with a chimney fan system

Take control of your chimney draught
with a chimney fan system
2
Many experience problems
Many homes with wood-burning stoves or fireplaces experience problems when
lighting the fire. Some of the most typical problems are:
Difficulty lighting the fire
Difficulties in lighting the fire can be caused by using poor quality fuel or because the
draught in the chimney is insufficient. The draught in the chimney is caused by the
warm air being lighter than the cooler air outside. As the chimney is cold when lighting the fire the draught is reduced and it can be hard to get the fire started. It is important that the kindling is dry and that you start with small pieces of wood. This will
ensure that the fire will take hold quickly, creating the heat that is necessary to create a
good chimney draught, but sometimes even this is not enough.
Smoke in the room
Spillage can occur if there is insufficient draught. This can be caused by insufficient air
supply or the use of extractor fans. Fireplace and stove size, chimney height and chimney location in relation to nearby buildings can also effect draught and result in smoke
spilling in to the room. It is also important to be aware that the chimney draught can
vary with the season, the outside temperature and the weather (wind, rain, etc).
The fire goes out
Good combustion needs air. The chimney’s “job” is not only to remove smoke but to
draw in fresh air through the supply vents to replace the air used by the fire. If the air
supply is reduced too quickly, uncombusted gasses and particles will exit through the
chimney, causing soot and smokey odours.
Odours and soot
Poor combustion can cause soot build up on the stove door as well as smoke odours.
Damp or wet fuel, an incorrectly set air damper or insufficient chimney draught will
also cause this. Good combustion requires high temperatures and sufficient air supply. If the air supply is reduced too quickly, uncombusted gasses and particles will exit
through the chimney, causing soot and smokey odours.
You are not the one
doing something wrong
3
People are often disappointed when their dream of a cosy warm fire is ruined by insufficient chimney draught.
Many often think it must be something that they are doing wrong when they light the
fire. The simple act of lighting a fire is made difficult by smoky down draughts, soot
or the fire going out. Problems lighting the fire can arise because of incorrect or poor
quality fuel, but in most cases problems are caused by insufficient chimney draught.
Thirty years ago we accepted kitchen smells because we did not have kitchen
extractor fans. Why should we now accept soot and smoke escaping into our rooms,
when a chimney fan will solve the problems caused by insufficient chimney draught.
Many people believe that it is their
fault when the fireplace or stove
causes smoke in the living room.
But the problem is typically caused
by insufficient chimney draught.
4
Control your chimney draft
with a chimney fan system
Solves your chimney draught problems
and gives you additional advantages
If you install a variable speed chimney fan system you will always have control of the chimney
draught. Apart from providing you with the optimal chimney draught as soon as you light your fire,
a chimney fan system will also give you many other advantages.
Lighting the fire is quick and easy
It will be easier for you to light your fire, regardless of the weather or the
size of your fireplace or stove in relation to your chimney. For the environmentally aware, it is also nice to know that because the fire takes hold
much quicker, fewer particles escape into the atmosphere.
No smoke or odours
Because the chimney fan ensures that the smoke exits through the chimney rather than into your living room, you will not have smoke spillage
and odours, even when you light or refuel the fire.
Improved combustion saves money
The correct chimney draught ensures steady combustion and thus saves
you money. Optimal combustion reduces the amount of fuel needed by
up to 15 %.
Healthier soot-and-smoke-free indoor environment
If you turn the chimney fan on while you clean your fireplace, the fine
ash is extracted up through the chimney instead of escaping into the
room and onto your furniture. Please make sure that the fan is cleaned
afterwards. Your home’s indoor environment is much healthier as all the
particles are sucked up through the chimney.
Additional ventilation
As an extra bonus, when the fireplace is not in use you can use the
chimney fan for ventilation during the summer or winter. If for example
you leave your chimney fan running at low speed overnight after you
have entertained guests, it ensures you will be breathing fresh air, free of
odours the next morning.
5
6
A better indoor environment
as an additional bonus
A chimney fan does not just deliver the perfect chimney draught. It can also
improve your indoor climate. When you air the room, vacuum, or use your
cooker hood you do it to improve your indoor climate. A mechanically generated chimney draught can also benefit your indoor environment.
The chimney fan stops soot from covering furniture and fixings. It also ventilates the
room if you turn it on when you are not using the fireplace. It stops ash escaping into
the room if it is turned on while your wood-burning stove or fireplace is being cleaned.
In short, a chimney fan helps you achieve a better indoor environment.
Benefit from 50+ years
of experience
7
exodraft products are based on 50 years of experience within chimney draught technology and an extensive expertise in the field of chimneys and chimney draught. Many
different kinds of solutions are tried when it comes to chimney draught problems, but a
chimney fan is the most effective solution to insufficient chimney draught.
Our commitment to quality, honesty and integrity
has helped us become the world market leader within
the industry for mechanical chimney draught.
Our chimney fans are of the highest quality and reliability.
All of our products also come with a two-year factory warranty.
Appraisa
l form – fire
places, sto
ves and co
1a Originato
r:
Company:
Telephone
Work:
Job refere
nce:
property:
Private dwel
ling
 Public house/hot
el/restaura
2. Fuel used
Wood

:
3a Do you
have
h
a
1-sided

h
h

LPG 
h
b
Other
2-sided

b
h
a
a
c
c
b
b
h
h
a
a
h
h
a
Opening into
a
ents
2 rooms
 Inglenook hood
b
Width of open
(3-sided)

Height from ing (a)_______ mm
Centre firepla
(______ in)
8a Chimney
heart
ce 
hood (h) _____ h to top of open
height: _____
ing or to
___ mm (____
_______ m
Internal size
Depth from
or __________
__ ins)
__________
front of open
_ ft
No. of bend
____ mm
Depth from
ing (b) _____
or __________
s in chimney
front of open
_
mm
(______ in)
________
Height of
ing (c) _____
8b Chimney
(45°) _____ __ in
gathe
_ mm (____
shape:
__ (90°)
chimney _____ r/hood from top of
__
in)
opening to
___ mm (____
Round
throat of
 Rectangula
__ in)
3c If gas,
r
please state
8c Flue mate
maximum
rial:
__________
gas inpu
_____kW
Brick
t:
or __________

