Rio-Eco Therm N

High-efficiency Drinking Water Pump
Rio-Eco Therm N
Type Series Booklet
Legal information/Copyright
Type Series Booklet Rio-Eco Therm N
All rights reserved. The contents provided herein must neither be distributed, copied, reproduced,
edited or processed for any other purpose, nor otherwise transmitted, published or made available to
a third party without the manufacturer's express written consent.
Subject to technical modification without prior notice.
© KSB Aktiengesellschaft, Frankenthal 24.08.2015
Contents
Contents
Building Services: Heating ................................................................................................................................. 4
Variable-speed Drinking Water Pumps ......................................................................................................................... 4
Rio-Eco Therm N ........................................................................................................................................................ 4
Main applications ................................................................................................................................................ 4
Fluids handled ...................................................................................................................................................... 4
Operating data .................................................................................................................................................... 4
Designation .......................................................................................................................................................... 4
Design details ....................................................................................................................................................... 4
Materials .............................................................................................................................................................. 5
Product benefits ................................................................................................................................................. 5
Certifications ........................................................................................................................................................ 5
Selection information .......................................................................................................................................... 5
Programme overview / selection tables ............................................................................................................. 7
Technical data ...................................................................................................................................................... 7
Selection chart ..................................................................................................................................................... 8
Characteristic curves ............................................................................................................................................ 8
Dimensions ......................................................................................................................................................... 10
Flange design ..................................................................................................................................................... 11
Installation information .................................................................................................................................... 11
Scope of supply .................................................................................................................................................. 11
Accessories ......................................................................................................................................................... 12
3
Building Services: Heating
Variable-speed Drinking Water Pumps
Building Services: Heating
Code
Variable-speed Drinking Water Pumps
100
Rio-Eco Therm N
Design details
Design
Description
30 = R 1 1/4
40 ... 65 = DN 40 ... DN 65
Head in m x 10 (example 10 m = 100)
▪ Highly efficient, maintenance-free wet rotor pump
(glandless)
▪ Screw-ended or flanged
▪ Permanent magnet motor
▪ Continuously variable differential pressure control
Operating modes
▪ Automatic mode with variable differential pressure
▪ Open-loop control mode with external 0 - 10 V setpoint
signal for speed
▪ Open-loop control mode with manual setpoint input
Automatic functions
▪ Continuous output adjustment depending on the
operating mode
▪ Deblocking function
▪ Soft start (slow start)
Main applications
▪ Drinking water circulation systems
▪ Similar systems in industry and building services
applications (e.g. cooling water circulation)
▪ Full motor protection
Manual functions
▪ Setting the operating mode
▪ Setting the differential pressure setpoint
▪ Setting the speed level
Fluids handled
▪ Drinking water and water for the food and beverage
industry, as per German 2001 drinking water regulations
External control functions
▪ Control input "start/stop"
▪ Control input for remote speed adjustment 0-10 V
Signalling and display functions
Operating data
▪ General fault indication (volt-free changeover contact)
Operating properties
Characteristic
Flow rate
Head
Fluid temperature
Ambient temperature
Operating pressure
Connection
Value
Q [m3/h] Screw-ended pumps: ≤ 12
Flanged pumps: ≤ 38
Q [l/s]
Screw-ended pumps: ≤ 3.33
Flanged pumps: ≤ 10.6
H [m]
≤ 12
T [°C]
Heating water: -10 to +110
Drinking water (≤ 20 °dH):
≤ 80
T [°C]
≤ 40
p [bar] ≤ 10
Screw-end: R 1 1/4
Flange: DN 40 - DN 65
▪ Fault indication, display of error codes
Interfaces
▪ Serial digital Modbus RTU interface for connecting higherlevel automation systems via the RS485 system bus
Twin pump management
▪ Duty/stand-by mode with timer-controlled pump
changeover every 24 hours and automatic changeover in
the event of a fault
Drive
▪ Electronically commutated synchronous motor with
permanent magnet rotor
▪ 1~230 VAC, 50/60 Hz
▪ IP42 enclosure
Designation
Example: Rio-Eco Therm N 30-100
Designation key
Code
Rio
Eco
Therm
N
30
Description
Type series
High-efficiency pump
Drinking water pump
New generation
Nominal diameter of pipe connection
▪ Thermal class F
▪ Temperature class TF 110
▪ Variable speed electric drives to EN 61800-3 EMC
requirements
▪ Interference emission standard EN 55014-1 or
EN 61000-6-3
▪ Interference immunity standard EN 55014-2 or
EN 61000-6-2
Bearings
▪ Product-lubricated special plain bearing
4
Rio-Eco Therm N
Building Services: Heating
Variable-speed Drinking Water Pumps
Materials
Overview of available materials
Component
Volute casing
Shaft
Impeller
Bearings
Material
Bronze
Stainless steel 1.4034
Plastic (PSU - 30 % glass fibre)
Carbon, resin-impregnated
Product benefits
▪ Maximum savings of operating costs by high-efficiency
motor combined with speed control
▪ "All-in" concept saves costs
▪ Design principle ensures long service life and high level of
comfort
▪ Universal use reduces storage costs
Certifications
Overview
Label
Effective in:
Germany
Comment
All sizes
Selection information
Minimum pressure
The minimum pressure pmin at the pump suction nozzle serves
to avoid cavitation noises at an ambient temperature of +40 °C
and the indicated fluid temperature Tmax.
