Document

Rittal PMC
Technical Specifications
7857.010
7857.015
7857.030
7857.110
7857.020
7857.040
7857.120
10 – 15 – 20 – 30 – 40 kVA
Uninterruptible Power Supply (UPS)
Modular, n+1 redundant, three-phase
On-line, Double-Conversion, VFI
A3346402IT74-GB
A3346402IT74-GB
2
CONTENTS
TECHNICAL SPECIFICATIONS POWER MODULAR CONCEPT PMC ..................................................3
1. GENERAL DATA ................................................................................................................................3
2. RECTIFIER DATA ..............................................................................................................................4
3. BATTERY DATA .................................................................................................................................4
4. INVERTER DATA ...............................................................................................................................4
5. POWER MANAGEMENT DISPLAY (PMD) ........................................................................................5
6. OPTIONALS........................................................................................................................................5
7. TECHNICAL SPECIFICATIONS POWER MODULAR CONCEPT BASIC ........................................6
7.1 MECHANICAL CHARACTERISTICS PMC BASIC....................................................................6
7.2 BLOCK DIAGRAM PMC BASIC .................................................................................................8
7.3 CABLE SECTIONS AND FUSE RATINGS RECOMMENDED BY EUROPEAN STANDARDS
ALTERNATIVELY, LOCAL STANDARDS TO BE RESPECTED......................................................8
8. TECHNICAL SPECIFICATIONS POWER MODULAR CONCEPT TWIN..........................................9
8.1 MECHANICAL CHARACTERISTICS PMC TWIN (NOT AVAILABLE FOR 40KVA MODULE) ..........9
8.2 BLOCK DIAGRAM PMC TWIN ................................................................................................10
8.3 CABLE SECTIONS AND FUSE RATINGS RECOMMENDED BY EUROPEAN STANDARDS
ALTERNATIVELY, LOCAL STANDARDS TO BE RESPECTED....................................................10
9. TECHNICAL SPECIFIKATIONS POWER MODULAR EXTENDED TWIN......................................11
9.1 MECHANICAL CHARACTERISTICS PMC EXTENDED TWIN .................................................11
9.2 BLOCK DIAGRAM EXTENDED TWIN......................................................................................13
9.3 CABLE SECTIONS AND FUSE RATINGS RECOMMENDED BY EUROPEAN STANDARDS
ALTERNATIVELY, LOCAL STANDARDS TO BE RESPECTED....................................................13
3
A3346402IT74-GB
TECHNICAL SPECIFICATIONS POWER
MODULAR CONCEPT PMC
10, 15, 20, 30 and 40 kVA (three phase input and output)
1. GENERAL DATA
Output Rated Power
kVA
10
15
20
30
40
0.8
Output Power Factor
On-Line, Double Conversion, VFI
Topology
Second Generation, Tansformerless
Technology
Modular, Parallelable
Construction
For redundancy and/or capacity:
- Standard up to 10 modules
- Without limitation on request
Parallel Configuration
Double Conversion AC-AC efficiency with batt. fully charged
100%/75%/50%25% Linear Load (cos=0.8ind)
%
94.5/94.5/93/91
94.5/94.5/93/91
94.5/94.5/93/91
