263°F (°F+100) * 10 Circuit #1 Previous Alarm $0833 1 - 26; 129 - 154 See alarm list below Circuit #1 Status $0428 0 - 13 See status list below Circuit #1 Subcooling Temperature $049B (hi byte) $049C (lo byte) 0 to 263°F °F * 10 Circuit #1 Suction Temperature $0475 (hi byte) $0476 (lo byte) -40 to 263°F (°F+100) * 10 Circuit #1 Superheat Temperature $0493 (hi byte) $0494 (lo byte) 0 to 263°F °F * 10 Circuit #2 Condenser Approach Temperature $0499 (hi byte) $049A (lo byte) 0 to 263°F °F * 10 Circuit #2 Condenser Pressure $0469 (hi byte) $046A (lo byte) 0-450 PSI * 10 Circuit #2 Conditions at Time of Alarm: Condenser Pressure $082A (hi byte) $082B (lo byte) 0-450 PSI * 10 Circuit #2 Conditions at Time of Alarm: Evaporator Pressure $0828 (hi byte) $0829 (lo byte) 0-145 PSI * 10 Circuit #2 Conditions at Time of Alarm: Liquid Line Temperature $082E (hi byte) $082F (lo byte) -40 to 263°F (°F+100) * 10 Circuit #2 Conditions at Time of Alarm: Suction Temperature $082C (hi byte) $082D (lo byte) -40 to 263°F (°F+100) * 10 Circuit #2 Current Alarm $0832 1 - 26; 129 - 154 See alarm list below 24 Variable Name Range Units Circuit #2 Evaporator Pressure $0465 (hi byte) $0466 (lo byte) 0-145 PSI * 10 Circuit #2 Liquid Line Temperature $047B (hi byte) $047C (lo byte) -40 to 263°F (°F+100) * 10 Circuit #2 Previous Alarm $0834 1 - 23; 129 - 151 See alarm list below Circuit #2 Status $0429 0 - 13 See status list below Circuit #2 Subcooling Temperature $049D (hi byte) $049E (lo byte) 0 to 263°F °F * 10 Circuit #2 Suction Temperature $0477 (hi byte) $0478 (lo byte) -40 to 263°F (°F+100) * 10 Circuit #2 Superheat Temperature $0495 (hi byte) $0496 (lo byte) 0 to 263°F °F * 10 Compressor #1 Operating Hours (High Speed) $0862 (hi byte) $0863 (lo byte) 0 - 65279 (hi byte*256) + lo byte Compressor #1 Operating Hours (Low Speed) $09D7 (hi byte) $09D8 (lo byte) 0 - 65279 (hi byte*256) + lo byte Compressor #1 Starts (High Speed) $086A (hi byte) $086B (lo byte) 0 - 65279 (hi byte*256) + lo byte Compressor #1 Starts (Low Speed) $09DF (hi byte) $09E0 (lo byte) 0 - 65279 (hi byte*256) + lo byte Compressor #2 Operating Hours (High Speed) $0864 (hi byte) $0865 (lo byte) 0 - 65279 (hi byte*256) + lo byte Compressor #2 Operating Hours (Low Speed) $09D9 (hi byte) $09DA (lo byte) 0 - 65279 (hi byte*256) + lo byte Compressor #2 Starts (High Speed) $086C (hi byte) $086D (lo byte) 0 - 65279 (hi byte*256) + lo byte Compressor #2 Starts (Low Speed) $09E1 (hi byte) $09E2 (lo byte) 0 - 65279 (hi byte*256) + lo byte Condenser Entering Water Temperature $0470 (hi byte) $0471 (lo byte) -40 to 263°F (°F+100) * 10 Condenser Leaving Water Temperature $0472 (hi byte) $0473 (lo byte) -40 to 263°F (°F+100) * 10 Evaporator Entering Water Temperature $046E (hi byte) $046F (lo byte) -40 to 263°F (°F+100) * 10 Evaporator Leaving Water Temperature $0461 (hi byte) $0462 (lo byte) -40 to 263°F (°F+100) * 10 OAT $047D (hi byte) $047E (lo byte) -40 to 263°F (°F+100) * 10 Stage of Cooling $042B 0-8 Unit % RLA $0474 0 - 100 Percent Unit Status $0427 0 - 14 See unit status list below Note: 25 Address For notes on alarms and alarm related data, temperatures, pressures, compressor operating hours and starts, see Appendix A. Version 5.0 Circuit #1 Condenser Approach Temperature $0497/$0498 This location contains the Condenser Approach Temperature in °F. The approach temperature is calculated by subtracting the Condenser Leaving Water Temperature from the condenser refrigerant temperature. Circuit #1 Condenser Pressure Measured pressure in circuit # 1 condenser. $0467/$0468 Circuit #1 Conditions at Time of Alarm: Condenser Pressure Condenser pressure at time of circuit #1 alarm occurrence. $0822/$0823 Circuit #1 Conditions at Time of Alarm: Evaporator Pressure Evaporator pressure at time of circuit #1 alarm occurrence. $0820/$0821 Circuit #1 Conditions at Time of Alarm: Liquid Line Temperature Measured temperature in circuit #1 liquid line at time of alarm occurrence. $0826/$0827 Circuit #1 Conditions at Time of Alarm: Suction Temperature Measured temperature in circuit #1 suction line at time of alarm occurrence. $0824/$0825 Circuit #1 Current Alarm Defined values for CR2-M1xx series: $0831 Alarm Name Cleared Active Hi Condenser Pre-Alarm Hold Stage 1 129 Hi Condenser Pre-Alarm Stage Down 2 130 Freeze Refrigerant Pre-Alarm Stage Down 3 131 Loss Of Chilled Water Flow 4 132 No Pump Down 5 133 Refrigerant Freeze Protect 6 134 Low Evap Pressure 7 135 Comp4 Motor Protect 8 136 Comp3 Motor Protect 9 137 Comp2 Motor Protect 10 138 Comp1 Motor Protect 11 139 Comp4 Low Oil Pressure 12 140 Comp3 Low Oil Pressure 13 141 Comp2 Low Oil Pressure 14 142 Comp1 Low Oil Pressure 15 143 High Cond Pressure 16 144 Mech. High Pressure 17 145 Bad Evap Pressure Sensor 18 146 Bad Cond Pressure Sensor 19 147 Bad Phase/Volts 20 148 Chilled Water Freeze Protect 21 149 Bad Voltage Ratio Sensor 22 150 Bad Evap Lvg T Sensor 23 151 Cleared Active Defined values for CR2-M2xx series: Alarm Name Version 5.0 26 Compressor Warning 128 Hi Condenser Pre-Alarm Hold Stage 1 129 Hi Condenser Pre-Alarm Stage Down 2 130 Freeze Refrigerant Pre-Alarm Stage Down 3 131 Loss Of Chilled Water Flow 4 132 No Pump Down 5 133 Low Evap Press: No Start 6 134 Failed Pre-Purge 7 135 Failed Low Ambient Start 8 136 Refrigerant Freeze Protect 9 137 Low Evap Pressure 10 138 Comp2 Bad Suction Temp 11 139 Comp1 Bad Suction Temp 12 140 Comp2 Motor Protect/Very Low Pressure 13 141 Comp1 Motor Protect/Very Low Pressure 14 142 Comp4 Low Oil Pressure 15 143 Comp3 Low Oil Pressure 16 144 Comp2 Low Oil Pressure 17 145 Comp1 Low Oil Pressure 18 146 High Cond Pressure 19 147 Mech. High Pressure 20 148 Bad Evap Pressure Sensor 21 149 Bad Cond Pressure Sensor 22 150 System Alarm/Bad Phase/Volts 23 151 Chilled Water Freeze Protect 24 152 Bad Voltage Ratio Sensor 25 153 Bad Evap Lvg T Sensor 26 154 A value of zero indicates "no alarm." Circuit # 1 Evaporator Pressure Measured pressure in circuit #1 evaporator. $0463/$0464 Circuit #1 Liquid Line Temperature $0479/$047A This location contains the temperature, in °F, of the liquid refrigerant entering the expansion valve. Circuit #1 Previous Alarm See list for circuit #1 Current Alarm, above. 27 $0833 Version 5.0 Circuit #1 Status Defined values for CR2-M1xx series: 0= Off, S-1 System Switch 1= Off, Manual Setpoint 2= Off, Alarm 3= Off, Pump Down Switch 4= Off, Wait For Cycle 5= Off, Ready to Start 6= Start Cooling 7= Start Pump Down 8= Pump Down 9= Wait For Cooling Pressure 10 = Brine Start Cycling 11 = Cooling $0428 Defined values for CR2-M2xx series: 0= Off, S-1 System Switch 1= Off, Manual Setpoint 2= Off, Alarm 3= Off, Pump Down Switch 4= Off, Wait For Cycle 5= Off, Ready to Start 6= Start Cooling 7= Start Pump Down 8= Pump Down 9= Pre-Purge Cycle 10 = Purge Cycle 11 = Open Solenoid Valve 12 = Low Ambient Start 13 = Cooling Circuit #1 Subcooling Temperature $049B/$049C This location contains the Subcooling Temperature in °F. The subcooling temperature is calculated by subtracting the Liquid Line Temperature from the condenser refrigerant temperature. Circuit #1 Suction Temperature $0475/$0476 This location contains the temperature, in °F, of the low-pressure vaporized refrigerant entering the compressor. Circuit #1 Superheat Temperature $0493/$0494 This location contains the Superheat Temperature in °F. The superheat temperature is calculated by subtracting the evaporator refrigerant temperature from the Suction Temperature. Circuit #2 Condenser Approach Temperature $0499/$049B This location contains the Condenser Approach Temperature in °F. The approach temperature is calculated by subtracting the Condenser