4 Close
Metal (twin
Stone
___ Btu
d appliance
-wall)

? (fill out meas
Metal (sing
 Flexib
Other _____
le wall)
Stove
urements
_________

 Clay le liner 
in 3b)
Cooker
8d Flue insul

Max heat

ation:
input: _____
___ kW or
Thickness
5
__________
_________
For a firep
Btu
mm, _____
lace havin
9a Is the
____ m2 K/W
g a lintel,
chimney
Depth (D)
state
more
the
of
the lintel
of the roof:
than 40 cm
D
(Maximum
higher than
(D) 100 mm ____ mm ( _____ in)
the ridge
Yes 
6
W
Is the THRO
No 
AT in the
9b The angle
centre of
Yes 
of the roof
the gath
er?
is:
No 
If no, state
<25° 
shortest W___
25°-40°
7 Extra
_ mm (____

9c The chim
ct fan syste
>40° 
in)
m in the
ney is close
room?
Yes 
r than 20
coast:
km (12.5
No 
mi) to the
Yes 
No 
9d Is the
chimney
close to adjac
Yes 
ent obstructi
ons:
No 
Adjacent obstr
uctions are
Dimension
within a 15
buildings,
tall trees or
m range, exten
ed sketch
mountains
a 10°+ vertic
ding at a 30°+
of installa
al angle from
horizontal
tion with
For office
angle and
top of chim
flue run mu
use only
ney.
st be include
Flue gas Temp
. __________
d as attachm
Air volum
__________
e __________
ent!
__________
Pressure loss
__________
__°C
__________
__________
Controller:
Recomme
__ m3/h
__________
__________
nded fan:
__________
__________
Accessories
__________
__ Pa
: __________
__________
__________
Calculated
_________
______
__________
by:
__________
__________
Please send
Date: _____
_____
__________
__________
__________
info@exod the filled out form
_____
___
raft.co.uk
__________
to:
or
__________
fax: +01494
_
465 163
3b Measurem
- 02.2012
Natural Gas
a
a
31000114
nt 
Smokeless
or coal