95/95/93.5/92
95/95/93.5/92
100%/75%/50%/25% Linear Load (Resistive cos=1)
%
94/94/92/90
94/94/92/90
94/94/92/90
94/94/92.5/91
94/94/92.5/91
100%/75%/50%/25% Non-linear Load (EN50091-1)
%
93/93/91/90
93/93/91/90
93/93/91/90
93/93/92/91
93/93/92/91
%
98
98
98
98
98
1600
Eco-Mode efficiency (load on by-pass) at 100% load
Heat Dissipation With 100% Load (cos=
0.8ind)
W
400
600
800
1200
Heat Dissipation With 100% Load (Resistive cos=
1)
W
480
720
960
1450
1920
Heat Dissipation With 100% Non-linear Load (EN50091-1)
W
560
840
1120
1680
2240
Airflow (25° - 30°C) with Non-linear Load (EN50091-1)
3
m /h
110
150
200
300
400
Audible Noise with 100% / 50% Load
dBA
55/49
57/49
57/49
59/51
63/53
Ambient Temperature for UPS
°C
0 – 40
Ambient Temperature for Batteries (recommended)
°C
20 - 25
Storage Temperature
°C
-25 - +70
Max. 6 months
Battery Storage Time at Ambient Temperature
Fan-assisted
Cooling
Max. 95% (non-condensing)
Relative Air-humidity
Standards
Safety
Electromagnetic Compatibility
Performance
EN 50091 - Part 1 (IEC 62040-1, IEC 60950)
EN 50091 - Part 2 (IEC 62040 –2)
EN 50091 - Part 3 (IEC 62040 –3)
Provided with UPS
Transportation Palette
Accessibility
Totally front accessibility for service and maintenance (no need for side, top
or rear access)
Positioning
Min. 10cm rear space (required for fan)
From front and bottom
Input and Output Power Cabling
For remote signalling and automatic computer shutdown
Dry Port (Volt-free contacts)
For monitoring and integration in network management
Smart Port (RS 232)
EMERGENCY OFF (Normally closed)
GEN-ON (Normally open)
BATTERY TEMP. SENSOR
Input Terminals
UPS Module Weight
UPS Module Size (WxHxD)
kg
10 – 20kVA = 40kg, 30kVA = 55kg ; 40kVA = 58kg
mm
483 x 400 x 675
4
A3346402IT74-GB
2. RECTIFIER DATA
Input Voltage
Input Voltage Tolerance (ref to 3x400/230V)
Input Frequency
V
3x380/220V+N, 3x400V/230V+N, 3x415/240V+N
For Loads:
<100%(-23%,+15%)
V (%)
<80%(-30%,+15%)
Hz
<60%(-40%,+15%)
35 – 70
Input Power Factor
0.98
Input Current Form
Sinewave THDI = 7÷9% at 100% load
Limited by soft start
Inrush Current
Model
kVA
10
15
20
30
40
Input Power with rated output power and charged battery
kW
8.6
12.9
17.2
25.8
34
Max. Input Power with rated output power and discharged battery
kW
9.6
13.8
19.2
28.2
38
3. BATTERY DATA
Maximum Battery Charger Current (standard)
10 A
Battery Charging Curve
IU (DIN 41773)
Temperature Controlled Battery Charger
Yes
Battery Charger Ripple
Ripple-free battery charging
Battery Test
Automatic and periodic (adjustable)
Battery Type
Variable Number of 12V Battery Blocks
Lead-acid, Maintenance-free and NiCd
30-50 blocks for 10-20kVA, 40-50 blocks for 30kVA and 50 blocks for 40kVA
4. INVERTER DATA
Output Rated Power
KVA
Output Rated Voltage
V
10
15
20
30
3x380/220V, 3x400/230V, 3x415/240V
0.8
Output Power Factor
Output Voltage Stability
- Static
%
< +/- 1
- Dynamic (with load Step 0-100%, 100-0%)
%
< +/- 4
Output Voltage Distortion
- With Linear Load
%
+/-2
- With Non-linear Load (EN 50091)
%
< +/- 3 (according to EN 50091-1)
Recovery Time After Load Jump (0-100%, 100-0%)
msec
20
%
100% (all 3 phases regulated independently)
Permissible Unbalanced Load
sinewave
Output waveform
Hz
50 or 60
- Free-running, Quartz Oscillator
%
+ / - 0.1
- Synchronized with mains (adjustable)
%
+/-4
%
125 for 10min. and 150 for 1min.