Leaving Water Temperature from the condenser refrigerant temperature. Version 5.0 28 Circuit #2 Condenser Pressure Measured pressure in circuit #2 condenser. $0469/$046A Circuit #2 Conditions at Time of Alarm: Condenser Pressure Condenser pressure at time of circuit #2 alarm occurrence. $082A/$082B Circuit #2 Conditions at Time of Alarm: Evaporator Pressure Evaporator pressure at time of circuit #2 alarm occurrence. $0828/$0829 Circuit #2 Conditions at Time of Alarm: Liquid Line Temperature Measured temperature in circuit #2 liquid line at time of alarm occurrence. $082E/$082F Circuit #2 Conditions at Time of Alarm: Suction Temperature Measured temperature in circuit #2 suction line at time of alarm occurrence. $082C/$082D Circuit #2 Current Alarm Defined values for CR2-M1xx series: $0832 Alarm Name Cleared Active Hi Condenser Pre-Alarm Hold Stage 1 129 Hi Condenser Pre-Alarm Stage Down 2 130 Freeze Refrigerant Pre-Alarm Stage Down 3 131 Loss Of Chilled Water Flow 4 132 No Pump Down 5 133 Refrigerant Freeze Protect 6 134 Low Evap Pressure 7 135 Comp4 Motor Protect 8 136 Comp3 Motor Protect 9 137 Comp2 Motor Protect 10 138 Comp1 Motor Protect 11 139 Comp4 Low Oil Pressure 12 140 Comp3 Low Oil Pressure 13 141 Comp2 Low Oil Pressure 14 142 Comp1 Low Oil Pressure 15 143 High Cond Pressure 16 144 Mech. High Pressure 17 145 Bad Evap Pressure Sensor 18 146 Bad Cond Pressure Sensor 19 147 Bad Phase/Volts 20 148 Chilled Water Freeze Protect 21 149 Bad Voltage Ratio Sensor 22 150 Bad Evap Lvg T Sensor 23 151 Alarm Name Cleared Active Compressor Warning 128 Hi Condenser Pre-Alarm Hold Stage 1 129 Hi Condenser Pre-Alarm Stage Down 2 130 Freeze Refrigerant Pre-Alarm Stage Down 3 131 Defined values for CR2-M2xx series: 29 Version 5.0 Alarm Name Cleared Active Loss Of Chilled Water Flow 4 132 No Pump Down 5 133 Low Evap Press: No Start 6 134 Failed Pre-Purge 7 135 Failed Low Ambient Start 8 136 Refrigerant Freeze Protect 9 137 Low Evap Pressure 10 138 Comp2 Bad Suction Temp 11 139 Comp1 Bad Suction Temp 12 140 Comp2 Motor Protect/Very Low Pressure 13 141 Comp1 Motor Protect/Very Low Pressure 14 142 Comp4 Low Oil Pressure 15 143 Comp3 Low Oil Pressure 16 144 Comp2 Low Oil Pressure 17 145 Comp1 Low Oil Pressure 18 146 High Cond Pressure 19 147 Mech. High Pressure 20 148 Bad Evap Pressure Sensor 21 149 Bad Cond Pressure Sensor 22 150 System Alarm/Bad Phase/Volts 23 151 Chilled Water Freeze Protect 24 152 Bad Voltage Ratio Sensor 25 153 Bad Evap Lvg T Sensor 26 154 A value of zero indicates "no alarm." Circuit #2 Evaporator Pressure Measured pressure in circuit #2 evaporator. $0465/$0466 Circuit #2 Liquid Line Temperature $047B/$047C This location contains the temperature, in °F, of the liquid refrigerant entering the expansion valve. Version 5.0 Circuit #2 Previous Alarm See list for circuit #2 Current Alarm, above. $0834 Circuit #2 Status Defined values for CR2-M1xx series: $0429 0= Off, S-1 System Switch 1= Off, Manual Setpoint 2= Off, Alarm 3= Off, Pump Down Switch 4= Off, Wait For Cycle 5= Off, Ready to Start 6= Start Cooling 7= Start Pump Down 8= Pump Down 9= Wait For Cooling Pressure 30 10 = Brine Start Cycling 11 = Cooling Defined values for CR2-M2xx series: 0= Off, S-1 System Switch 1= Off, Manual Setpoint 2= Off, Alarm 3= Off, Pump Down Switch 4= Off, Wait For Cycle 5= Off, Ready to Start 6= Start Cooling 7= Start Pump Down 8= Pump Down 9= Pre-Purge Cycle 10 = Purge Cycle 11 = Open Solenoid Valve 12 = Low Ambient Start 13 = Cooling Circuit #2 Subcooling Temperature $049D/$049E This location contains the Subcooling Temperature in °F. The subcooling temperature is calculated by subtracting the Liquid Line Temperature from the condenser refrigerant temperature. Circuit #2 Suction Temperature $0477/$0478 This location contains the temperature, in °F, of the low-pressure vaporized refrigerant entering the compressor. Circuit #2 Superheat Temperature $0495/$0496 This location contains the Superheat Temperature in °F. The superheat temperature is calculated by subtracting the evaporator refrigerant temperature from the Suction Temperature. 31 Compressor #1 Operating Hours (High Speed) Cumulative total of high speed operating hours for compressor #1. $0862/$0863 Compressor #1 Operating Hours (Low Speed) Cumulative total of low speed operating hours for compressor #1. $09D7/$09D8 Compressor #1 Starts (High Speed) Running total of high speed starts for compressor #1. $086A/$086B Compressor #1 Starts (Low Speed) Running total of low speed starts for compressor #1. $09DF/$09E0 Compressor #2 Operating Hours (High Speed) Cumulative total of high speed operating hours for compressor #2. $0864/$0865 Compressor #2 Operating Hours (Low Speed) Cumulative total of low speed operating hours for compressor #2. $09D9/$09DA Compressor #2 Starts (High Speed) Running total of high speed starts for compressor #2. $086C/$086D Compressor #2 Starts (Low Speed) Running total of low speed starts for compressor #2. $09E1/$09E2 Version 5.0 Condenser Entering Water Temperature $0470/$0471 This location contains the temperature, in °F, of water entering the condenser. (Applies to water cooled units only.) Condenser Leaving Water Temperature $0472/$0473 This location contains the temperature, in °F, of water leaving the condenser. (Applies to water cooled units only.) Evaporator Entering Water Temperature $046E/$046F This location contains the temperature, in °F, of the chilled water entering the evaporator. Evaporator Leaving Water Temperature $0461/$0462 This location contains the temperature, in °F, of the chilled water leaving the evaporator. OAT This location contains the Outdoor Air Temperature. $047D/$047E Stage of Cooling Stage of cooling capacity at which the chiller is currently operating. Unit % RLA $0474 This location contains the percentage of Rated Load Amps being drawn by the unit. If the input from the transducer for % RLA drops below 0.1VDC, a value of 254 (decimal) will be placed in this location, in order to differentiate between noise and low current draw. Unit Status Defined values: Version 5.0 0= Off, Manual Setpoint 1= Off, S-1 System Switch 2= Off, Remote Communication 3= Off, Remote Switch 4= Off, Time Schedule 5= Off, Alarm 6= Off, Pump Down Switches 7= Off, Ready to Start 8= Starting 9= Waiting For Flow 10 = Waiting For Load 11 = Cool Stage Up 12 = Cool Stage Down 13 = Cool Staging 14 = Manual Cool Staging $0427 32 Read Only Memory Locations (CR4 Chillers) Variable Name 33 Address Range Units Circuit #1 Condenser Approach Temperature $0445 (hi byte) $0446 (lo byte) 0 to 263°F °F * 10 Circuit #1 Condenser Pressure $0467 (hi byte) $0468 (lo byte) 0-450 PSI * 10 Circuit #1 Conditions at Time of Alarm: Condenser Pressure $0993 (hi byte) $0994 (lo byte) 0-450 PSI * 10 Circuit #1 Conditions at Time of Alarm: Evaporator Pressure $0991 (hi byte) $0992 (lo byte) 0-145 PSI * 10 Circuit #1 Conditions at Time of Alarm: Liquid Line Temperature $0997 (hi byte) $0998 (lo byte) -40 to 263°F (°F+100) * 10 Circuit #1 Conditions at Time of Alarm: Suction Temperature $0995 (hi byte) $0996 (lo byte) -40 to 263°F (°F+100) * 10 Circuit #1 Current Alarm $087C 1 - 30; 129 - 158 See alarm list below Circuit #1 Evaporator Pressure $0463 (hi byte) $0464 (lo byte) 0-145 PSI * 10 Circuit #1 Liquid Line Temperature $0479 (hi byte) $047A (lo byte) -40 to 263°F (°F+100) * 10 Circuit #1 Previous Alarm $0880 1 - 27; 129 - 155 See alarm list below Circuit #1 Status $042A 0 - 13 See status list below Circuit #1 Subcooling Temperature $0440 (hi byte) $0441 (lo byte) 0 to 263°F °F * 10 Circuit #1 Suction Temperature $0475 (hi byte) $0476 (lo byte) -40 to 263°F (°F+100) * 10 