Quick Start Guide - ATV212 ENGLISH S1A5382501 DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH • Read and understand this quick start guide before performing any procedure with this drive. • The user is responsible for compliance with all international and national electrical code requirements with respect to grounding of all equipment. • Many parts of this drive, including the printed circuit boards, operate at the line voltage. DO NOT TOUCH. Use only electrically insulated tools. • DO NOT touch unshielded components or terminal strip screw connections with voltage present. • DO NOT short across terminals PA/+ and PC/- or across the DC bus capacitors. • Before servicing the drive: - Disconnect all power, including external control power that may be present. - Place a "DO NOT TURN ON" label on all power disconnects. - Lock all power disconnects in the open position. - WAIT 15 MINUTES to allow the DC bus capacitors to discharge. - Measure the voltage of the DC bus between the PA/+ and PC/- terminals to ensure that the voltage is less than 42 Vdc. - If the DC bus capacitors do not discharge completely, contact your local Schneider Electric representative. Do not repair or operate the drive. • Install and close all covers before applying power or starting and stopping the drive. Failure to follow these instructions will result in death or serious injury. Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this product. Information below is designed to use single drive connected to single motor with a motor cable length less than 50 meters (164 ft). In any other case, consult the ATV212 installation manual and programming manual on www.schneider-electric.com. Check your cables before connecting the drive with motor (length, power, shielded or unshielded). Motor cable length is _______(< 50 meters, 164 ft). 1 Check the delivery of the drive • Remove ATV212 from the packaging and check that it has not been damaged. WARNING DAMAGED DRIVE EQUIPMENT Do not operate or install any drive or drive accessory that appears damaged. Failure to follow these instructions can result in death, serious injury, or equipment damage. • Check that the drive reference printed on the label is the same as that on the delivery note corresponding to the purchase order. ATV212HU15N4 1.5KW - 2HP - 380 / 480V Write the drive Model Reference: _____________ ___________and Serial Number: ____________________________ 2 Check the line voltage compatibility • Check that the line voltage is compatible with the supply range of the drive. Line voltage _______ Volts Drive voltage range _______ Volts Drive range: ATV212 pppp M3X = 200 ... 240 V three-phase / ATV212 pppp N4p = 380 ... 480 V three-phase. 3 8B0915316127 Mount the drive vertically For a surrounding air temperature up to 40 °C (104 °F). ATV212W (a) (a) (a) (a) 50 mm (2 in.) (a) (c) (b) (a) (b) (a) ATV212H (b) 100 mm (4 in.) (c) 10 mm (0.4 in.) See installation manual on www.schneider-electric.com for other thermal conditions. www.schneider-electric.com 1/4 S1A53825 - 10/2010 4 Connect the drive: Power Connect the drive: Control choice 5 • Wire the drive to the ground. • Check circuit breaker rating or fuse rating. • Check that the motor voltage is compatible with the drive voltage. Motor voltage ______Volts. • Wire the drive to the motor. • Wire the drive to the line supply. [REMOTE configuration] 5.1 (Control by external reference) 0,6 N.m 5.3 lb.in • Wire the speed reference: PP: Internal supply for analogue inputs VIA: Analog/ logic input CC: Common ATV 2 12 PP 200...240 V ATV212 M3X RUN 2.2 to 10 kΩ % PRG CC VIA Hz MON Loc Rem • Wire the command: MODE ENT RUN STOP or Control command 2-wire: 380...400 V F: Run forward ATV 2 12 R: Run reverse P24: Internal supply F for logic inputs ATV212 N4 P24 R Do: 6 + 7 + 8 + 9.1 Do: 6 + 7 + 8 + 9.1 Do: 6 + 7 + 8 + 9.2 Control command 3-wire: F: Run forward R: Stop RES: Run reverse P24: internal supply for logic inputs Note: for ATV212H075ppp, ATV212HU15ppp, ATV212HU22ppp, to connect power, open