Output Frequency
Output Frequency Tolerance
Overload Capability
Crest - Factor
3:1
40
5
A3346402IT74-GB
5. POWER MANAGEMENT DISPLAY (PMD)
The user-friendly PMD consists of three parts the MIMIC DIAGRAM, CONTROL KEYS and LCD that
provides the necessary monitoring information about the UPS.
MIMIC DIAGRAM
The mimic diagram serves to give the general status of the UPS. The LED-indicators show the power
flow status and in the event of mains failure or load transfer from inverter to bypass and vice-versa the
corresponding LED-indicators will change colour from green (normal) to red (warning). The LED’s LINE
1 (rectifier) and LINE 2 (bypass) indicate the availability of the mains power supply. The LED’s
INVERTER and BYPASS if green indicate which of the two are supplying power to the critical load.
When the LED-indicator BATTERY is lit it means that the battery due to mains failure is supplying the
load. The LED-indicator ALARM is a visual indication of any internal or external alarm condition. At the
same time the audible alarm will be activated.
PUSHBUTTONS
The pushbuttons serve to manage the UPS by performing commands. The 2xON/OFF pushbuttons
serve to start-up or shutdown the UPS if pressed simultaneously. The pushbuttons UP and DOWN allow
working through the PMD-menu. The RESET pushbutton serves to cancel the audible alarm in the event
of a disturbance. If the alarm condition was only transient the LED-indicator ALARM would also
extinguish otherwise it will remain on (red).
DISPLAY
The 2 x 20 character LCD simplifies the communication with the UPS. The menu driven LCD enables
the access to the EVENT REGISTER, or to monitor the input and output U, I, f, P, Autonomy Time and
other Measurement’s, to perform commands like start-up and shut-down of INVERTER or load transfer
from INVERTER to BYPASS and vice-versa and finally it serves for the DIAGNOSIS (SERVICE MODE)
for adjustments and testing (for more details see the USER MANUAL of Power Modular Concept).
Power Modular Concept
ON/OFF
LINE 2
BY PASS
BATTERY
LINE 1
ON/OFF
ALARM
INV
RESET
ENTER
Power Management Display (PMD) of Power Modular Concept.
6. OPTIONALS
Extended Battery Autonomies
Optional Battery Charger
In matching battery frames TS 8
For longer autonomies
Remote Signalling Panel (RSP)
For UPS-Status indication
Parallel Configuration (standard)
A number of units may be paralleled
for redundancy or capacity PMC Extended Twin
PMC-Software
SNMP - Adapter
Input or Output Isolation Transformer
For automatic shut-down and monitoring
For network management and remote monitoring
For special voltages or for galvanic isolation
6
A3346402IT74-GB
7. TECHNICAL SPECIFICATIONS POWER MODULAR CONCEPT
BASIC
7.1 MECHANICAL CHARACTERISTICS PMC BASIC
kVA
MODEL
10
15
mm
Dimensions (WxHxD)
20
30
40
600 x 2000 x 1000
Protection Degree
600 x 2000 x
1000
IP 20
Ventilation
Fan assisted
Colour
RAL 7035
m
Foot Print
2
0.41
Maximum Output Power of one PMC Basic
40 kVA
Dimensions of PMC Basic (Depth 1000mm)
PMC Basic Frame: TS 8
Power
(kVA)
2000mm
600mm
TS 8
Maximum
Autonomy
(min.)
Maximum
Battery
Frame
Type
UPS
+Battery
Weight
(kg)
10
0
____
TS 8
200
10
16
40 x 7Ah
TS 8
300
10
16
(2x30) x 7Ah
TS 8
350
10
24
(2x40) x 7Ah
TS 8
400
10
40
(3x40) x 7Ah
TS 8
500
15
0
____
TS 8
205
15
10
(2x30) x 7Ah
TS 8
355
15
14
(2x40) x 7Ah
TS 8
405
15
24
(3x40) x 7Ah
TS 8
505
20
0
____
TS 8
205
20
10
(2x40) x 7Ah
TS 8
405
20
16
(3x40) x 7Ah
TS 8
505
30
0
____
TS 8
210
30
10
(3x40) x 7Ah
TS 8
510
Battery Frame TS 8
In the Battery Frame TS 8 to 90 x 24Ah / 28Ah
may be fitted. The maximum achievable autonomy
with one additional Battery Frame TS 8 are:
Maximum
Power
Maximum
Autonomy
(kVA)
Battery
(min.)