Circuit #1 Superheat Temperature $04A7 (hi byte) $04A8 (lo byte) 0 to 263°F °F * 10 Circuit #2 Condenser Approach Temperature $0447 (hi byte) $0448 (lo byte) 0 to 263°F °F * 10 Circuit #2 Condenser Pressure $0469 (hi byte) $046A (lo byte) 0-450 PSI * 10 Circuit #2 Conditions at Time of Alarm: Condenser Pressure $099B (hi byte) $099C (lo byte) 0-450 PSI * 10 Circuit #2 Conditions at Time of Alarm: Evaporator Pressure $0999 (hi byte) $099A (lo byte) 0-145 PSI * 10 Circuit #2 Conditions at Time of Alarm: Liquid Line Temperature $099F (hi byte) $09A0 (lo byte) -40 to 263°F (°F+100) * 10 Circuit #2 Conditions at Time of Alarm: Suction Temperature $099D (hi byte) $099E (lo byte) -40 to 263°F (°F+100) * 10 Circuit #2 Current Alarm $087D 1 - 30; 129 - 158 See alarm list below Circuit #2 Evaporator Pressure $0465 (hi byte) $0466 (lo byte) 0-145 PSI * 10 Version 5.0 Variable Name Version 5.0 Address Range Units Circuit #2 Liquid Line Temperature $047B (hi byte) $047C (lo byte) -40 to 263°F (°F+100) * 10 Circuit #2 Previous Alarm $0881 1 - 27; 129 - 155 See alarm list below Circuit #2 Status $042D 0 - 13 See status list below Circuit #2 Subcooling Temperature $045E (hi byte) $045F (lo byte) 0 to 263°F °F * 10 Circuit #2 Suction Temperature $0477 (hi byte) $0478 (lo byte) -40 to 263°F (°F+100) * 10 Circuit #2 Superheat Temperature $04A9 (hi byte) $04AA (lo byte) 0 to 263°F °F * 10 Circuit #3 Condenser Approach Temperature $0449 (hi byte) $044A (lo byte) 0 to 263°F °F * 10 Circuit #3 Condenser Pressure $049B (hi byte) $049C (lo byte) 0-450 PSI * 10 Circuit #3 Conditions at Time of Alarm: Condenser Pressure $09A3 (hi byte) $09A4 (lo byte) 0-450 PSI * 10 Circuit #3 Conditions at Time of Alarm: Evaporator Pressure $09A1 (hi byte) $09A2 (lo byte) 0-145 PSI * 10 Circuit #3 Conditions at Time of Alarm: Liquid Line Temperature $09A7 (hi byte) $09A8 (lo byte) -40 to 263°F (°F+100) * 10 Circuit #3 Conditions at Time of Alarm: Suction Temperature $09A5 (hi byte) $09A6 (lo byte) -40 to 263°F (°F+100) * 10 Circuit #3 Current Alarm $087E 1 - 30; 129 - 158 See alarm list below Circuit #3 Evaporator Pressure $0497 (hi byte) $0498 (lo byte) 0-145 PSI * 10 Circuit #3 Liquid Line Temperature $04A3 (hi byte) $04A4 (lo byte) -40 to 263°F (°F+100) * 10 Circuit #3 Previous Alarm $0882 1 - 27; 129 - 155 See alarm list below Circuit #3 Status $042E 0 - 13 See status list below Circuit #3 Subcooling Temperature $04C7 (hi byte) $04C8 (lo byte) 0 to 263°F °F * 10 Circuit #3 Suction Temperature $049F (hi byte) $04A0 (lo byte) -40 to 263°F (°F+100) * 10 Circuit #3 Superheat Temperature $04AB (hi byte) $04AC (lo byte) 0 to 263°F °F * 10 Circuit #4 Condenser Approach Temperature $044B (hi byte) $044C (lo byte) 0 to 263°F °F * 10 Circuit #4 Condenser Pressure $049D (hi byte) $049E (lo byte) 0-450 PSI * 10 Circuit #4 Conditions at Time of Alarm: Condenser Pressure $09AB (hi byte) $09AC (lo byte) 0-450 PSI * 10 34 Variable Name 35 Address Range Units Circuit #4 Conditions at Time of Alarm: Evaporator Pressure $09A9 (hi byte) $09AA (lo byte) 0-145 PSI * 10 Circuit #4 Conditions at Time of Alarm: Liquid Line Temperature $09AF (hi byte) $09B0 (lo byte) -40 to 263°F (°F+100) * 10 Circuit #4 Conditions at Time of Alarm: Suction Temperature $09AD (hi byte) $09AE (lo byte) -40 to 263°F (°F+100) * 10 Circuit #4 Current Alarm $087F 1 - 30; 129 - 158 See alarm list below Circuit #4 Evaporator Pressure $0499 (hi byte) $049A (lo byte) 0-145 PSI * 10 Circuit #4 Liquid Line Temperature $04A5 (hi byte) $04A6 (lo byte) -40 to 263°F (°F+100) * 10 Circuit #4 Previous Alarm $0883 1 - 27; 129 - 155 See alarm list below Circuit #4 Status $042F 0 - 13 See status list below Circuit #4 Subcooling Temperature $04FD (hi byte) $04FE (lo byte) 0 to 263°F °F * 10 Circuit #4 Suction Temperature $04A1 (hi byte) $04A2 (lo byte) -40 to 263°F (°F+100) * 10 Circuit #4 Superheat Temperature $04AD (hi byte) $04AE (lo byte) 0 to 263°F °F * 10 Compressor #1 Operating Hours (High Speed) $0862 (hi byte) $0863 (lo byte) 0 - 65279 (hi byte*256) + lo byte Compressor #1 Operating Hours (Low Speed) $09D7 (hi byte) $09D8 (lo byte) 0 - 65279 (hi byte*256) + lo byte Compressor #1 Starts (High Speed) $086A (hi byte) $086B (lo byte) 0 - 65279 (hi byte*256) + lo byte Compressor #1 Starts (Low Speed) $09DF (hi byte) $09E0 (lo byte) 0 - 65279 (hi byte*256) + lo byte Compressor #2 Operating Hours (High Speed) $0864 (hi byte) $0865 (lo byte) 0 - 65279 (hi byte*256) + lo byte Compressor #2 Operating Hours (Low Speed) $09D9 (hi byte) $09DA (lo byte) 0 - 65279 (hi byte*256) + lo byte Compressor #2 Starts (High Speed) $086C (hi byte) $086D (lo byte) 0 - 65279 (hi byte*256) + lo byte Compressor #2 Starts (Low Speed) $09E1 (hi byte) $09E2 (lo byte) 0 - 65279 (hi byte*256) + lo byte Compressor #3 Operating Hours (High Speed) $0866 (hi byte) $0867 (lo byte) 0 - 65279 (hi byte*256) + lo byte Compressor #3 Operating Hours (Low Speed) $09DB (hi byte) $09DC (lo byte) 0 - 65279 (hi byte*256) + lo byte Compressor #3 Starts (High Speed) $086E (hi byte) $086F (lo byte) 0 - 65279 (hi byte*256) + lo byte Compressor #3 Starts (Low Speed) $09E3 (hi byte) $09E4 (lo byte) 0 - 65279 (hi byte*256) + lo byte Version 5.0 Variable Name Address Range Units Compressor #4 Operating Hours (High Speed) $0868 (hi byte) $0869 (lo byte) 0 - 65279 (hi byte*256) + lo byte Compressor #4 Operating Hours (Low Speed) $09DD (hi byte) $09DE (lo byte) 0 - 65279 (hi byte*256) + lo byte Compressor #4 Starts (High Speed) $0870 (hi byte) $0871 (lo byte) 0 - 65279 (hi byte*256) + lo byte Compressor #4 Starts (Low Speed) $09E5 (hi byte) $09E6 (lo byte) 0 - 65279 (hi byte*256) + lo byte Condenser Entering Water Temperature $0470 (hi byte) $0471 (lo byte) -40 to 263°F (°F+100) * 10 Condenser Leaving Water Temperature $0472 (hi byte) $0473 (lo byte) -40 to 263°F (°F+100) * 10 Evaporator Entering Water Temperature $046E (hi byte) $046F (lo byte) -40 to 263°F (°F+100) * 10 Evaporator Leaving Water Temperature $0461 (hi byte) $0462 (lo byte) -40 to 263°F (°F+100) * 10 OAT $047D (hi byte) $047E (lo byte) -40 to 263°F (°F+100) * 10 Stage of Cooling $042B 0-8 Unit % RLA $0474 0 - 100 Percent Unit Status $0427 0 - 14 See unit status list below Note: For notes on alarms and alarm related data, temperatures, pressures, compressor operating hours and starts, see Appendix A. Circuit #1 Condenser Approach Temperature $0445/$0446 This location contains the Condenser Approach Temperature in °F. The approach temperature is calculated by subtracting the Condenser Leaving Water Temperature from the condenser refrigerant temperature. Circuit #1 Condenser Pressure Measured pressure in circuit #1 condenser. $0467/$0468 Circuit #1 Conditions at Time of Alarm: Condenser Pressure Condenser pressure at time of circuit #1 alarm occurrence. $0993/$0994 Circuit #1 Conditions at Time of Alarm: Evaporator Pressure Evaporator pressure at time of circuit #1 alarm occurrence. $0991/$0992 Circuit #1 Conditions at Time of Alarm: Liquid Line Temperature Measured temperature in circuit #1 liquid line at time of alarm occurrence. $0997/$0998 Circuit #1 Conditions at Time of Alarm: Suction Temperature Measured temperature in circuit #1 suction line at time of alarm occurrence. $0995/$0996 Circuit #1 Current Alarm Defined values for CR4-M1xx series: Version 5.0 $087C Alarm Name Cleared Active Hi Condenser Pre-Alarm Hold Stage 1 129 Hi Condenser Pre-Alarm Stage Down 2 130 Freeze Refrigerant Pre-Alarm Stage Down 3 131 36 Alarm Name Cleared Active Loss Of Chilled Water Flow 4 132 No Pump Down 5 133 Refrigerant Freeze Protect 6 134 Low Evap Pressure 7 135 Comp4 Thermal Overload 8 136 Comp3 Thermal Overload 9 