Oil 
an open firepl
ace and which
?
h
a
We have an extensive network of dealers around the world
that can help you choose the right chimney fan for your
fireplace. Just download an appraisal form from our homepage www.exodraft.co.uk and send it in.
okers
Telephone
mobile/ho
me:
Fax Number:
1b Type of
An almost invisible solution
– with a visible effect
The chimney fan is mounted discreetly on the top of the chimney and ensures that you
have the correct chimney draught to enjoy a cosy fire in your wood-burning stove or
fireplace.
b
8
Frequently asked questions
How does a chimney fan work?
The chimney fan is mounted onto the top of your chimney. When the chimney fan is turned
on, it creates a negative pressure in the chimney, causing smoke to be extracted up the
chimney and fresh air to be drawn to the fire, which in turn ensures effective combustion.
Can a chimney sweep clean the chimney when a fan is mounted on the top?
The chimney sweep can easily open the chimney fan and access the chimney which can be
cleaned in the normal fashion.
How is a chimney fan maintained?
Cleaning is the only the maintenance that a chimney fan requires. How often it needs to be
cleaned depends on the kind of fuel being burned in the fireplace or stove. If only dry wood
is used in the fireplace the chimney fan only needs to be cleaned once a year depending
upon usage. Dirt and soot can be removed from the fan using a steel brush or scraper.
Can the chimney fan fall down the chimney?
The chimney fan is fitted to the chimney top using mounting brackets or a flange plate. The
brackets or the flange along with the weight of the fan will keep it fixed in place even in
extreme weather conditions. An additional safety wire means the chimney fan cannot fall
down from the chimney when it is being serviced or when the chimney is being swept.
What happens if there is a power failure?
If there is a power failure, or if the electricity has been switched off, the chimney will function as it did before the chimney fan was installed. The fan will offer very little resistance to
the natural flow.
What is the working lifetime of a chimney fan?
Chimney fans are made of cast aluminium and high temperature resistant materials. This
ensures a long and reliable working lifetime. Many of our fans have been running for more
than 25 years.
For more information visit www.exodraft.co.uk
“I recommend exodraft chimney fan
solutions to my customers when I can see
they have chimney draught problems.”
Martin Holm Andersen
Certified Chimney Sweep
A good idea
– and inexpensive to use
Some people believe a chimney fan is expensive to run.
In fact a chimney fan uses no more electricity than a 60 W bulb.
10
The chimney fan system
An exodraft chimney fan system consists of a chimney fan connected to a manual or semi-automatic control so the chimney
draught can be adjusted according to requirements. The
chimney fan is easy to mount on the top of the chimney
and can tolerate constant temperatures as high as 250 ºC.
The impeller is dynamically balanced to keep vibrations to a
minimum so the chimney fan operates very quietly.
Chimney fans
Chimney fans are available in two model types for solid fuel applications. The RSV model has vertical discharge while the
RS model has horizontal discharge.
Model RSV
Model RS
If the chimney top is above the ridge height of the roof, both RS and RSV type models
can be used. RSV models are recommended for use in windy areas. If the chimney top is
lower than the height of the roof ridge or if the building has a thatched roof we would
also recommend the RSV chimney fan due to the vertical discharge.
Both models are available in various sizes to suit any size of fireplace or wood-burning
stove. RS models have square baseplates as standard but are also available with octagonal baseplates.
The chimney fans can be opened easily,
enabling a chimney sweep
to sweep the chimney and clean the
chimney fan without any problems.
To find out more about chimney fans
visit www.exodraft.co.uk
Controls and accessories
Manual control
The EFC16 control unit lets the user manually control the chimney draught.
It has an on/off button and an LED to indicate when the chimney fan is running.
The EFC16 and EFC18 control units must have a repair/isolation switch
fitted to the chimney, this can only be done by a qualified electrician.
Manual/automatic control
The EFC18 control unit is used to regulate the chimney draught. The chimney
fan can either be started manually or automatically. The fan speed is regulated
manually.
The control unit comes with a temperature sensor, which enables the
control unit to stop the chimney fan depending on the temperature in the
chimney. When you restoke the fire you can boost the speed of the chimney fan
to maximum for three minutes with the touch of a button. The chimney fan will
automatically adjust itself back down to the preset speed afterwards. We recommend that the EFC18 is used on closed appliances.
Wireless control
The EW 41 wireless control regulates the chimney draught. It is quick
and easy to install as there is no need for cables between the power unit and
the control panel. The control comes with a temperature sensor that gives you
access to a range of functions and options that not only help improve the indoor
environment but also increase safety, such as:
yy
yy
yy
yy
a boost function, making lighting the fire easier
an alarm function, for example in the case of a chimney fire
an automatic stop function, controlled by the temperature in the chimney
a function indicating when the fire needs relighting/stoking
The wireless control only communicates with electronically paired components
and will not be disturbed by other wireless units such as doorbells, baby alarms
etc.
Flanges
The chimney fan is fitted to a steel chimney using a corrosion resistant flange,
ensuring the chimney fan is mounted onto a level surface. Two types of flanges
are available:
yy FR square flange for RSV and RS chimney fans with square baseplates
yy FR-02 octagonal flange for RS chimney fans with octagonal baseplates
To learn more about chimney fan controls and accessories visit
www.exodraft.co.uk
11
exodraft’s extensive product range is based on more than 50 years of experience and
knowledge in the field of combustion and chimney draft technology.
Our products are known for high safety and quality and we are helping to set the standards
and requirements for draft technology.
exodraft products are all fully documented in accordance with current national and
international standards and are sold in more than 40 countries – for small domestic
fireplaces in private homes to larger commercial and industrial boiler installations.
Decentralized
multiple fireplaces
connected to same
chimney
Solid fuel and biofuel boilers
(pellets etc.)
Bakeries
Industry
Restaurants and pubs
Gas fireplaces
Oil and gas boilers
Decentralized
multiple heating
appliances connected
to same chimney
DK: exodraft a/s
NO: exodraft a/s
DE: exodraft GmbH
C. F. Tietgens Boulevard 41
DK-5220 Odense SØ
Tel: +45 7010 2234
Fax: +45 7010 2235
[email protected]
www.exodraft.dk
Fjordgløttveien 11
NO-3060 Svelvik
Tel: +47 3329 7062
Fax: +47 3378 4110
[email protected]
www.exodraft.no
Rosengartenstr. 9
DE-55569 Monzingen
Tel: +49 (0)6751 855 599-0
Fax: +49 (0)6751 855 599-9
[email protected]
www.exodraft.de
SE: exodraft a/s
UK: exodraft Ltd.
Årnäsvägen 25B
SE-432 96 Åskloster
Tlf: +46 (0)8-5000 1520
Fax: +46 (0)340-62 64 42
[email protected]
www.exodraft.se
Unit 3, Lancaster Ct.
Cressex Business Park
GB-High Wycombe HP12 3TD
Tel: +44 (0)1494 465 166
Fax: +44 (0)1494 465 163
[email protected]
www.exodraft.co.uk
3100013-12.12 • Fotos: sxc.hu & exodraft
Solid fuel and woodburning stoves and
fireplaces
Technical data
Chimney fans, controllers & accessories
yy Solid fuel and wood-burning stoves and fireplaces
yy Biofuel boilers
yy Decentralised multiple heating appliances connected to same chimney
Project and design support
exodraft solutions are so much more than just products
and systems. In close co-operation with our exodraft
Technology Centres we provide pre-sale analysis, system
design and implementation recommendations.
engineering and installation support. All designs are
stored electronically, so our engineers and technicians
have a record of what a system looks like and what it
includes.
During this process we use design software, developed
by exodraft, which enables us to design any system
with great accuracy and speed.
Appraisal
form – fire
places, sto
ves and coo
kers
1a Origin
ator:
Company:
Telephone
Work:
Job referen
ce:
Telephone
mobile/home
Fax Numbe
:
r:
1b Type of
property:
Private dwellin
g
The design software allows exodraft and our
Technology Centres’ experienced engineers to design
complete systems quickly, accurately and efficiently,
whilst providing engineers with sizing reports.
estaurant
Wood

3a Do you
have
h

Smokeless
or coal

Oil 
an open firepla
ce and which?
Natural Gas

LPG 
Other
h
a
a
a
a
1-sided
- 02.2012
As exodraft or our Technology Centres design the
system, we also take full responsibility for its operation.
This is part of exodraft’s “Performance Guarantee”.
All calculations and system recommendations provided
by exodraft are performed in accordance with the
relevant rules and regulations.
 Public house/hotel/r
2. Fuel used:
31000114
2

h
h
h
b
b
h
a
a
c
c
b
b
h
h
h
h

a
3b Measu
Opening into
a
rements
2 rooms
 Inglenook hood
b
Width of openin
(3-sided)
g (a)_______

Height from
Centre fireplace
mm (_____
8a Chimn
hearth to
_ in)

ey height
top of openin
hood (h) ______
: ____________
g or to
__ mm (_____
Internal size
Depth from
m or ______
_ ins)
____________
front of openin
_____ ft
No. of bends
Depth from
__ mm or
in chimne
front of openin g (b) ______ mm (_____
y ________ ____________ in
Height of
g (c) ______
_ in)
8b Chimn
(45°) ______
gather
ey shape
mm (_____
_ (90°)
chimney ______ /hood from top of
:
_ in)
opening to
__ mm (_____
Round
throat of

_
in)
Rectangular
3c If gas,
please state
8c Flue mater

maximum
ial:
____________
gas input:
Brick
___kW or

____________
4 Closed
Metal (twin-w
Stone
_ Btu
appliance?
all)

(fill out measu
Flexible
Other ______ Metal (single wall) 
Stove
rements in
________

