Specifications

3 phase/4 wire, 3 phase/3 wire, RS232/USB
1 phase/2 wire, 1 phase/3 wire, SD card memory
3 PHASE POWER
ANALYZER
Model : DW-6092
ISO-9001, CE, IEC1010
SD card real time data logger
3 PHASE POWER ANALYZER
Model : DW-6092
FEATURES
* Analysis for 3 phase multi-power system, 1P/2W,
1P/3W, 3P/3W, 3P/4W
* Voltage & Current are the True RMS value.
* True Power ( KW、MW、GW ) measurement.
* Apparent Power ( KVA、MVA、GVA ) measurement.
* Reactive Power ( KVAR MVAR、GVAR) measurement.
* Watt-Hour ( WH、SH、QH、PFH ).
* Power Factor( PF )、Phase Angle( Φ ).
* Voltage measurement range : 10 to 600 ACV
* Current measurement range: 0.2A to 1200 ACA.
* Programmable CT ratio (1 to 600) and PT ratio (1 to 1000).
* ACV input impedance is 10 Mega ohms.
* Safety Standard : IEC 1010, CAT III 600V
* Built-in clock and Calendar, real time data record with
SD memory card , sampling time set from 2 to 7200
seconds. Just slot in the SD card into the computer, it
can down load the all the measured value with the
time information ( year/month/data/
hour/mimute/second ) to the Excel directly, then user
can make the further data analysis by themselves.
* Complete set with 4 PCs Test Leads, 4 PCs Alligator
clips, 3 PCs Clamp Probe, AC to DC 9V adapter,
2 G SD memory card and Carrying bag.
* Computer data output, can cooperate with USB Cable
/USB-01 RS232 cable/UPCB-02 and Data Acquisition
software, SW-U801-WIN.
GENERAL SPECIFICATIONS
Circuit
Custom one-chip of microprocessor LSI
circuit
Display
* LCD Size :
81.4 X 61 mm ( 3.2 X 2.4 inch )
* Dot Matrix LCD (320 X 240 pixels )
with back light.
Measurement
* ACV
* ACA
* AC WATT ( True Power )
AC WATT( Apparent Power )
AC WATT( Reactive Power )
* Power factor
* Phase angle
* Frequency
Wire
1P/2W, 1P/3W, 3P/3W, 3P/4W.
connections
Voltage ranges
10 ACV to 600 ACV, auto range.
Current ranges
0.2 ACA to 1200 ACA,
auto range/manual range.
Safety
IEC1010 CAT III 600 V.
standard
ACV input
10 Mega ohms.
impedance
Range select
ACV Auto range.
ACA Auto range & manual range.
Clamp
40 Hz to 1 KHz.
frequency
response
Spec. tested
45 to 65 Hz.
frequency
Over load
ACV 720 ACV rms
protection
ACA 1300 ACA with clamp probe
CP-1200
Over Indicator
Show " OL ".
Under Indicator
Show " UR ".
Data Hold
Freeze the display reading.
Data Record
SD Card Record.
Sampling Time
Approx. 1 second.
Power ON/OFF
Manual OFF by push button.
Real time
* Real time data logger, saved the data
data logger
into SD memory card and down load
the all the measured value with the
time information ( year/month/data/
hour/mimute/second ) down load
to the Excel
* Integration time for data logger :
2 seconds to 7200 seconds, the during
of setting step are 2 seconds.
Data Output
RS232 computer serial interface :
USB/RS232
* Connect the optional USB cable
* Computer
USB-01 will get the USB plug.
interface
* Connect the optional RS232 cable
UPCB-02 will get the RS232
plug.
Operating
0 to 50℃ ( 0 to 122℉ ).
Temperature
Operating
Less than 80% R.H..
Humidity
Power Supply
* DC 1.5V, AA ( UM-3 ) Battery X 8 PCs
(Alkaline or heavy duty battery).
* AC to DC 9V power adapter.
Power
* Meter : 300 DCmA.
Consumption
* Clamp : 20 DCmA.
Clamp max.