137 Comp2 Thermal Overload 10 138 Comp1 Thermal Overload 11 139 Comp4 Motor Protect 12 140 Comp3 Motor Protect 13 141 Comp2 Motor Protect 14 142 Comp1 Motor Protect 15 143 Comp4 Low Oil Pressure 16 144 Comp3 Low Oil Pressure 17 145 Comp2 Low Oil Pressure 18 146 Comp1 Low Oil Pressure 19 147 High Cond Pressure 20 148 Mech. High Pressure 21 149 Bad Evap Pressure Sensor 22 150 Bad Cond Pressure Sensor 23 151 Bad Phase/Volts 24 152 Chilled Water Freeze Protect 25 153 Bad Voltage Ratio Sensor 26 154 Bad Evap Lvg T Sensor 27 155 Defined values for CR4-M2xx series: 37 Alarm Name Cleared Active Compressor Warning 128 Hi Condenser Pre-Alarm Hold Stage 1 129 Hi Condenser Pre-Alarm Stage Down 2 130 Freeze Refrigerant Pre-Alarm Stage Down 3 131 Loss Of Chilled Water Flow 4 132 No Pump Down 5 133 Low Evap Press: No Start 6 134 Failed Pre-Purge 7 135 Failed Low Ambient Start 8 136 Low Evap Pressure 9 137 Refrigerant Freeze Protect 10 138 Comp4 Bad Suction Temp Sensor/Thermal Overload 11 139 Comp3 Bad Suction Temp Sensor/Thermal Overload 12 140 Comp2 Bad Suction Temp Sensor/Thermal Overload 13 141 Version 5.0 Alarm Name Cleared Active Comp1 Bad Suction Temp Sensor/Thermal Overload 14 142 Comp4 Motor Protect/Very Low Pressure 15 143 Comp3 Motor Protect/Very Low Pressure 16 144 Comp2 Motor Protect/Very Low Pressure 17 145 Comp1 Motor Protect/Very Low Pressure 18 146 Comp4 Low Oil Pressure 19 147 Comp3 Low Oil Pressure 20 148 Comp2 Low Oil Pressure 21 149 Comp1 Low Oil Pressure 22 150 High Cond Pressure 23 151 Mech. High Pressure 24 152 Bad Evap Pressure Sensor 25 153 Bad Cond Pressure Sensor 26 154 System Alarm/Bad Phase/Volts 27 155 Chilled Water Freeze Protect 28 156 Bad Voltage Ratio Sensor 29 157 Bad Evap Lvg T Sensor 30 158 A value of zero indicates "no alarm." Circuit #1 Evaporator Pressure Measured pressure in circuit #1 evaporator. $0463/$0464 Circuit #1 Liquid Line Temperature $0479/$047A This location contains the temperature, in °F, of the liquid refrigerant entering the expansion valve. Version 5.0 38 Circuit #1 Previous Alarm See list for circuit #1 Current Alarm, above. $0880 Circuit #1 Status Defined values for CR4-M1xx series: $042A 0= Off, S-1 System Switch 1= Off, Manual Setpoint 2= Off, Alarm 3= Off, Pump Down Switch 4= Off, Wait For Cycle 5= Off, Ready to Start 6= Start Cooling 7= Start Pump Down 8= Pump Down 9= Wait For Cooling Pressure 10 = Brine Start Cycling 11 = Cooling Defined values for CR4-M2xx series: 0= Off, S-1 System Switch 1= Off, Manual Setpoint 2= Off, Alarm 3= Off, Pump Down Switch 4= Off, Wait For Cycle 5= Off, Ready to Start 6= Start Cooling 7= Start Pump Down 8= Pump Down 9= Pre-Purge Cycle 10 = Purge Cycle 11 = Open Solenoid Valve 12 = Low Ambient Start 13 = Cooling Circuit #1 Subcooling Temperature $0440/$0441 This location contains the Subcooling Temperature in °F. The subcooling temperature is calculated by subtracting the Liquid Line Temperature from the condenser refrigerant temperature. Circuit #1 Suction Temperature $0475/$0476 This location contains the temperature, in °F, of the low-pressure vaporized refrigerant entering the compressor. Circuit #1 Superheat Temperature $04A7/$04A8 This location contains the Superheat Temperature in °F. The superheat temperature is calculated by subtracting the evaporator refrigerant temperature from the Suction Temperature. 39 Version 5.0 Circuit #2 Condenser Approach Temperature $0447/$044B This location contains the Condenser Approach Temperature in °F. The approach temperature is calculated by subtracting the Condenser Leaving Water Temperature from the condenser refrigerant temperature. Circuit #2 Condenser Pressure Measured pressure in circuit #2 condenser. $0469/$046A Circuit #2 Conditions at Time of Alarm: Condenser Pressure Condenser pressure at time of circuit #2 alarm occurrence. $099B/$099C Circuit #2 Conditions at Time of Alarm: Evaporator Pressure Evaporator pressure at time of circuit #2 alarm occurrence. $0999/$099A Circuit #2 Conditions at Time of Alarm: Liquid Line Temperature Measured temperature in circuit #2 liquid line at time of alarm occurrence. $099F/$09A0 Circuit #2 Conditions at Time of Alarm: Suction Temperature Measured temperature in circuit #2 suction line at time of alarm occurrence. $099D/$099E Circuit #2 Current Alarm Defined values for CR4-M1xx series: Version 5.0 $087D Alarm Name Cleared Active Hi Condenser Pre-Alarm Hold Stage 1 129 Hi Condenser Pre-Alarm Stage Down 2 130 Freeze Refrigerant Pre-Alarm Stage Down 3 131 Loss Of Chilled Water Flow 4 132 No Pump Down 5 133 Refrigerant Freeze Protect 6 134 Low Evap Pressure 7 135 Comp4 Thermal Overload 8 136 Comp3 Thermal Overload 9 137 Comp2 Thermal Overload 10 138 Comp1 Thermal Overload 11 139 Comp4 Motor Protect 12 140 Comp3 Motor Protect 13 141 Comp2 Motor Protect 14 142 Comp1 Motor Protect 15 143 Comp4 Low Oil Pressure 16 144 Comp3 Low Oil Pressure 17 145 Comp2 Low Oil Pressure 18 146 Comp1 Low Oil Pressure 19 147 High Cond Pressure 20 148 Mech. High Pressure 21 149 Bad Evap Pressure Sensor 22 150 Bad Cond Pressure Sensor 23 151 Bad Phase/Volts 24 152 Chilled Water Freeze Protect 25 153 40 Alarm Name Cleared Active Bad Voltage Ratio Sensor 26 154 Bad Evap Lvg T Sensor 27 155 Defined values for CR4-M2xx series: Alarm Name Cleared Active Compressor Warning 128 Hi Condenser Pre-Alarm Hold Stage 1 129 Hi Condenser Pre-Alarm Stage Down 2 130 Freeze Refrigerant Pre-Alarm Stage Down 3 131 Loss Of Chilled Water Flow 4 132 No Pump Down 5 133 Low Evap Press: No Start 6 134 Failed Pre-Purge 7 135 Failed Low Ambient Start 8 136 Low Evap Pressure 9 137 Refrigerant Freeze Protect 10 138 Comp4 Bad Suction Temp Sensor/Thermal Overload 11 139 Comp3 Bad Suction Temp Sensor/Thermal Overload 12 140 Comp2 Bad Suction Temp Sensor/Thermal Overload 13 141 Comp1 Bad Suction Temp Sensor/Thermal Overload 14 142 Comp4 Motor Protect/Very Low Pressure 15 143 Comp3 Motor Protect/Very Low Pressure 16 144 Comp2 Motor Protect/Very Low Pressure 17 145 Comp1 Motor Protect/Very Low Pressure 18 146 Comp4 Low Oil Pressure 19 147 Comp3 Low Oil Pressure 20 148 Comp2 Low Oil Pressure 21 149 Comp1 Low Oil Pressure 22 150 High Cond Pressure 23 151 Mech. High Pressure 24 152 Bad Evap Pressure Sensor 25 153 Bad Cond Pressure Sensor 26 154 System Alarm/Bad Phase/Volts 27 155 Chilled Water Freeze Protect 28 156 Bad Voltage Ratio Sensor 29 157 Bad Evap Lvg T Sensor 30 158 A value of zero indicates "no alarm." Circuit #2 Evaporator Pressure Measured pressure in circuit #2 evaporator. 41 $0465/$0466 Version 5.0 Circuit #2 Liquid Line Temperature $047B/$047C This location contains the temperature, in °F, of the liquid refrigerant entering the expansion valve. Circuit #2 Previous Alarm See list for circuit #2 Current Alarm, above. $0881 Circuit #2 Status Defined values for CR4-M1xx series: $042D 0= Off, S-1 System Switch 1= Off, Manual Setpoint 2= Off, Alarm 3= Off, Pump Down Switch 4= Off, Wait For Cycle 5= Off, Ready to Start 6= Start Cooling 7= Start Pump Down 8= Pump Down 9= Wait For Cooling Pressure 10 = Brine Start Cycling 11 = Cooling Defined values for CR4-M2xx series: 0= Off, S-1 System Switch 1= Off, Manual Setpoint 2= Off, Alarm 3= Off, Pump Down Switch 4= Off, Wait For Cycle 5= Off, Ready to Start 6= Start Cooling 7= Start Pump Down 8= Pump Down 9= Pre-Purge Cycle 10 = Purge Cycle 11 = Open Solenoid Valve 12 = Low Ambient Start 13 = Cooling Circuit #2 Subcooling Temperature $045E/$045F This location contains the Subcooling Temperature in °F. The subcooling temperature is calculated by subtracting the Liquid Line Temperature from the condenser refrigerant temperature. Circuit #2 Suction Temperature $0477/$0478 