 Clay liner 
3b)
Cooker
8d Flue insula

Max heat

input: ______
tion:
__ kW or ______
Thickness
5
_________
____ Btu
For a firepla
mm, ______
ce having
9a Is the
___ m2 K/W
a lintel, state
chimney
Depth (D)
more than
the
of the lintel
of the roof:
D
40 cm higher
(Maximum
than the
(D) 100 mm ____ mm ( _____ in)
Yes 
6
ridge
W
Is the THROA
No 
T in the centre
9b The angle
Yes 
of the gathe
of the roof
is:
r?
No 
If no, state
<25° 
shortest W____
25°-40°
7 Extrac
mm (____

9c The chimn
t fan system
>40° 
in)
ey is closer
in the room?
Yes 
coast:
than 20 km
No 
(12.5 mi)
to the
Yes 
No 
9d Is the
chimney
close to adjace
Yes 
nt obstru
ctions:
No 
Adjacent obstruc
tions are buildin
Dimension
within a 15
gs,
tall trees or
m range, extend
ed sketch
mountains
a 10°+ vertica
ing at a 30°+
of installatio
l angle from
horizontal
n
For office
angle and
with
top of chimne
flue
use only
y.
run must
Flue gas Temp.
be included
____________
as attachme
Air volume
____________
____________
nt!
________°C
Pressure loss
____________
________
Controller:
Recommende __________________
m3/h
____________
______
d fan: ______
Accessories:
____________
____________ ________ Pa
____________
____________
___________
Calculated
____________
by:
___________
Please send
Date: ______ __________________
____________
______
info@exodraftthe filled out form
____________ _________
to:
___________
fax: +01494 .co.uk or
465 163
2-sided
a
a
b
exodraft and our Technology Centres offer telephone
System solutions
with a perspective
Want to know more
about chimney fan solutions?
exodraft’s systems provide the basis for an optimal
solution – both during planning and implementation.
They are a reliable, simple solution for all professional
partners.
We have a number of CPD seminars that cover your
business requirements in connection with the design of
boiler systems and/or fireplaces.
Well-documented, our system solutions are adapted to
meet the requirements and standards within the various
areas of use.
We look forward to assisting you in getting started.
The exodraft chimney draught systems are available
through our network of exodraft Technology Centers
(ETC), who distribute the full range of exodraft chimney
draught systems throughout the UK.
Each ETC has a certified exodraft product manager. The
product manager is knowledgeable of exodraft’s full
chimney draught system and product range and will
be able to answer all of your questions. All ETCs hold
exodraft products in stock and items can usually be
delivered within 24 hours.
Our seminars will help you to take full advantage of the
possibilities that mechanical chimney draught gives you
to design energy efficient, flexible, and guaranteed safe
boiler or fireplace systems.
Please feel free to contact us for further information
on our CPD seminars or our Chimney Automation
Solutions.
Peace of mind guarantee
exodraft systems are supplied with a peace of mind
guarantee:
yy 3 year warranty against any mechanical failure to the
systems
yy 10 year warranty against corrosion.
Table of contents
3
System descriptions
Components for fireplaces or wood-burning stoves
3
Components for installations with multiple wood-burning stoves connected to the same chimney
4
Components for solid fuel or biomass-burning boilers
5
Technical data
RS chimney fan
6
RSV chimney fan
8
EFC16 control
10
EFC35 control
10
EFC18 control
11
EW41 control
12
EBC20 control
13
Isolation switches
14
Flanges14
Other installation accessories 14
Installing the fans, service and maintenance
Installing the fans
Hiding the chimney fan
Service and maintenance
15
15
15
4
Components for fireplaces or wood-burning stoves
With exodraft chimney fan systems you always have control over the chimney draught regardless of the
weather conditions or other factors influencing the natural draught.
It is the function of the chimney both to remove the smoke
and supply oxygen for effective combustion. In an ideal
situation this is done though the natural chimney draught,
but in reality both the chimney itself and other external
factors affect the natural draught and thus the effectiveness
of the chimney.
1
4
3
An exodraft chimney fan gives you complete control over
the chimney draught. The chimney fan is installed on top of
the chimney and creates a negative pressure in the flue, thus
ensuring that the flue gases are extracted up the chimney
rather than into the room. The fan control enables you to
adjust the chimney draught to suit your needs, so you can
enjoy the full comfort of a warm fireplace or wood-burning
stove.
An exodraft chimney fan system for a fireplace or woodburning stove consists of an RS or RSV chimney fan with an
axial vane, a fan control and accessories.
2
The EFC16, EFC18, EFC35 and EW41 controls allow the user
to manually adjust the chimney draught. The EFC18 control
comes with a temperature sensor enabling automatic stop
of the chimney fan after the fire is out. The EFC18 also has
a boost function for extra chimney draught on start-up
or when re-stoking the fire, so smoke down draughts and
odours do not escape into the room.
The EW41 wireless controller is easy to install as no power
supply cables are needed for the control panel.
In addition to having similar functionality as the EFC18, the
EW41 also signals when it is time to re-stoke the fire and
audibly indicates if the temperature inside the chimney
becomes too high. It is easy to see and change the settings
via the display on the control panel.
Find the components you need here:
1
2
Component
Type
Page
Chimney fan
RS with horizontal exhaust
6
RSV with vertical exhaust
8
EFC16
10
EFC35
10
EFC18
11
EW41
12
REP-AFB
14
REPSW2x16
14
Flange
14
Control
3
Isolation switch
4
Accessories