2000mm
800mm
1000mm
Frame
Type
UPS
+Battery
Weight
(kg)
10
132
90x24Ah
TS 8
1160
15
78
90x24Ah
TS 8
1160
20
53
90x24Ah
TS 8
1160
30
32
90x24Ah
TS 8
1160
7
A3346402IT74-GB
Dimensions of PMC Basic (Depth 1000mm) for 40kVA
PMC Basic Frame: TS 8
Power
(kVA)
Autonomy
(min.)
Battery
Type
Frame
Type
Weight
(kg)
40
0
____
TS 8
280
40
8
(3x50) x 7Ah
TS 8
660
40
12
(4x50) x 7Ah
TS 8
790
2000mm
600mm
TS 8
Battery Frame TS 8
In the Battery Frame TS 8 up to 100 x
24Ah / 28Ah may be fitted.
The maximum achievable autonomy with
one additional Battery Frame TS 8 are:
2000mm
800mm
1000mm
Power
(kVA)
Maximum
Autonomy
(min.)
Maximum
Battery
40
25
40
42
Frame
Type
UPS+Battery
Weight
(kg)
(2x50)x24Ah
TS 8
1370
(3x50)x24Ah
2xTS 8
2010
8
A3346402IT74-GB
7.2 BLOCK DIAGRAM PMC BASIC
7.3 CABLE SECTIONS AND FUSE RATINGS RECOMMENDED BY EUROPEAN
STANDARDS ALTERNATIVELY, LOCAL STANDARDS TO BE RESPECTED
STANDARD VERSION (SINGLE FEED INPUT)
Power (kVA)
Fuse A (Agl/CB)
Cable A
(IEC 60950-1:2001)
Cable D
(IEC 60950-1:2001)
Fuse E
+/N/-
Cable E
+/N/-
5x2.5
5x4
5x6
5x10
5x25
3x32A
3x63A
3x63A
3x80A
3x100A
3x4
3x10
3x10
3x16
3x25
3x20
5x2.5
10
3x25
5x4
15
3x40
5x6
20
3x63
5x10
30
3x80
5x25
40
VERSION ON REQUEST (DUAL FEED INPUT)
Power (kVA)
Fuse B (Agl/CB)
Cable B
(IEC 60950-1:2001)
Fuse C
(Agl/CB)
Cable C
(IEC 60950-1:2001)
Cable D
(IEC 60950-1:2001)
Fuse E
+/N/-
Cable E
+/N/-
10
15
20
30
40
3x20
3x25
3x40
3x63
3x80
5x2.5
5x4
5x6
5x10
5x25
3x20
3x25
3x40
3x63
3x80
4x2.5
4x4
4x6
4x10
4x25
5x2.5
5x4
5x6
5x10
5x25
3x32A
3x63A
3x63A
3x80A
3x100A
3x4
3x10
3x10
3x16
3x25
9
A3346402IT74-GB
8. TECHNICAL SPECIFICATIONS POWER MODULAR CONCEPT TWIN
8.1 MECHANICAL CHARACTERISTICS PMC TWIN (NOT AVAILABLE FOR 40KVA
MODULE)
MODEL
KVA
2x10
2x15
mm
Dimensions (WxHxD)
2x20
2x30
600 x 2000 x 1000
Protection Degree
IP 20
Ventilation
Fan assisted
Colour
RAL 7035
m2
Foot Print
0.41
Maximum Output Power of one PMC Twin
60 kVA
Dimensions of PMC Twin (depth 1000mm)
TS 8
TS 8
2000
Power
(kVA)
Autonomy
(min.)