This location contains the temperature, in °F, of the low-pressure vaporized refrigerant entering the compressor. Circuit #2 Superheat Temperature $04A9/$04AA This location contains the Superheat Temperature in °F. The superheat temperature is calculated by subtracting the evaporator refrigerant temperature from the Suction Temperature. Version 5.0 42 Circuit #3 Condenser Approach Temperature $0449/$044A This location contains the Condenser Approach Temperature in °F. The approach temperature is calculated by subtracting the Condenser Leaving Water Temperature from the condenser refrigerant temperature. Circuit #3 Condenser Pressure Measured pressure in circuit #3 condenser $049B/$049C Circuit #3 Conditions at Time of Alarm: Condenser Pressure Condenser pressure at time of circuit #3 alarm occurrence. $09A3/$09A4 Circuit #3 Conditions at Time of Alarm: Evaporator Pressure Evaporator pressure at time of circuit #3 alarm occurrence. $09A1/$09A2 Circuit #3 Conditions at Time of Alarm: Liquid Line Temperature Measured temperature in circuit #3 liquid line at time of alarm occurrence. $09A7/$09A8 Circuit #3 Conditions at Time of Alarm: Suction Temperature Measured temperature in circuit #3 suction line at time of alarm occurrence. $09A5/$09A6 Circuit #3 Current Alarm Defined values for CR4-M1xx series: 43 $087E Alarm Name Cleared Active Hi Condenser Pre-Alarm Hold Stage 1 129 Hi Condenser Pre-Alarm Stage Down 2 130 Freeze Refrigerant Pre-Alarm Stage Down 3 131 Loss Of Chilled Water Flow 4 132 No Pump Down 5 133 Refrigerant Freeze Protect 6 134 Low Evap Pressure 7 135 Comp4 Thermal Overload 8 136 Comp3 Thermal Overload 9 137 Comp2 Thermal Overload 10 138 Comp1 Thermal Overload 11 139 Comp4 Motor Protect 12 140 Comp3 Motor Protect 13 141 Comp2 Motor Protect 14 142 Comp1 Motor Protect 15 143 Comp4 Low Oil Pressure 16 144 Comp3 Low Oil Pressure 17 145 Comp2 Low Oil Pressure 18 146 Comp1 Low Oil Pressure 19 147 High Cond Pressure 20 148 Mech. High Pressure 21 149 Bad Evap Pressure Sensor 22 150 Bad Cond Pressure Sensor 23 151 Bad Phase/Volts 24 152 Chilled Water Freeze Protect 25 153 Bad Voltage Ratio Sensor 26 154 Version 5.0 Alarm Name Cleared Active Bad Evap Lvg T Sensor 27 155 Defined values for CR4-M2xx series: Alarm Name Cleared Active Hi Condenser Pre-Alarm Hold Stage 1 129 Hi Condenser Pre-Alarm Stage Down 2 130 Freeze Refrigerant Pre-Alarm Stage Down 3 131 Loss Of Chilled Water Flow 4 132 No Pump Down 5 133 Low Evap Press: No Start 6 134 Failed Pre-Purge 7 135 Failed Low Ambient Start 8 136 Low Evap Pressure 9 137 Refrigerant Freeze Protect 10 138 Comp4 Bad Suction Temp Sensor/Thermal Overload 11 139 Comp3 Bad Suction Temp Sensor/Thermal Overload 12 140 Comp2 Bad Suction Temp Sensor/Thermal Overload 13 141 Comp1 Bad Suction Temp Sensor/Thermal Overload 14 142 Comp4 Motor Protect/Very Low Pressure 15 143 Comp3 Motor Protect/Very Low Pressure 16 144 Comp2 Motor Protect/Very Low Pressure 17 145 Comp1 Motor Protect/Very Low Pressure 18 146 Comp4 Low Oil Pressure 19 147 Comp3 Low Oil Pressure 20 148 Comp2 Low Oil Pressure 21 149 Comp1 Low Oil Pressure 22 150 High Cond Pressure 23 151 Mech. High Pressure 24 152 Bad Evap Pressure Sensor 25 153 Bad Cond Pressure Sensor 26 154 System Alarm/Bad Phase/Volts 27 155 Chilled Water Freeze Protect 28 156 Bad Voltage Ratio Sensor 29 157 Bad Evap Lvg T Sensor 30 158 A value of zero indicates "no alarm." Circuit #3 Evaporator Pressure Measured pressure in circuit #3 evaporator. $0497/$0498 Circuit #3 Liquid Line Temperature $04A3/$04A4 This location contains the temperature, in °F, of the liquid refrigerant entering the expansion valve. Version 5.0 44 Circuit #3 Previous Alarm See list for circuit #3 Current Alarm, above. $0882 Circuit #3 Status Defined values for CR4-M1xx series: $042E 0= Off, S-1 System Switch 1= Off, Manual Setpoint 2= Off, Alarm 3= Off, Pump Down Switch 4= Off, Wait For Cycle 5= Off, Ready to Start 6= Start Cooling 7= Start Pump Down 8= Pump Down 9= Wait For Cooling Pressure 10 = Brine Start Cycling 11 = Cooling Defined values for CR4-M2xx series: 0= Off, S-1 System Switch 1= Off, Manual Setpoint 2= Off, Alarm 3= Off, Pump Down Switch 4= Off, Wait For Cycle 5= Off, Ready to Start 6= Start Cooling 7= Start Pump Down 8= Pump Down 9= Pre-Purge Cycle 10 = Purge Cycle 11 = Open Solenoid Valve 12 = Low Ambient Start 13 = Cooling Circuit #3 Subcooling Temperature $04C7/$04C8 This location contains the Subcooling Temperature in °F. The subcooling temperature is calculated by subtracting the Liquid Line Temperature from the condenser refrigerant temperature. Circuit #3 Suction Temperature $049F/$04A0 This location contains the temperature, in °F, of the low-pressure vaporized refrigerant entering the compressor. Circuit #3 Superheat Temperature $04AB/$04AC This location contains the Superheat Temperature in °F. The superheat temperature is calculated by subtracting the evaporator refrigerant temperature from the Suction Temperature. 45 Version 5.0 Circuit #4 Condenser Approach Temperature $044B/$044C This location contains the Condenser Approach Temperature in °F. The approach temperature is calculated by subtracting the Condenser Leaving Water Temperature from the condenser refrigerant temperature. Circuit #4 Condenser Pressure Measured pressure in circuit #4 condenser. $049D/$049E Circuit #4 Conditions at Time of Alarm: Condenser Pressure Condenser pressure at time of circuit #4 alarm occurrence. $09AB/$09AC Circuit #4 Conditions at Time of Alarm: Evaporator Pressure Evaporator pressure at time of circuit #4 alarm occurrence. $09A9/$09AA Circuit #4 Conditions at Time of Alarm: Liquid Line Temperature Measured temperature in circuit #4 liquid line at time of alarm occurrence. $09AF/$09B0 Circuit #4 Conditions at Time of Alarm: Suction Temperature Measured temperature in circuit #4 suction line at time of alarm occurrence. $09AD/$09AE Circuit #4 Current Alarm Defined values for CR4-M1xx series: Version 5.0 $087F Alarm Name Cleared Active Hi Condenser Pre-Alarm Hold Stage 1 129 Hi Condenser Pre-Alarm Stage Down 2 130 Freeze Refrigerant Pre-Alarm Stage Down 3 131 Loss Of Chilled Water Flow 4 132 No Pump Down 5 133 Refrigerant Freeze Protect 6 134 Low Evap Pressure 7 135 Comp4 Thermal Overload 8 136 Comp3 Thermal Overload 9 137 Comp2 Thermal Overload 10 138 Comp1 Thermal Overload 11 139 Comp4 Motor Protect 12 140 Comp3 Motor Protect 13 141 Comp2 Motor Protect 14 142 Comp1 Motor Protect 15 143 Comp4 Low Oil Pressure 16 144 Comp3 Low Oil Pressure 17 145 Comp2 Low Oil Pressure 18 146 Comp1 Low Oil Pressure 19 147 High Cond Pressure 20 148 Mech. High Pressure 21 149 Bad Evap Pressure Sensor 22 150 Bad Cond Pressure Sensor 23 151 Bad Phase/Volts 24 152 Chilled Water Freeze Protect 25 153 Bad Voltage Ratio Sensor 26 154 46 Alarm Name Cleared Active Bad Evap Lvg T Sensor 27 155 Defined values for CR4-M2xx series: Alarm Name Cleared Active Hi Condenser Pre-Alarm Hold Stage 1 129 Hi Condenser Pre-Alarm Stage Down 2 130 Freeze Refrigerant Pre-Alarm Stage Down 3 131 Loss Of Chilled Water Flow 4 132 No Pump Down 5 133 Low Evap Press: No Start 6 134 Failed Pre-Purge 7 135 Failed Low Ambient Start 8 136 Low Evap Pressure 9 137 Refrigerant Freeze Protect 10 138 Comp4 Bad Suction Temp Sensor/Thermal Overload 11 139 Comp3 Bad Suction Temp Sensor/Thermal Overload 12 140 Comp2 Bad Suction Temp Sensor/Thermal Overload 13 141 Comp1 Bad Suction Temp Sensor/Thermal Overload 14 142 Comp4 Motor Protect/Very Low Pressure 15 143 Comp3 Motor Protect/Very Low Pressure 16 144 Comp2 Motor Protect/Very Low Pressure 17 145 Comp1 Motor Protect/Very Low Pressure 18 146 Comp4 Low Oil Pressure 19 147 Comp3 Low Oil Pressure 20 148 Comp2 Low Oil Pressure 21 149 Comp1 Low Oil Pressure 22 150 High Cond Pressure 23 151 Mech. High Pressure 24 152 Bad Evap Pressure Sensor 25 153 Bad Cond Pressure Sensor 26 154 System Alarm/Bad Phase/Volts 27 155 Chilled Water Freeze Protect 28 156 Bad Voltage Ratio Sensor 29 157 Bad Evap Lvg T Sensor 30 158 A value of zero indicates "no alarm." Circuit #4 Evaporator Pressure Measured pressure in circuit #4 evaporator. $0499/$049A Circuit #4 Liquid Line Temperature $04A5/$04A6 This location contains the temperature, in °F, of the liquid refrigerant entering the expansion valve. 