for Installation
Components for a solid fuel or biomass-burning boiler
5
A natural draught chimney system is designed to work at average conditions
for the region. So, when a solid fuel or biomass boiler is used all year round,
the variable climatic conditions will sometimes lead to insufficient chimney
draught. The use of a chimney fan system will ensure the correct chimney
draught under any climatic conditions at all times.
1
4
3
When a biomass burning appliance, for example a pellet
stove, has chimney draught problems, this can mean that
lighting the fire can be difficult and may cause soot and
smoke to be expelled back into the room. Insufficient
chimney draught can also lead to poor combustion, and
inefficient use of the fuel.
2
These problems can be solved by installing an exodraft
chimney fan system, because the system ensures the correct
chimney draught is available at all times.
Alarm
EBC20
EXHAUSTO
OK
Reset
An exodraft system for a solid fuel or biomass burning
boiler consists of an RS or RSV chimney fan with axial blades,
a controller and accessories. The EFC16, EFC18 or EFC35
controllers allow the user to manually adjust the chimney
draught as needed. The EFC18 controller is supplied with
a temperature sensor and will stop the chimney fan 45
minutes after the fire has gone out. It also starts the fan
automatically if the preset temperature in the chimney has
been reached by lighting the fire and the fan system has not
been started manually. However, it is not recommended to
light a fire unless the chimney fan is already in operation.
The EBC20 control regulates the fan speed automatically,
maintaining constant pressure in the chimney and creating
the optimal conditions to ensure correct combustion.
Find the components you need here:
1
2
Component
Type
Page
Chimney fan
RS with horizontal exhaust
6
RSV with vertical exhaust
8
EFC16
10
EFC35
10
EFC18
11
EBC20
13
REP-AFB
14
REPSW2x16
14
Flange
14
Control
3
Isolation switch
4
Accessories
for Installation
RS chimney fan
Design and construction
exodraft chimney fans are specially made to
continuously withstand flue gas temperatures of up to
250 °C and continue functioning in dirty environments.
They are constructed of corrosion resistant cast
aluminium and the screws and bolts are made of
stainless steel.
Description
An exodraft RS chimney fan is a specially designed
extractor fan with horizontal discharge.
The fans can be used with all types of fuel burning
appliances and are especially well-suited to appliances
burning solid fuel, such as biomass or solid-fuel boilers,
fireplaces and wood-burning stoves.
The fan is installed on top of a chimney and creates a
negative pressure (suction) along the full length of the
flue and chimney.
The fan is part of an exodraft system and must be
connected to an exodraft controller.
RS chimney fans are available in a range of sizes and
capacities. The RS9, RS12, RS14 and RS16 models are
equipped with stainless steel axial vanes for easy
cleaning.
The RS chimney fan has a temperature resistant, entirely
closed asynchronous motor, with ball bearings sealed
for life. The motor is positioned away from harmful flue
gases and is continuously cooled by a special cooling
plate and cooling vents. The heat-resistant supply cable
has cable-strain relief and is armoured. This all ensures
that the chimney fan has a long and reliable working
lifetime.
The chimney fan can be opened easily, so that a
chimney sweep can sweep the chimney and clean
the chimney fan without any problems. A safety mesh
covers the radial discharge for protection.
RS technical data
C
2
1
3
1. Motor cable
2. Top section
3. Motor
4. Vane
A
5
7
4
D
6
8
6
Model
RS009-4-1
RS012-4-1
RS014-4-1
RS016-4-1
5. Cooling plate
6. Base plate
7. Hinges
8. Locking screws
E
B
Motor data
rpm
1400
1400
1400
1400
V
1 x 230
1 x 230
1 x 230
1 x 230
Amp
0,3
0,4
0,6
1,2
Weight
kW*
0,05
0,09
0,13
0,29
kg
9
14
18
25
Dimension (mm)
A
250
275
330
405
B
300
365
420
480
CØ
285
350
395
450
*Power consumption at ambient temperature of 20 °C
The RPM of the above fan models are infinitely adjustable
Motor protection IP rating IP54
Insulation class F
The RS009 and RS012 fans can also be supplied with an octagonal bottom section, specially designed for circular chimneys.
D
75
85
100
100
EØ
220
280
330
380
RS sound data
7
Sound levels to external surroundings
Lw (dB) measured in accordance to ISO 3744
Lw (dB)
Model
125 Hz
250 Hz
500 Hz
1000 Hz
2000 Hz
4000 Hz
8000 Hz
Lp
dB (A)
54
64
75
81
50
60
69
76
47
55
65
72
43
52
62
69
38
48
57
64
31
42
51
58
25
34
44
52
21
30
41
47
RS009-4-1
RS012-4-1
RS014-4-1
RS016-4-1
Tolerance +/- 3 dB.
Lw = sound effect level dB (reference: 1 pW)
Lp = sound pressure level dB (A) at 10 m distance from the fan at half spheric sound distribution
Lp (5 m) = Lp (10 m) + 6 dB
Lp (20 m) = Lp (10 m) - 6 dB
RS capacity diagram
The capacity diagram shown below is only for illustration. Contact exodraft or your nearest dealer to calculate the
correct fan size.
Ps [Pa]
250
200
RS016
150
RS014
100
RS012
50
RS009
Type
Test flue
diameters
RS009
Ø 160 mm
RS012
Ø 200 mm
RS014
Ø 250 mm
RS016
Ø 315 mm
at 1400 rpm
0
500
100
200
1000
300
1500
400
2000
500
600
2500
700
3000
800
3500
900
1000
m3/h
l/s
PLEASE NOTE: The capacity diagrams are measured with a flue gas temperature of 20 °C. The fan's capacity changes
with the temperature of the flue gases. The correction of the capacity can be calculated using the following
equation:
Ps = Ps x 273 + t Ps = static pressure
20
t
293
t = temperature measured in °C
Example
System demand:
Fan selection:
500 m3/h and 90 Pa at 180 °C
500 m3/h and 139 Pa at 20 °C
RSV chimney fan
Design and construction
exodraft chimney fans are specially made to