The indicated values are applicable up to 300 m above sea
level. For installation at altitudes > 300 m, an allowance of
0.01 bar / 100 m must be added.
Minimum pressure pmin [bar] specified for the fluid temperature [°C]
Size
30-100, 30-120, 40-100,
40-120, 50-90
65-120
Fluid temperature
Minimum pressure
[°C]
Up to 80
81 to 95
Up to 80
81 to 95
[bar]
0,5
1,5
0,8
1,5
Rio-Eco Therm N
5
Building Services: Heating
Variable-speed Drinking Water Pumps
Description of the characteristic curve
4,0
H [m]
3,5
4
3,0
2,5
3
2,0
a)
b)
2
1,5
.
1,0
c)
0,5
0
A
1
0
1 Q [m3/h] 1,5
0,5
2
2,5
3
2
2,5
3
30
P1 [W]
25
4
a)
20
3
b)
2
15
c)
10
1
5
0
0
0,5
1 Q [m3/h] 1,5
Selection example
1
2
3
4
A
Level 1
Open-loop control (n = constant)
Level 2
Open-loop control (n = constant)
Level 3
Open-loop control (n = constant)
Level 4
Open-loop control (n ≠ constant)
Point of maximum pump power output (Q x H = Pmax.)
Control range
a)
b)
Control curve, maximum head
Control curve, maximum pump power output
(factory setting)
Control curve, minimum head
c)
The characteristic curve can be adjusted between a) and c)
by turning the control knob.
Description of the Modbus interface
Description see operating manual of the pump.
6
Rio-Eco Therm N
Building Services: Heating
Variable-speed Drinking Water Pumps
Programme overview / selection tables
Features and functions
Features and functions
Functions
Operating modes
Δp-v for variable differential pressure
Fixed speed operation
Manual functions
Setting the operating mode
Setting the differential pressure setpoint
Setting the speed
Vent plug
Automatic functions
Continuous output adjustment depending on the mode of operation
Deblocking function
Slow start
External control functions
Control input for remote speed adjustment 0-10 V
Control input "start/stop"
Signalling and display functions
Display of error codes
General fault message (volt-free NC contact)
Fault indicator lamp
Data exchange
Serial digital Modbus RTU interface for connection to a building management system via RS485 bus system
Features / scope of supply
Sealing elements for connection (not fitted)
Installation/operating manual
Technical data
30-100
30-120
40-100
40-120
50-90
65-120
R
DN
G
R1¼
R1¼
DN 40
DN 40
DN 50
DN 65
G2
G2
DN 40
DN 40
DN 50
DN 65
PN
P1
Motor protection
Size
[W]
6/10
6/10
6/10
6/10
6/10
6/10
22 - 250
30 - 340
30 - 350
27 - 450
30 - 350
100 - 1400
Signalling contacts
Rio-Eco Therm N selection table
✘
✘
✘
✘
✘
✘
SSM
SSM
SSM
SSM
SSM
SSM
Rated current Mat. No.