86 mm ( 3.4 inch ) Dia.
conductor
Size
Weight
* Meter: 1049g ( includes batteries )
* Clamp : 522g
Dimension
Meter : 225 X 125 X 64 mm
( 8.86 X 4.92 X 2.52 inch )
Clamp : 210 X 64 X 33mm
( 8.3 X 2.5 X 1.3 inch )
Clamp Jaw : 86 mm (3.4 inch)- outside
*
Accessories
Included
*
*
*
*
*
*
*
*
*
*
Optional
Accessories
Instruction manual........................1
Test Leads (TL88-4AT)..................1
Alligator clips (TL88-4AC).............. 1
Clamp Probe ( CP-1200 )...............3
AC to DC 9V adapter.....................1
SD card ( 2 G ).............................1
Carrying bag.................................1
PC
Set (4 PCs)
Set (4 PCs)
PCs
PC
PC
PC
USB Cable , USB-01
RS232 cable, UPCB-02
Data Acquisition software,
SW-U811-WIN
ELECTRICAL SPECIFICATIONS
ACV
Range
Resolution
Accuracy
10.0V to 600.0V
0.1V
± (0.5%+0.5V)
* Phase to neutral line
10.0V to 600.0V
* Phase to phase
ACA
Range
Resolution
Accuracy
20A
200A
1200A
0.001A/0.01A
0.01A/0.1A
0.1A/1A
± (0.5%+0.1A)
± (0.5%+0.5A)
± (0.5%+5A)
Range
Resolution
Accuracy
0.00 to 1.00
0.01
± 0.04
Power factor
Remark :
* PFH : Long term average power factor ( WH/SH )
* PFΣ :
For 3Φ 4W, 3Φ 3W
PFΣ = ( PF1 + PF2 + PF3 )/3
For 1Φ 3W
PFΣ = ( PF1 + PF2 )/2
Φ ( Phase angle )
Range
Resolution
Accuracy
-180° to 180°
0.1°
± 1° * ACOS(PF)
Frequency
Range
Resolution
Accuracy
45 to 65 Hz
0.1 Hz
0.1 Hz
Resolution
0.001 KW
0.01 KW
0.1 KW
0.001 MW
Accuracy
± (1%+0.008 KW)
± (1%+0.08 KW)
± (1%+0.8 KW)
± (1%+0.008 MW)
Resolution
Accuracy
Range
Resolution
Accuracy
0.000 to 9.999 KVAR
10.00 to 99.99 KVAR
100.0 to 999.9 KVAR
1.000 to 9.999 MVAR
0.001 KVAR
0.01 KVAR
0.1 KVAR
0.001 MVAR
± (1%+0.008 KVAR)
± (1%+0.08 KVAR)
± (1%+0.8 KVAR)
± (1%+0.008 MVAR)
Active (Real) Power
Range
0.000 to 9.999 KW
10.00 to 99.99 KW
100.0 to 999.9 KW
1.000 to 9.999 MW
Apparent Power
Range
0.000
10.00
100.0
1.000
to
to
to
to
9.999
99.99
999.9
9.999
KVA
KVA
KVA
MVA
0.001 KVA
0.01 KVA
0.1 KVA
0.001 MVA
± (1%+0.008 KVA)
± (1%+0.08 KVA)
± (1%+0.8 KVA)
± (1%+0.008 MVA)
Reactive Power
Watt Hour ( Active Power Hour) : WH
Range
0.000
10.00
100.0
1.000
to
to
to
to
9.999
99.99
999.9
9.999
KWH
KWH
KWH
MWH
Resolution
Accuracy
0.001 KWH
0.01 KWH
0.1 KWH
0.001 MWH
± (2%+0.008 KWH)
± (2%+0.08 KWH)
± (2%+0.8 KWH)
± (2%+0.008 MWH)
VA Hour ( Apparent Power Hour ) : SH
Range
0.000 to 9.999 KVAH
10.00 to 99.99 KVAH
100.0 to 999.9 KVAH
1.000 to 9.999 MVAH
Resolution
0.001 KVAH
0.01 KVAH
0.1 KVAH
0.001 MVAH
Accuracy
± (2%+0.008 KVAH)
± (2%+0.08 KVAH)
± (2%+0.8 KVAH)
± (2%+0.008 MVAH)
VAR Hour ( Reactive Power Hour ) : QH
Range
0.000
10.00
100.0
1.000
to 9.999
to 99.99
to 999.9
to 9.999
Appearance and specifications listed in this brochure are subject to change without notice.
KVARH
KVARH
KVARH
MVARH
MRC-10.15
Resolution
Accuracy
0.001 KVARH
0.01 KVARH
0.1 KVARH
0.001 MVARH
± (2%+0.008 KVARH)
± (2%+0.08 KVARH)
± (2%+0.8 KVARH)
± (2%+0.008 MVARH)
DW-6092