continuously withstand flue gas temperatures of up to
250 °C and continue functioning in dirty environments.
They are constructed of corrision resistant cast
aluminium and the screws and bolts are made of
stainless steel.
Description
An exodraft RSV chimney fan is a specially designed
extractor fan with vertical discharge.
The fans can be used with all types of fuel burning
appliances and are especially well-suited to appliances
burning solid fuel such as biomass or solid-fuel boilers,
fireplaces and wood-burning stoves.
The fan is installed on top of a chimney and creates a
negative pressure along the full length of the flue and
chimney.
The RSV9, RSV12, RSV14 and RSV16 models are
equipped with axial stainless steel vanes. The RSV250,
RSV315 and RSV400 models are equipped with a cast
aluminium centrifugal impeller and are used for larger
installations, where multiple fireplaces are connected to
the same chimney.
The RSV chimney fan has a temperature resistant,
entirely closed asynchronous motor, with ball bearings
sealed for life. The motor is positioned away from
harmful flue gases and is continuously cooled by a
special cooling plate and cooling vents. The heatresistant supply cable has cable-strain relief and is
armoured. This all ensures that the chimney fan has a
long and reliable working lifetime.
The chimney fan can be opened easily, so that a
chimney sweep can sweep the chimney and clean
the fan without any problems. The exhaust vent has a
protective stainless-steel grille.
The fan is part of an exodraft system and must be
connected to an exodraft controller.
RSV technical data
2
1
3
1. Connecting cable
2. Top section
3. Motor
4. Vane/centrifugal impeller
A
7
6
E
8
4
8
5
5. Bottom section
6. Locking screws
7. Handle
8. Hinges
D
C
B
Model
RSV009-4-1
RSV012-4-1
RSV014-4-1
RSV016-4-1
RSV250-4-1
RSV315-4-1
RSV400-4-1
Motor data
rpm
1400
1400
1400
1400
1400
1400
1400
V
1 x 230
1 x 230
1 x 230
1 x 230
1 x 230
1 x 230
1 x 230
Amp
0,2
0,4
0,8
1,8
0,8
1,8
2,9
*Power consumption at ambient temperature of 20 °C
The RPM of the above fan models are infinitely adjustable
Motor protection IP rating IP54
Insulation class F
Weight
kW*
0,05
0,07
0,16
0,32
0,16
0,37
0,60
kg
13
17
24
35
27
37
47
Dimension (mm)
A
250
280
335
380
335
380
430
BxB
310
390
485
580
485
580
650
CxC
240
310
385
465
385
465
525
DØ
215
275
335
365
250
315
400
E
70
80
100
115
100
115
130
RSV sound data
9
Sound levels to external surroundings
Lw (dB) measured in accordance with ISO 3744
Lw (dB)
Model
125 Hz
250 Hz
500 Hz
1000 Hz
2000 Hz
4000 Hz
8000 Hz
Lp
dB (A)
RSV009-4-1
57
55
54
49
40
35
26
26
RSV012-4-1
64
62
61
55
51
46
40
33
RSV014-4-1
71
70
68
61
56
50
44
40
RSV016-4-1
76
76
70
65
60
55
49
44
RSV250-4-1
RSV315-4-1
64
71
68
75
66
70
65
73
61
68
49
57
45
52
41
48
RSV400-4-1
76
80
75
79
74
62
57
53
Tolerance +/- 3 dB
Lw = sound effect level dB (reference: 1 pW)
Lp = sound pressure level dB (A) at 10 m distance from the fan at half spheric sound distribution
Lp (5 m) = Lp (10 m) + 6 dB
Lp (20 m) = Lp (10 m) - 6 dB
RSV capacity diagrams
The capacity diagrams shown below are only for illustration. Contact exodraft or your nearest dealer to calculate
the correct fan size.
Ps [Pa]
250
Ps [Pa]
500
200
RSV016
150
400
RSV315
RSV014
300
Test flue
diameters
RSV009
RSV012
RSV014
Ø 160 mm
Ø 200 mm
Ø 250 mm
200
RSV012
RSV200
50
100
RSV009
500
100
200
1000
300
1500
400
2000
500
600
2500
700
3000
800
RSV016 Ø 315 mm
RSV250 Ø 250 mm
RSV315 Ø 315 mm
RSV400 Ø 400 mm
at 1400 rpm
RSV250
100
0
Type
RSV400
RSV160
3500 m3/h
900
l/s
0
1000
0
2000
500
3000
4000
1000
5000 m3/h
l/s
PLEASE NOTE: The capacity diagrams are measured with a flue gas temperature of 20 °C. The fan's capacity changes
with the temperature of the flue gases. The correction of the capacity can be calculated using the following
equation:
Ps = Ps x 273 + t Ps = static pressure
20
t
293
t = temperature measured in °C
Example
System demand:
Fan selection:
500 m3/h and 90 Pa at 180 °C
500 m3/h and 139 Pa at 20 °C
EFC16 and EFC35 manual controls
EFC16
EFC35
Description
EFC16 and EFC35 are electronic speed regulators used
to manually control exodraft chimney fans.
The EFC16 or EFC35 speed regulators adjust the
chimney fan's speed, thereby making it possible to
control the chimney fan's capacity (draught) in the
range 25–100 %.
Function
The EFC16 and EFC35 speed regulators are designed for
manual control. When the knob on these controllers is
turned to the right, it will click and the fan will turn on at
full rpm. As the knob is rotated clockwise, the fan speed
will be reduced. To turn the fan off, the knob must be
turned all the way anti-clockwise, until it has passed the
on/off point again.
The speed regulators have a built-in ON/OFF switch in
the control knob, a built-in minimum-speed trimmer,
and an LED to indicate operation. They are CE-certified.
EFC16 or EFC35 control units must have a REP-AFB
isolation switch mounted on the chimney. The isolation
switch must be installed by an authorised electrician.
EFC16 and EFC35 technical data
Height (mm)
85
102
Width (mm)
85
74
Depth (mm)
52
67
Load (Amp)
Max. 1.5 A
Max. 3.5A
Fuse (Amp)
T 1.6 A
T4A
Power supply
230 V AC, 50 Hz
230 V AC, 50 Hz
Ambient
temperature
0–40 °C
0–35 °C
IP-rating
IP30
IP30
Casing material
ABS
ABS
White
White
RS009/012/014/016
RSV009/012/014
RSV016
Colour
Usable with the
following fans
listed in this
brochure:
EFC16
40
EFC35
22
EFC16
85
Description
85
32, 5
60
12
52
70
6,5
EFC35
102
10
74
52
48,5
67
11
EFC18
EFC18
11
Temperature sensor
Description
The EFC18 is a manual nine-step speed regulator
with an integrated automatic START/STOP for the
exodraft chimney fan. It also features a boost
function, to make lighting the fire easier. The EFC18