Battery
Type
Frame
Type
Weight
(kg)
10 + 10
0
____
TS 8
265
10 + 10
7+7
(2x30)x7Ah
TS 8
415
10 + 10
10 + 10
(2x40)x7Ah
TS 8
465
10 + 10
16 + 16
2x(2x30)x7Ah
TS 8
575
15 + 15
0
____
TS 8
280
15 + 15
5+5
(2x30)x7Ah
TS 8
430
15 + 15
7+7
(2x40)x7Ah
TS 8
480
15 + 15
10 + 10
2x(2x30)x7Ah
TS 8
580
20 + 20
0
____
TS 8
280
20 + 20
5+5
(2x40)x7Ah
TS 8
480
20 + 20
7+7
2x(2x30)x7Ah
TS 8
580
30 + 30
0
____
TS 8
290
30 + 30
10
(3x40)x7Ah *)
TS 8
590
*) This battery is common for the 2 modules of 30kVA,
Two separate batteries (5+5)min. are available on request.
600mm
1000mm
Power
(kVA)
Maximum
Autonomy
(min.)
Maximum
Battery
Frame
Type
UPS +
Battery
Weight
(kg)
10 + 10
90 + 90
120x24Ah
TS 8
1535
15 + 15
55 + 55
120x24Ah
TS 8
1550
20 + 20
38 + 38
120x24Ah
TS 8
1550
30 + 30
46
120x24Ah*)
TS 8
1560
*) This battery is common for the 2 modules of 30kVA,
Two separate batteries (23+23)min. are available on request.
10
A3346402IT74-GB
8.2 BLOCK DIAGRAM PMC TWIN
MAINS (3x380V/220V,
3x400/230V,3x415/240V
Cable A
F4
Fuse E
Inverter
Rectifier
F5
Inverter
Cable C
Cable E
Fuse
E
Rectifier
F4
Inverter
F1 F2
Main.Bypass IA1
Rectifier
F5
Inverter
Static Switch
Static Switch
IA2-1
IA2-2
IA2-2
IA2-1
Twin Frame
Cable B
MAINS (3x380V/220V,
3x400/230V,3x415/240
F1 F2
Static Switch
Static Switch
Fuse C
F2
UPS module 2
Rectifier
Cable E
F1
F2
UPS module 1
F1
Fuse B
UPS module 1
Fuse A
VERSION ON REQUEST (DOUBLE INPUT FEED)
UPS module 2
STANDARD VERSION (SINGLE INPUT FEED)
Main.Bypass IA1
Twin Frame
Cable D
Cable D
Load
Load
8.3 CABLE SECTIONS AND FUSE RATINGS RECOMMENDED BY EUROPEAN
STANDARDS ALTERNATIVELY, LOCAL STANDARDS TO BE RESPECTED
STANDARD VERSION (SINGLE FEED INPUT)
Cable A
Power (kVA) Fuse A (Agl/CB)
(IEC 60950-1:2001)
3x40
5x6
10
3x40
5x6
10+10
3x63
5x10
15
3x63
5x10
15+15
3x80
5x16
20
3x80
5x16
20+20
3x100
5x25
30
3x100
5x25
30+30
Cable D
(IEC 60950-1:2001)
5x6
5x6
5x10
5x10
5x16
5x16
5x25
5x25
Fuse E
Cable E
+/N/-
+/N/-
3x32A
3x63A
3x63A
3x100A*
3x63A
3x125A*
3x80A
3x125A*
3x4
3x10*
3x10
3x25*
3x10
3x35*
3x16
3x35*
VERSION ON REQUEST (DUAL FEED INPUT)
Cable B
Cable C
Cable D
Power (kVA)
Fuse B (Agl/CB)
Fuse C (Agl/CB)
(IEC 60950-1:2001)