47 Version 5.0 Circuit #4 Previous Alarm See list for circuit #4 Current Alarm, above. $0883 Circuit #4 Status Defined values for CR4-M1xx series: $042F 0= Off, S-1 System Switch 1= Off, Manual Setpoint 2= Off, Alarm 3= Off, Pump Down Switch 4= Off, Wait For Cycle 5= Off, Ready to Start 6= Start Cooling 7= Start Pump Down 8= Pump Down 9= Wait For Cooling Pressure 10 = Brine Start Cycling 11 = Cooling Defined values for CR4-M2xx series: 0= Off, S-1 System Switch 1= Off, Manual Setpoint 2= Off, Alarm 3= Off, Pump Down Switch 4= Off, Wait For Cycle 5= Off, Ready to Start 6= Start Cooling 7= Start Pump Down 8= Pump Down 9= Pre-Purge Cycle 10 = Purge Cycle 11 = Open Solenoid Valve 12 = Low Ambient Start 13 = Cooling Circuit #4 Subcooling Temperature $04FD/$04FE This location contains the Subcooling Temperature in °F. The subcooling temperature is calculated by subtracting the Liquid Line Temperature from the condenser refrigerant temperature. Circuit #4 Suction Temperature $04A1/$04A2 This location contains the temperature, in °F, of the low-pressure vaporized refrigerant entering the compressor. Circuit #4 Superheat Temperature $04AD/$04AE This location contains the Superheat Temperature in °F. The superheat temperature is calculated by subtracting the evaporator refrigerant temperature from the Suction Temperature. Compressor #1 Operating Hours (High Speed) Cumulative total of high speed operating hours for compressor #1. Version 5.0 $0862/$0863 48 Compressor #1 Operating Hours (Low Speed) Cumulative total of low speed operating hours for compressor #1. $09D7/$09D8 Compressor #1 Starts (High Speed) Running total of high speed starts for compressor #1. $086A/$086B Compressor #1 Starts (Low Speed) Running total of low speed starts for compressor #1. $09DF/$09E0 Compressor #2 Operating Hours (High Speed) Cumulative total of high speed operating hours for compressor #2. $0864/$0865 Compressor #2 Operating Hours (Low Speed) Cumulative total of low speed operating hours for compressor #2. $09D9/$09DA Compressor #2 Starts (High Speed) Running total of high speed starts for compressor #2. $086C/$086D Compressor #2 Starts (Low Speed) Running total of low speed starts for compressor #2. $09E1/$09E2 Compressor #3 Operating Hours (High Speed) Cumulative total of high speed operating hours for compressor #3. $0866/$0867 Compressor #3 Operating Hours (Low Speed) Cumulative total of low speed operating hours for compressor #3. $09DB/$09DC Compressor #3 Starts (High Speed) Running total of high speed starts for compressor #3. $086E/$086F Compressor #3 Starts (Low Speed) Running total of low speed starts for compressor #3. $09E3/$09E4 Compressor #4 Operating Hours (High Speed) Cumulative total of high speed operating hours for compressor #4. $0868/$0869 Compressor #4 Operating Hours (Low Speed) Cumulative total of low speed operating hours for compressor #4. $09DD/$09DE Compressor #4 Starts (High Speed) Running total of high speed starts for compressor #4. $0870/$0871 Compressor #4 Starts (Low Speed) Running total of low speed starts for compressor #4. $09E5/$09E6 Condenser Entering Water Temperature $0470/$0471 This location contains the temperature, in °F, of water entering the condenser. (Applies to water cooled units only.) Condenser Leaving Water Temperature $0472/$0473 This location contains the temperature, in °F, of water leaving the condenser. (Applies to water cooled units only.) Evaporator Entering Water Temperature $046E/$046F This location contains the temperature, in °F, of the chilled water entering the evaporator. Evaporator Leaving Water Temperature $0461/$0462 This location contains the temperature, in °F, of the chilled water leaving the evaporator. OAT This location contains the Outdoor Air Temperature. $047D/$047E Stage of Cooling Stage of cooling capacity at which the chiller is currently operating. 49 Version 5.0 Unit % RLA $0474 This location contains the percentage of Rated Load Amps being drawn by the unit. If the input from the transducer for % RLA drops below 0.1VDC, a value of 254 (decimal) will be placed in this location, in order to differentiate between noise and low current draw. Unit Status Defined values: Version 5.0 0= Off, Manual Setpoint 1= Off, S-1 System Switch 2= Off, Remote Communication 3= Off, Remote Switch 4= Off, Time Schedule 5= Off, Alarm 6= Off, Pump Down Switches 7= Off, Ready to Start 8= Starting 9= Waiting For Flow 10 = Waiting For Load 11 = Cool Stage Up 12 = Cool Stage Down 13 = Cool Staging 14 = Manual Cool Staging $0427 50 Read and Write Memory Locations Memory locations common to all types of chillers - CR1, CR2, and CR4 Variable Name Address Range Units Network Command $044F 0-1 0 = Enable 1 = Disable Network Demand Limit $044D 0 - 100% Percent Network Evaporator Leaving Chilled Water Temperature Reset $044E 0 - 100% Percent Network Command $044F The Network Command is a way to disable the chiller through the Open Protocol interface. If all other enable/disable features are in the "enabled" position, writing a "1" to the Network Command memory location will disable the chiller. If any of the enable/disable features is in the "disabled" position, the Network Command will have no effect. The memory for Network Command is a RAM location that, upon loss and subsequent restoration of power, is initialized to "Enable." Network Demand Limit $044D The chiller can be Demand Limited two ways - either by a hardwired 4 - 20 mA signal or by network communications. Here is the formula: [ ] ( C − 1) × ( % S + % N ) + 50 C− 100 Where: C = Number of cooling stages S = 4 - 20 mA range in percent N = Network range in percent Example 1: If there are eight cooling stages, and "50" has been written to the Network Demand Limit. (No external 4 - 20 mA signal is wired). [ ] ( 8 − 1) × ( 0 + 50) + 50 8− 100 [ 7 × 50] + 50 8− = 4 stages Maximum Limit 100 Example 2: If there are eight cooling stages, the input from the 4 - 20 signal is 8 mA and the Network Demand Limit is zero. [ ] ( 8 − 1) × ( 25 + 0) + 50 8− 100 [ 7 × 25] + 50 8− = 6 stages Maximum Limit 100 51 Version 5.0 Network Evaporator Leaving Chilled Water Temperature Reset $044E This location contains the percentage of chilled water temperature reset to be performed when Network Chilled Water Reset is selected as the Reset Option Setpoint. Memory locations applicable only to CR1 and CR2 chillers Variable Name Address Range Units Clear Circuit #1 Alarm $091A 0-1 Clear Circuit #2 Alarm $091B 0-1 Evaporator Entering Water Temperature Setpoint $090D 30 - 160 (15°F 80°F) °F * 2 Evaporator Leaving Water Temperature Setpoint $0905 20 - 160 (10°F 80°F) °F * 2 Maximum Chilled Water Reset Setpoint $090C 0 - 90 (0°F 45°F) °F * 2 Reset Option Setpoint $090B 0-4 Clear Circuit #1 Alarm 1 = Clear Active Alarm 0 = Do Nothing $091A Memory location will change to zero when alarm is cleared. Clear Circuit #2 Alarm 1 = Clear Active Alarm 0 = Do Nothing $091B Memory location will change to zero when alarm is cleared. Evaporator Entering Water Temperature Setpoint $090D