controller comes with a temperature sensor to be
fitted under the fan.
Function
The EFC18 controller switches the chimney fan on
with a simple press of a button on the control panel.
To ensure sufficient up-draught when lighting
the fire, the fan will run at full speed for seven minutes
unless turned down manually. After
the start up period the fan will modulate down
to the speed it was running the last time it was in
operation.
When re-stoking the fire, press the operating button
once. The EFC18 control will then run the fan in boost
mode for three minutes so no smoke or dust will escape
into the room.
The EFC18 temperature sensor, which is
installed under the chimney fan, registers falling
temperature. As the fire dies out and the flue
temperature drops, the controller will (at a preset
temperature of 20, 40 or 80°C) run the fan for 45
minutes before stopping it. This ensures that all the
material in the fire has combusted and also that the fan
is automatically started if a chimney temperature above
a set level is registered.
The fan speed can always be adjusted manually
during operation, but the temperature sensor will
prevent the fan from being turned off while the fire
is still burning and thereby avoid damaging the fan
motor and eliminate the risk of spillage.
A REPSW2x16 isolation switch must be fitted to
the chimney when the EFC18 control system is
installed. The isolation switch must be installed by
an authorised electrician.
Height (mm)
85
Width (mm)
85
Depth (mm)
32.5
Load (Amp)
1.2 A
Fuse (Amp)
T 1.25 A
Power supply
230 V AC, 50 Hz
Temperature sensor range
-50 °C to +400 °C
Ambient temperature
0–40 °C
IP-rating
IP30
Casing material
ABS
Colour
Usable with the following fans
listed in this brochure:
White
RS009/012/014/016 and
RSV009/012/014
40
EFC18
22
Description
85
EFC18 technical data
85
32,5
60
12
70
6,5
12
EW41 wireless control
Description
The wireless control EW41 from exodraft , is used to
regulate chimney fans for solid fuel fires, such as open
fires or wood-burning stoves.
EW41
Power unit and Temperature
sensor
Optional accessories
yy Installation kit for steel chimneys.
yy Mains adapter (230 V) for the control panel.
yy Repeater unit to maintain signal strength for those
installations where the control panel and power
unit are placed far away from each another.
EW41 technical data
Description
EW41
EW41
Frequency
Protocol
Range
868,42 MHz
Z-wave
~ 12 m inside buildings
Control box
Dimensions (w x h x d)
Material
Ingress protection
Voltage
Fuse
Current out
Operating temperature
Temperature sensor
Power consumption (standby)
122 x 120 x 55 mm
ABS
IP64
230 V ±10 %, 50 Hz
T 2.0
2 Ampere
-30 °C to 60 °C
-50 °C to 450 °C
1W
Control panel
Dimensions (w x h x d)
Material
Operating temperature
Ingress protection
Battery
Battery lifetime
130 x 100 x 44 mm
ABS
0 °C til 40 °C
IP20
4 pcs. AA (LR6)
approx. one year
EW41 consists of:
yy a control panel
yy a control box with fan repair switch and 5 m cable
that plugs into the mains
yy a temperature sensor to be placed under the fan
(Must be connected to the control box)
The EW41 control panel lets you start and stop the fan
or regulate its speed. The panel saves the last operating
setting and you can read the consumption data in the
display.
The temperature sensor automatically monitors the
system’s temperature to prevent possible overloading
caused by omission. When the fire is lit, the system will
switch on automatically even if you do not activate
the EW41. Once the fireplace is cold, the fan turns off
automatically, so the heat from the dwelling is not sucked
away.
EW41 boosts the chimney draught for seven minutes. So
lighting the fire is quick and easy.
The controller signals when it is time to re-stoke the fire.
Once you have stoked the fire, the panel is activated and
chimney draught is increased for three minutes. This
prevents unpleasant smoky down draughts and your fire
lights faster.
The control panel monitors chimney draught and triggers
the alarm if:
yy
yy
yy
yy
the repair switch is switched off
the fan power fails
there is no connection to the control box
there is risk of a chimney fire because chimney
temperature is too high.
The EW41 controller uses radio wave (Z-wave)
communication, which is a very safe system as all
commands are confirmed and there is no risk of
interference from other equipment.
EBC20 automatic control
13
Description
The EBC20 is an automatic control system for boiler
installations and for other installations in which
multiple heat sources are connected to the same
chimney. The control monitors and maintains a
specific draught by maintaining a constant pressure.
EBC20
XTP sensor
EBC20 technical data
B
a
cd
Description
EBC20
EBC20EU01/EBC20EU02
Height x width x depth
Weight
IP-rating / material
Voltage (A)
Power consumption
Fuse (B)
Temperature
Monitoring range
204.3 x 239.5 x 77.2 mm
1.62 kg
IP54/ABS PA758
230 V AC ±10 %, 50 Hz ±1 %
475 W (3,7 A)
T4A
-20 °C to +60 °C
-500 to +500 Pa
XTP sensor
Dimension (w x h x d)
Operating temperature
Monitoring range
Max. distance between EBC20
and XTP sensor
IP-rating
EBC20EU01 Inputs
Digital inputs (D11 & D12) (C)
Pressure sensor (XTP) input
Pressure switch (PDS) input
EBC20EU01 Outputs
Digital relay outputs
(DO1 & DO2) (D)
Motor regulator
Motor start/stop relay
Control signal 0–10 VDC
24 VDC power supply
Alarm output relay
75 x 92 x 49 mm
0 to 70 °C
0 to +150 Pa
100 m
IP54
18-230 V AC/DC
0 to 10 V DC, 20 mA
24 V DC, 20 mA
250 V AC, 8 A,
Supply voltage -3 %, 3 A
250 V AC, 8 A
20 mA
100 mA
250 V AC, 8 A
The control may only be used with exodraft fans.
The EBC20 system consists of an EBC20 controller,
which can be positioned anywhere, and a pressure