(IEC 60950-1:2001) (IEC 60950-1:2001)
3x40
5x6
3x40
4x6
5x6
10
3x40
5x6
3x40
4x6
5x6
10+10
3x63
5x10
3x63
4x10
5x10
15
3x63
5x10
3x63
4x10
5x10
15+15
3x80
5x16
3x80
4x16
5x16
20
3x80
5x16
3x80
4x16
5x16
20+20
3x100
5x25
3x100
4x25
5x25
30
3x100
5x25
3x100
4x25
5x25
30+30
*only valid for common battery use
Fuse E
Cable E
+/N/-
+/N/-
3x32A
3x63A*
3x63A
3x100A*
3x63A
3x125A*
3x80A
3x125A*
3x4
3x10*
3x10
3x25*
3x10
3x35*
3x16
3x35*
11
A3346402IT74-GB
9. TECHNICAL SPECIFIKATIONS POWER MODULAR EXTENDED
TWIN
9.1 MECHANICAL CHARACTERISTICS PMC EXTENDED TWIN
MODEL
KVA
3x10
mm
Dimensions (WxHxD)
3x15
3x20
3x30
3x40
600 x 2000 x 1000
Protection Degree
IP 20
Ventilation
Fan assisted
Colour
RAL 7035
m
Foot Print
2
0.41
Maximum Output Power of one Extended Twin
90kVA or 120 kVA
Dimensions of PMC Extended Twin(depth 1000mm)
TS 8
TS 8
2000
600mm
Power
(kVA)
Autonomy
(min.)
Battery
Type
Frame
Type
Weight
(kg)
10
0
____
TS 8
170
10 + 10
0
____
TS 8
215
10 + 10 + 10
0
____
TS 8
260
15
0
____
TS 8
175
15 + 15
0
____
TS 8
225
15 + 15 + 15
0
____
TS 8
275
20
0
____
TS 8
175
20 + 20
0
____
TS 8
225
20 + 20 + 20
0
____
TS 8
275
30
0
____
TS 8
180
30 + 30
0
____
TS 8
235
30 + 30 + 30
0
____
TS 8
290
1000mm
In the battery frame TS 8 up to 120 x 24Ah/28Ah batteries respectively may be fitted allowing the
maximum autonomies as shown in the table on the left bellow:
Power
(kVA)
Maximum
Autonomy
(min.)
Maximum
Battery
10+10+10
15+15+15
20+20+20
30+30+30
46+46+46
28+28+28
20+20+20
11+11+11
120x24Ah
120x24Ah
120x24Ah
120x24Ah
Frame Type
TS 8
TS 8
TS 8
TS 8
UPS +
Battery
Weight
(kg)
1530
1545
1545
1560
12
A3346402IT74-GB
Dimensions of PMC Extended Twin (depth 100mm) for 40kVA
TS 8
TS 8 (for separate battery)
TS 8 (for common battery)
Power
(kVA)
Autonomy
(min.)
Battery
Type
Frame
Type
Weight
(kg)
40
0
____
TS 8
190
40 + 40
0
____
TS 8
248
40 + 40 + 40
0
____
TS 8
306
2000
800mm
1000mm
Power
(kVA)
Maximum
Autonomy
(min.)
Maximum Battery
Frame Type
UPS + Battery
Weight (kg)
40+40+40
11+11+11
(3x50)x24Ah
2x TS 8
2032
In the battery frame TS 8 up to 120 x 24Ah/28Ah batteries respectively may be fitted allowing the
maximum autonomies as shown in the above table.