Temperature setpoints are not stored as direct representations of a temperature. They are stored as temperature * 2. This will in effect allow temperatures to be specified in 0.5°F increments. Example: 54.5°F is stored as 109 decimal. Default value of Evaporator Entering Water Temperature Setpoint is 108 (54°F). Version 5.0 Evaporator Leaving Water Temperature Setpoint Default value of Evaporator Leaving Water Temperature Setpoint is 88 (44°F). $0905 Maximum Chilled Water Reset Setpoint Default value of Maximum Chilled Water Reset Setpoint is 20 (10°F). $090C Reset Option Setpoint Possible values: $090B 0= No Chilled Water Reset (default) 1= Return Chilled Water Reset (see I&M) 2= 4 - 20 mA Chilled Water Reset 3= Network Chilled Water Reset 4= Ice Chilled Water Reset (see I&M) 52 To reset from a hardwired 4 - 20 mA signal, write "2" to $090B. The chilled water supply temperature will then be controlled from a range of 44°F (Evaporator Leaving Water Setpoint) to 54°F [Maximum Chilled Water Temperature Reset Setpoint (10°F) plus the Evaporator Leaving Water Temperature Setpoint (44°F)]. At 4 mA or below, the temperature setpoint will be 44°F. At 20mA, the temperature setpoint will be 54°F. To reset through communication, write "3" to $090B. The chilled water supply temperature will then be controlled from a range of 44°F (Evaporator Leaving Water Setpoint) to 54°F [Maximum Chilled Water Temperature Reset (10°F) + Evaporator Leaving Water Temperature Setpoint (44°F)]. You may write 0 through 100 (% reset) to the Network Evaporator Leaving Reset. If you write a "0," the temperature setpoint will be 44°F. If you write a "100," the temperature setpoint will be 54°F. Memory locations applicable only to CR4 chillers Variable Name Address Range Units Clear Circuit #1 Alarm $097F 0-1 Clear Circuit #2 Alarm $0980 0-1 Clear Circuit #3 Alarm $0981 0-1 Clear Circuit #4 Alarm $0982 0-1 Evaporator Entering Water Temperature Setpoint $091C 30 - 160 (15°F 80°F) °F * 2 Evaporator Leaving Water Temperature Setpoint $0909 20 - 160 (10°F 80°F) °F * 2 Maximum Chilled Water Reset Setpoint $091B 0 - 90 (0°F 45°F) °F * 2 Reset Option Setpoint $091A 0-4 Clear Circuit #1 Alarm 1 = Clear Active Alarm 0 = Do Nothing $097F Memory location will change to zero when alarm is cleared. Clear Circuit #2 Alarm 1 = Clear Active Alarm 0 = Do Nothing $0980 Memory location will change to zero when alarm is cleared. Clear Circuit #3 Alarm 1 = Clear Active Alarm 0 = Do Nothing $0981 Memory location will change to zero when alarm is cleared. Clear Circuit #4 Alarm 1 = Clear Active Alarm 0 = Do Nothing $0982 Memory location will change to zero when alarm is cleared. Evaporator Entering Water Temperature Setpoint $091C Temperature setpoints are not stored as direct representations of a temperature. They are stored as temperature * 2. This will in effect allow temperatures to be specified in 0.5°F increments. Example: 54.5°F is stored as 109 decimal. 53 Version 5.0 Default value of Evaporator Entering Water Temperature Setpoint is 108 (54°F). Evaporator Leaving Water Temperature Setpoint Default value of Evaporator Leaving Water Temperature Setpoint is 88 (44°F). $0909 Maximum Chilled Water Reset Setpoint Default value of Maximum Chilled Water Reset Setpoint is 20 (10°F). $091B Reset Option Setpoint Possible values: $091A 0= No Chilled Water Reset (default) 1= Return Chilled Water Reset (see I&M) 2= 4 - 20 mA Chilled Water Reset 3= Network Chilled Water Reset 4= Ice Chilled Water Reset (see I&M) To reset from a hardwired 4 - 20 mA signal, write "2" to $091A. The chilled water supply temperature will then be controlled from a range of 44°F (Evaporator Leaving Water Setpoint) to 54°F [Maximum Chilled Water Temperature Reset Setpoint (10°F) plus the Evaporator Leaving Water Temperature Setpoint (44°F)]. At 4 mA or below, the temperature setpoint will be 44°F. At 20 mA the temperature setpoint will be 54°F. To reset through communication, write "3" to $091A. The chilled water supply temperature will then be controlled from a range of 44°F (Evaporator Leaving Water Setpoint) to 54°F [Maximum Chilled Water Temperature Reset (10°F) + Evaporator Leaving Water Temperature Setpoint (44°F)]. You may write 0 through 100 (% reset) to the Network Evaporator Leaving Reset. If you write a "0," the temperature setpoint will be 44°F. If you write a "100," the temperature setpoint will be 54°F. Version 5.0 54 Reciprocating Chiller Simulator Package Required Development Testing Tools To develop and test an Open Protocol interface for the reciprocating chillers, the following is required. 1. McQuay "Open Protocol Data Communications" document (version 1.3 dated Nov. 23, 1992 or latest update). 2. McQuay Open Protocol Hardware Simulators Package includes: (1) Model 250 (2) Model 125's (1) Model 120 (1) Power supply with power cord and adapter cables. (1) RS-232 Communications Cable package (1) RS-485 Communication Cable package 3. Open Protocol Simulator Monitor software for the reciprocating chiller (P/N 950451-010) 4. Monitor Program Users Manual. Setup of Hardware for Testing One setup that is particularly helpful for proving out an Open Protocol interface is shown below. In this arrangement, the Open Protocol interface is operational on Port A and the McQuay Monitor program is operational on Port B. Level 1 AWR A TCC Comm. Device B (9600 Baud) Level 2 "Monitor" Software The procedure for setting up this network arrangement is as follows: 55 Version 5.0 1. 2. 3. 4. 5. 6. 7. Install the Open Protocol Simulator Monitor software on your PC. To install, simply insert the diskette into one of your floppy drives and type "install." The install program will prompt you through its installation. Set the hex address switches on the Model 250 controller to Hi = F, and Lo = F. (This forces Port A to 1200 Baud TTY and Port B to 9600 Baud TTY.) Connect the RS-232 communications cable to Port B on the 250 controller. Power the 250 controller. Invoke the monitor program by typing "Run" at the DOS command prompt. Establish communications with the controller (monitor program should connect at 9600 baud). See the Monitor Program Users Manual for more details on using the monitor program. Download to the controller the chiller simulator control code. The options for this simulator code are: "ARE12BO0.COD" - For Group 1 chillers "CR215AO0.COD" - For Group 2 CR2 Chillers "CR415AO0.COD" - For Group 3 CR4 Chillers Note the download procedure may prompt you that port configurations are being changed; this is O.K. Press <Enter> to continue. Also note that the controller is assumed to have all password memory locations set to F. When download is completed, restart the controller as prompted by the monitor program. The monitor program should prompt "restart successful." De-power the controller and set the hex address switches to Hi = 0 and Lo = 1. Re-power the controller and establish communications with the monitor program. 