transducer (XTP sensor) which is positioned in the
chimney.
Function
In installations where several fireplaces or stoves are
connected to the same chimney, the chimney fan
operates continuously. The EBC20 controller monitors
and maintains a specific draught by maintaining
a constant pressure. The pressure in the chimney
is measured by the XTP sensor. If the draught falls
below the set value, the speed of the chimney fan
is regulated until the draught reaches the required
level again.
The EBC20 is usable with all exodraft chimney fan
types.
EBC20EU01
EBC20EU02
Controls for indoor installation.
Controls for outdoor installation.
14
Isolation switch
It is a legal requirement that an isolation switch is installed in the immediate
vicinity of the chimney fan, so that, for example, chimney sweeps can
disconnect the electrical current to the chimney fan. The type of isolation
switch required depends on the chimney fan control system.
REPSW2x16
REP-AFB
Type
Description
Used with controls
REP-AFB
2-pole isolation switch
EFC16, EFC35, EW41*, EBC20
REPSW2x16
4-pole** isolation switch
EFC18
* EW41 is delivered with the repair switch
** 3-pole with help switch
FR flange
FR flanges from exodraft are used to install exodraft chimney fans on steel
chimneys.
The flanges are made of stainless steel and ensure that the chimney fans
have a flat and level installation base. The flange is supplied with four
vibration dampers that reduce vibrations and help create a stable base for
the chimney fan.
The diameter of the flange spigot is 3 mm smaller than the diameter of the
chimney. For example, the diameter of the spigot of an FR1-200 is Ø 197 mm,
designed to fit into a chimney opening with a Ø 200 mm diameter.
FR
The flange range caters for all types of chimney fans and chimneys. Flanges
with diameters other than those shown in the table can be made to order.
FR-02
Type
mm
Chimney diameter
Chimney fan
FR1
240 x 240
125 - 150 -175 - 200
RSV009, RSV160
FR2
310 x 310
125 - 150 - 175 - 200 - 250
RS009, RS255, RSV012, RSV200
FR3
395 x 395
150 - 175 - 200 - 250 - 300- 350
RS012, RS014, RS285, RSV014, RSV250
FR4
500 x 500
200 - 250 -300 - 350 - 400 - 450
RS016, RSV016, RSV315, RSV400, RSV450
FR2-02
310 x 310
150-160-200
RS009-4-1-02
FR3-02
395 x 395
150-200
RS012-4-1-02
Spigot length 120 mm
Other fitting accessories
Four levelling screws type RSD can be installed between the fan and the chimney to
create dilution air in brick chimneys if the temperature in the chimney is too high.
If dilution air is required, it is important to take the increased capacity need into
consideration when sizing the fan system.
Installing a chimney fan
15
The chimney fan is installed on top of the chimney. The chimney fan
is supplied as standard with adjustable location brackets, armoured
power cable, a safety wire and a mineral wool mat, which ensures
vibration-free operation.
When installing a fan onto a brick chimney the location brackets are
fitted under the chimney fan.
If the chimney fan is to be fitted onto a steel chimney, then a flange
and vibration dampers must be used instead of location brackets
The flange, which includes vibration dampers, must be ordered
separately.
NB! If the chimney has been used previously to a fan being installed,
then it should be cleaned before the chimney fan is switched on,
thus reducing the risks of a chimney fire.
Hiding the chimney fan
Installation of exodraft chimney fans on top of chimneys can
sometimes be difficult due to special site conditions such as listed
buildings or special architectural demands. For those installations it
is possible to make the fans virtually invisible.
Contact exodraft for assistance if such a solution is needed.
Service and maintenance
The chimney fan should be cleaned as often as
needed (at least once a year) depending on the
type of fire fuel.
When the fan is open, it is easy to clean it while
the chimney is being swept.
The chimney fan must always be running when there is a fire in the fireplace, stove or boiler. exodraft
provides a two-year manufacturer's warranty. The exodraft warranty does not include damage caused by fire.
exodraft’s extensive product range is based on more than 50 years of experience and
knowledge in the field of combustion and chimney draft technology.
Our products are known for high safety and quality and we are helping to set the standards
and requirements for draft technology.
exodraft products are all fully documented in accordance with current national and
international standards and are sold in more than 40 countries – for small domestic
fireplaces in private homes to larger commercial and industrial boiler installations.
Decentralized
multiple fireplaces
connected to same
chimney
Solid fuel and biofuel boilers
(pellets etc.)
Bakeries
Industry
Restaurants and pubs
DK: exodraft a/s
NO: exodraft a/s
C. F. Tietgens Boulevard 41
DK-5220 Odense SØ
Tel: +45 7010 2234
Fax: +45 7010 2235
[email protected]
www.exodraft.dk
Fjordgløttveien 11
NO-3060 Svelvik
Tel: +47 3329 7062
Fax: +47 3378 4110
[email protected]
www.exodraft.no
SE: exodraft a/s
UK: exodraft Ltd.
Årnäsvägen 25B
SE-432 96 Åskloster
Tlf: +46 (0)8-5000 1520
Fax: +46 (0)340-62 64 42
[email protected]
www.exodraft.se
Unit 3, Lancaster Ct.
Cressex Business Park
GB-High Wycombe HP12 3TD
Tel: +44 (0)1494 465 166
Fax: +44 (0)1494 465 163
[email protected]
www.exodraft.co.uk
Gas fireplaces
Oil and gas boilers
Decentralized
multiple heating
appliances connected
to same chimney
DE: exodraft GmbH
Rosengartenstr. 9
DE-55569 Monzingen
Tel: +49 (0)6751 855 599-0
Fax: +49 (0)6751 855 599-9
[email protected]
www.exodraft.de
3100110-0113. Fotos: sxc.hu & exodraft
Solid fuel and woodburning stoves and
fireplaces