[kg]
1~230 V [A]
0,20 - 1,55
0,25 - 2,10
0,25 - 2,20
0,22 - 2,70
0,25 - 2,30
0,90 - 9,50
29134185
29134186
29134187
29134188
29134189
29134190
8.6
8.6
12.8
16.5
13.5
36.5
✘ = integrated motor protection
SSM = general fault message
Rio-Eco Therm N
7
Building Services: Heating
Variable-speed Drinking Water Pumps
Selection chart
Rio-Eco Therm N
140
14
H [m]
[kPa]
40-120
12
120
65-120
30-120
40-100
50-90
10
100
30-100
8
80
6
60
4
40
2
20
0
0
0,1
1,0
10,0
Q [m3/h]
0,1
Q [l/s]
1,0
10,0
Characteristic curves
Rio-Eco Therm N 30-120
Rio-Eco Therm N 30-100
12
1~230 VAC
R 1 1/4
10
H [m]
8
14
1~230 VAC
R 1 1/4
12
H [m]
10
8
6
6
4
4
2
2
0
0
0
2
4
6
8
10
12
Q [m /h]
0
3
300
2
4
6
8
10
12
14
Q [m3/h]
6
8
10
12
14
Q [m3/h]
400
P1 [W]
350
P1 [W]
250
300
200
250
150
200
150
100
100
50
50
0
0
0
8
2
4
6
Rio-Eco Therm N
8
10
12
Q [m3/h]
0
2
4
Building Services: Heating
Variable-speed Drinking Water Pumps
Rio-Eco Therm N 40-100
Rio-Eco Therm N 50-90
12
12
1~230 VAC
DN 40
10
1~230 VAC
DN 50
10
H [m]
H [m]
8
8
6
6
4
4
2
2
0
0
0
2
4
6
8
10
12
14
16
Q [m /h]
0
3
400
P1 [W]
350
5
10
15
20
25
Q [m3/h]
15
20
25
Q [m3/h]
400
P1 [W]
350
300
300
250
250
200
200
150
150
100
100
50
50
0
0
2
4
6
8
10
12
14
16
0
0
Q [m /h]
3
Rio-Eco Therm N 40-120
5
10
Rio-Eco Therm N 65-120
14
14
1~230 VAC
DN 40
12
1~230 VAC
DN 65
H [m]
12
10
10
H [m]
8
8
6
6
4
4
2
2
0
0
0
2
4
6
8
10
12
14
16
Q [m /h]
0
10
20
30
40
50
Q [m3/h]
0
10
20
30
40
50
Q [m3/h]
3
1.600
P1 [W]
1.400
500
450
P1 [W]
400
1.200
350
1.000
300
250
800
200
600
150
400
100
200
50
0
0
0
2
4
6
8
10
12
14
16
Q [m /h]
3
Rio-Eco Therm N
9
Building Services: Heating
Variable-speed Drinking Water Pumps
Dimensions
Dimensions of screw-ended pump
75
35
150
90
H
230
G
Screw-ended pumps
Dimensions [mm]
Size
30-100
30-120
R
1 1/4
1 1/4
G
2
2
H
180
180
Dimensions of flanged pump
a
b
c
e
H
d
Flanged pump
Dimensions [mm]
Size
40-100
40-120
50-90
65-120
10
DN
40
40
50
65
a
215
215
225
235
b
75
75
75
93
Rio-Eco Therm N
c
75
75
95
105
d
150
150
160
180
e
125
125
140
170
H
250
250
280
340
Building Services: Heating
Variable-speed Drinking Water Pumps
Flange design
ØD
Ø k L2
Ø k L1
Ød
DN
n x Ø d1
n x Ø d2
Adapter flange
Dimensions [mm]
Adapter flange
DN 40
DN 50
DN 65
ØD
150
165
185
Ød
PN 6
PN 10
PN 6
PN 10
84
99
118
ØkL1
100
110
130
ØkL2
110
125
145
n × dL1
4 × Ø14
4 × Ø14
4 × Ø14
n × dL2
4 × Ø19
4 × Ø19
4 × Ø19
Installation information
Permissible installation positions
Sizes
Rio-Eco Therm N 30-100,
30-120, 40-100, 40-120, 50-90
Rio-Eco Therm N 65-120
Scope of supply
▪ Pump
▪ Installation/operating manual
Rio-Eco Therm N
11
Building Services: Heating
Variable-speed Drinking Water Pumps
Accessories
Electrical accessories
Description
Length
Mat. No.
[kg]
Modbus data cable
With preconfigured plug for Rio-Eco Therm N
5
19075536
0.2
Description
Mat. No.
[kg]
2 pipe unions
with G 1 1/2 union nut and insert with Rp 3/4 internal thread, brass
for pumps with G 1 1/2 external thread / R 3/4 pipe connection
2 pipe unions
with G 1 1/2 union nut and insert with Rp 1 internal thread, brass
for pumps with G 1 1/2 external thread / R 1 pipe connection
2 pipe unions
with G 2 union nut and insert with Rp 1 ¹/₄ internal thread, brass
for pumps with G 2 external thread / R 1 ¹/₄ pipe connection
19075563
0.2
19075564
0.2
19075565
0.2
Pipe union
12
Rio-Eco Therm N
24.08.2015
1142.51/03-EN
KSB Aktiengesellschaft
67225 Frankenthal • Johann-Klein-Str. 9 • 67227 Frankenthal (Germany)
Tel. +49 6233 86-0 • Fax +49 6233 86-3401