8. The simulator code by default has Port A set to 9600 baud TTY and Port B set to 9600 Baud TTY. The TCC device should now be able to communicate at 9600 baud on Port A and Port B. Select the chiller "WHR4I" as a start since, because this chiller has four compressors, it contains nearly all the Open Protocol data points. With both ports communicating, it is possible to read and write memory locations simultaneously through the monitor program on Port B and TTC device on Port B. The testing method should read every memory location from the TTC device and make sure it agrees with the McQuay Monitor program screens. Most of the Open Protocol memory locations are found on screens 1, 2, and 3 of the chiller being tested. For sample printouts of the various screens available in the monitor program, see Appendix B. If you wish to change the type of chiller being tested, go to Page 4 of any chiller selection and change the "Unit Configuration" to the unit desired. Then select the corresponding unit from the Unit Selection screen. Version 5.0 56 Appendix A - Notes on Read Only Memory Locations Note on Alarms and Alarm Related Data Individual alarms are represented as non-zero values in the memory locations as described in previous chapters. Values less than 128 decimal represent cleared alarms and values greater than 128 are active alarms. Zero indicates no alarm. Note on Temperatures To read temperature, you must read two separate bytes of information from the controller. We designate these as a high byte and a low byte. The high and low bytes are the controller’s representation of a decimal number from 0-65535. To convert them to decimal, multiply the high byte by 256 and add the low byte to the result. If the temperature is a calculated temperature (condenser approach, subcooling or superheat): convert the decimal value to degrees Fahrenheit by dividing it by 10, or, convert the decimal value to degrees Centigrade by dividing it by 10, subtracting 32 and multiplying the result by 5/9ths. high byte * 256 + low byte = X ( X / 10 ) = Temperature in °F, or, (( X / 10) - 32) * 5/9 = Temperature in °C Example: high byte = 3 low byte = 86 3 * 256 + 86 = 854 (854 / 10) = 85.4°F, or, ((854 /10) -32) * 5/9 = 29.7°C If the temperature is a sensed temperature: convert the decimal value to degrees Fahrenheit by dividing it by 10 and subtracting 100 from the result, or, convert the decimal value to degrees Centigrade by dividing it by 10, subtracting 132 and multiplying the result by 5/9ths. Example: high byte * 256 + low byte = X ( X / 10 ) - 100 = Temperature in °F, or, (( X / 10) - 132) * 5/9 = Temperature in °C Example: high byte = 7 low byte = 62 7 * 256 + 62 = 1854 (1854 / 10) - 100 = 85.4°F, or, ((1854 /10) -132) * 5/9 = 29.7°C 57 Version 5.0 Note on Pressures Reading a pressure also requires reading two separate bytes of information from the controller. We designate these the same as for temperature, a high and low byte. To convert them to decimal, multiply the high byte by 256 and add the low byte to the result. Divide this decimal number by 10 to find pressure in PSI or multiply it by .689 to find the pressure in KPA. high byte * 256 + low byte = X (X) / 10 = Pressure in PSI (X) * 0.689 = Pressure in KPA Example: high byte = 3 low byte = 86 3 * 256 + 86 = 854 854 / 10 = 85.4 PSI 854 * 0.689 = 588 KPA Note on Compressor Operating Hours and Starts To read operating hours and compressor starts, you must again read two separate bytes of information from the controller. We designate these the same as for temperature or pressure, a high and low byte To convert these two bytes to decimal, multiply the high byte by 256 and add the low byte to it. The resulting decimal number is the number of operating hours or compressor starts. high byte * 256 + low byte = X X = number of operating hours or compressor starts Example: high byte = 19 low byte = 233 19 * 256 + 233 = 5097 operating hours Version 5.0 58 Appendix B - Monitor Screens 59 Version 5.0 Version 5.0 60 61 Version 5.0 Version 5.0 62 Appendix C - Chiller Models GROUP 1 - CR1 Chillers Water Cooled Chillers Manufactured in Cecchina, Italy Model No. No. Compressors R22 R134a WHR-045 2 Yes Yes WHR-055 2 Yes Yes WHR-065 2 Yes Yes WHR-075 2 Yes Yes WHR-085 2 Yes Yes WHR-100 2 Yes Yes Air Cooled Chillers Manufactured in Cecchina, Italy Model No. No. Compressors R22 R134a ALR-035 2 Yes Yes ALR-038 2 Yes Yes ALR-045 2 Yes Yes ALR-055 2 Yes No ALR-060 2 Yes Yes ALR-065 2 Yes No ALR-070 2 Yes Yes ALR-075 2 Yes No ALR-085 2 Yes Yes ALR-095 2 Yes No GROUP 2 - CR2 Chillers Water Cooled Chillers Manufactured in Cecchina, Italy 63 Model No. No. Compressors WHR-105 2 WHR-125 2 WHR-150 2 WHR-175 2 WHR-190 2 Version 5.0 Air Cooled Chillers Manufactured in Cecchina, Italy Model No. No. Compressors ALR-100 2 ALR-110 2 ALR-130 2 ALR-155 2 ALR-180 2 GROUP 3 - CR4 Chillers Water Cooled Chillers Manufactured in Cecchina, Italy Model No. No. Compressors WHR-225 3 WHR-245 3 WHR-265 3 WHR-285 3 WHR-210 4 WHR-220 4 WHR-240 4 WHR-260 4 Air Cooled Chillers Manufactured in Cecchina, Italy Version 5.0 Model No. No. Compressors ALR-210 3 ALR-220 3 ALR-240 3 ALR-260 3 ALR-285 4 ALR-310 4 ALR-335 4 64 Glossary of Terms BAS Building Automation System KPA Kilopascals OAT Outdoor Air Temperature OPM Open Protocol Master PSI Pounds Per Square Inch RLA Rated Load Amps 65 Version 5.0 Index —A— —L— Air cooled chillers, 11, 13, 15, 63, 64, 65 Analog inputs, 11, 13, 15 Automation integrator, 5, 6, 8 Liquid line, 15, 18, 19, 20, 21, 22, 23, 25, 26, 27, 28, 29, 31, 32, 34, 35, 36, 39, 40, 42, 43, 45, 46, 48, 49 —B— Baud rates, 7, 8, 56, 57 Building automation system, 6, 8, 66 —C— Chilled water reset, 6, 52, 53, 54, 55 Comm port, 7, 8, 56, 57 Communications protocols, 7, 8, 56 Compressor operating hours, 19, 23, 26, 32, 36, 37, 49, 50, 59 Compressor starts, 19, 23, 26, 32, 36, 37, 49, 50, 59 Condenser approach temperature, 18, 20, 21, 25, 27, 29, 34, 35, 37, 40, 43, 46, 58 Condenser entering water, 11, 13, 15, 19, 23, 26, 33, 37, 50 Condenser leaving water, 11, 13, 15, 19, 20, 21, 23, 26, 27, 29, 37, 40, 43, 46, 50 Condenser pressure, 11, 13, 15, 18, 20, 21, 25, 27, 29, 34, 36, 37, 40, 43, 46 Cooling stage, 19, 20, 22, 23, 26, 27, 28, 30, 33, 37, 38, 41, 44, 47, 50, 51 CR1 chillers, 5, 6, 11, 18, 52, 53, 63 CR2 chillers, 4, 5, 13, 25, 27, 28, 29, 30, 31, 32, 52, 53, 57, 63 CR4 chillers, 4, 5, 15, 34, 38, 39, 40, 41, 42, 43, 44, 45, 46, 47, 48, 49, 52, 54, 57, 65 Current alarm, 18, 20, 22, 25, 27, 28, 30, 31, 34, 35, 38, 39, 41, 42, 44, 45, 47, 48 —D— Demand limitiing, 6, 11, 13, 15, 52 Digital inputs/outputs, 11, 12, 13, 14, 15, 16 —E— Evaporator entering water, 11, 13, 15, 19, 23, 26, 33, 37, 50, 53, 54, 55 Evaporator leaving water, 11, 13, 15, 19, 23, 26, 33, 37, 52, 53, 54, 55 Evaporator pressure, 11, 13, 15, 18, 19, 21, 22, 25, 26, 28, 30, 34, 35, 36, 39, 40, 42, 43, 45, 46, 48 —G— Group 1 chillers, 5, 57 Group 2 chillers, 4, 5, 57 Group 3 chillers, 4, 5, 57 —I— —M— Monitor software, 8, 56, 57 —N— Network command, 6, 52 Network, Open Protocol, 7, 8 —O— Open Protocol Master panel, 8, 10, 66 Open Protocol network, 7, 8 Outdoor air temperature, 19, 23, 26, 33, 37, 50, 66 —P— Personal computer, 8, 56 Port, 7, 8, 56, 57 Previous alarm, 19, 26, 28, 31, 35, 36, 39, 42, 45, 48 —R— Rated load amps, 11, 19, 24, 26, 33, 37, 50 Read/write requests, 4, 5, 6, 8, 10, 18, 25, 34, 52, 54, 55, 57, 58, 59 Relays, 11, 12, 13, 14, 16 Remote alarm clearing, 6 Remote start/stop, 6, 12, 14, 16 RLA, 11, 19, 24, 26, 33, 37, 50 —S— Sensors, 20, 22, 27, 28, 30, 31, 38, 39, 41, 42, 44, 45, 47, 48 Software IDENT, 5, 6 Solenoids, 12, 14, 16, 17, 29, 40, 43, 46, 49 Stage of cooling, 19, 20, 22, 23, 26, 27, 28, 30, 33, 37, 38, 41, 44, 47, 50, 51 Status, 4, 10, 19, 21, 22, 24, 26, 28, 31, 33, 35, 36, 37, 39, 42, 45, 48, 50 Subcooling, 19, 21, 23, 26, 29, 32, 35, 36, 40, 43, 46, 49 Suction, 11, 15, 18, 19, 20, 21, 23, 25, 26, 27, 28, 29, 30, 31, 32, 34, 35, 36, 37, 39, 40, 42, 43, 44, 45, 46, 47, 48, 49 Superheat, 18, 19, 21, 23, 25, 26, 29, 32, 34, 35, 36, 40, 43, 46, 49 Switches, 11, 12, 13, 14, 15, 16, 21 —W— Water cooled chillers, 11, 13, 15, 23, 50, 63, 65 IDENT, 5, 6 Integrator, automation, 5, 6, 8 Version 5.0 66 13600 Industrial Park Boulevard, P.O. Box 1551, Minneapolis, MN 55440 USA (763) 553-5330 (www.mcquay.com)
© Copyright 2026 Paperzz