13
A3346402IT74-GB
9.2 BLOCK DIAGRAM EXTENDED TWIN
VERSION ON REQUEST (DUAL INPUT FEED)
Cable A
Inverter
Static Switch
Inverter
Static Switch
IA2-1
Rectifier
Inverter
Extended
Twin
Frame
Cable E
Cable C
Rectifier
Inverter
IA2-1
Inverter
Rectifier
Inverter
Static Switch
IA2-2
Extended
Twin
Frame
Maintenance Bypass IA1
Rectifier
F1 F2
Static Switch
Static Switch
IA2-3
MAINS (3x380V/220V,
3x400/230V,3x415/240V
F1 F2
Fuse
E
Static Switch
IA2-2
Cable B
UPS module 1
Fuse
E
Rectifier
UPS module 3
Rectifier
Fuse C
F1 F2
F1 F2
UPS module 2
Cable E
F1 F2
UPS module 1
F1 F2
Fuse B
IA2-3
Maintenance Bypass IA1
Cable D
Cable D
Load
Load
9.3 CABLE SECTIONS AND FUSE RATINGS RECOMMENDED BY EUROPEAN
STANDARDS ALTERNATIVELY, LOCAL STANDARDS TO BE RESPECTED
STANDARD VERSION (SINGLE FEED INPUT)
Power
(kVA)
10
10+10
10+10+10
15
15+15
15+15+15
20
20+20
20+20+20
30
30+30
30+30+30
40
40+40
40+40+40
Fuse A (Agl/CB)
3x63
3x63
3x63
3x100
3x100
3x100
3x100
3x100
3x100
3x125
3x125
3x125
3x200
3x200
3x200
Cable A
(IEC 60950-1:2001)
5x10
5x10
5x10
5x25
5x25
5x25
5x25
5x25
5x25
5x35
5x35
5x35
5x70
5x70
5x70
* only valid for common battery use
Cable D
(IEC 60950-1:2001)
5x10
5x10
5x10
5x25
5x25
5x25
5x25
5x25
5x25
5x35
5x35
5x35
5x70
5x70
5x70
Fuse E
Cable E
+/N/-
+/N/-
3x32A
3x63A*
3x100A*
3x63A
3x100A*
3x125A*
3x63A
3x125A*
3x160A*
3x80A
3x125A*
3x200A*
3x100A
3x160A*
3x250A*
3x4
3x10*
3x25*
3x10
3x25*
3x35*
3x10
3x35*
3x50*
3x16
3x35*
3x70*
3x25
3x50*
3x120*
UPS module 3
MAINS (3x380V/220V,
3x400/230V,3x415/240V
Fuse A
UPS module 2
STANDARD VERSION (SINGLE INPUT FEED)
14
A3346402IT74-GB
VERSION ON REQUEST (DUAL FEED INPUT)
Power (kVA)
10
10+10
10+10+10
15
15+15
15+15+15
20
20+20
20+20+20
30
30+30
30+30+30
40
40+40
40+40+40
Fuse B
(Agl/CB)
3x63
3x63
3x63
3x100
3x100
3x100
3x100
3x100
3x100
3x125
3x125
3x125
3x200
3x200
3x200
Cable B
(IEC 60950-1:2001)
5x10
5x10
5x10
5x25
5x25
5x25
5x25
5x25
5x25
5x35
5x35
5x35
5x70
5x70
5x70
*only valid for common battery use
Fuse C
(Agl/CB)
3x63
3x63
3x63
3x100
3x100
3x100
3x100
3x100
3x100
3x125
3x125
3x125
3x200
3x200
3x200
Cable C
(IEC 60950-1:2001)
4x10
4x10
4x10
4x25
4x25
4x25
4x25
4x25
4x25
4x35
4x35
4x35
4x70
4x70
4x70
Cable D
(IEC 60950-1:2001)
5x10
5x10
5x10
5x25
5x25
5x25
5x25
5x25
5x25
5x35
5x35
5x35
5x70
5x70
5x70
Fuse E
Cable E
+/N/-
+/N/-
3x32A
3x63A*
3x100A*
3x63A
3x100A*
3x125A*
3x63A
3x125A*
3x160A*
3x80A
3x125A*
3x200A*
3x100A
3x160A*
3x250A*
3x4
3x10*
3x25*
3x10
3x25*
3x35*
3x10
3x35*
3x50*
3x16
3x35*
3x70*
3x25
3x50*
3x120*