the door, remove the terminal board, connect R/L1, S/L2 ,T/L3 and fix again the terminal board. ATV 212 F R RES P24 [LOCAL configuration] 5.2 (control by internal reference). Loc Rem 6 Apply power to the drive • Check that used Logic Inputs are not active (see F, R, RES, P24, open circuit). • Apply power to the drive. Run • At each power on , drive displays HELLO message, then run mode : mode 0. .0 7 Hz Set motor parameters • See on the motor Nameplate to set the following parameters. Menu Code Description Pt [Mot cont. mode sel.]: Motor control mode 0 [Constant V/Hz]: Constant V/Hz 1 [Variable Torque]: Variable torque 2 [Cst V/Hz+Boost]: Constant V/Hz with automatic torque boost 3 [SVC]: Sensorless vector control 4 [Economy]: Energy saving [Upper limit freq]: Nominal motor frequency on motor nameplate (Hz) [Motor Rated Voltage]: Nominal motor voltage on motor nameplate (V) [Motor rated current]: Nominal motor current on motor nameplate (A) [Motor rated speed]: Nominal motor speed on motor nameplate (rpm) [Motor Current Limit]: AUF [QUICK MENU] uL uLu F415 F--[EXTENDED MENU] F417 F601 www.schneider-electric.com Factory setting Limit current during motoring or braking (%) 2/4 Customer setting 1 50.0 drive rating drive rating drive rating 110 S1A53825 - 10/2010 Set motor parameters (continued) 7 Menu Code F--[EXTENDED MENU] Description F400 Customer setting Factory setting Set F400 [Auto-tuning drive] parameter to 2. The drive displays Atn1, the message disappears after a few seconds 0 Auto-Tunning for uLu, uL, F415 and F417 DANGER WARNING HAZARD OF ELECTRIC SHOCK OR ARC FLASH DAMAGED DRIVE EQUIPMENT • During auto-tuning, the motor operates at rated current. • Do not service the motor during auto-tuning. • It is essential that the following parameters uLu, uL, F415 and F417 are correctly configured before starting autotuning. • When one or more of these parameters have been changed after autotuning has been performed, F400 will return 0 and the procedure will have to be repeated. Failure to follow these instructions will result in death or serious injury. Failure to follow these instructions can result in death, serious injury, or equipment damage. Set basic parameters 8 Menu Code Description AU1 [Auto ramp] Automatic ramp adaptation: 0 [Disabled] 1 [Enable] - (ACC) and (dEC) 2 [ACC only] [Acceleration time 1]: Acceleration ramp and the time(s) [Deceleration time 1]: Deceleration ramp and the time (s) [Low limit frequency]: Motor frequency at minimum reference (Hz) [High speed]: Motor frequency at maximum reference (Hz) [Motor thermal prot.]: Motor Rated Current Overload Setting (%) [Switch. freq. level] Switching Frequency Level (kHz) Increasing the switching frequency may reduce audible motor noise. See the derating curves in the ATV21 2Installation Manual. ACC AUF [QUICK MENU] dEC LL UL tHr F--- [EXTENDED MENU] 9 F300 Customer setting Factory setting 1 ATV21 2 y 15KW = 10 s ATV212 u 18KW = 30 s 0. 0 50.0 100 8 to12 Set control choice 9.1 [REMOTE configuration] 9.2 [LOCAL configuration] Parameters factory settings: 2-wire control Menu _ F--[EXTENDED MENU] Code CMOd [Command mode sel] F111 [LI F selection] F112 [LI R selection] Setting 0 [Logic inputs] 2 [forward] RUN % PRG Hz MON 3 [reverse] Loc Rem MODE 3-wire control Menu _ F--[EXTENDED MENU] 10 ENT Code CMOd [Command mode sel] F111 [LI F selection] F112 [LI R selection] F113 [LI RES selection] Setting 0 [Logic inputs] 2 [forward] 49 [3-wire] 3 [reverse] RUN STOP RESET Start the motor www.schneider-electric.com 3/4 S1A53825 - 10/2010 Menus structure Programming mode Run mode RUN 0. .0 MODE Hz PRG ATV212 drive Power Up AUF Monitoring mode Submenu [Quick menu] ENT Submenu [ALL PARAM CHANGE] GrU MODE MODE AU1 [Auto ramp] F--- Submenu [EXTENDED MENU] ACC [Acceleration time 1] IO Submenu [I/O MENU] dEC [Deceleration time 1] COM Submenu [COMMUNICATION MENU] LL [Low limit frequency] Sr7 [Preset speed 7...1] UL [Upper limit freq] OLM [Motor overload prot] tHr [Motor thermal prot.] tHr [Motor thermal prot.] FM [AO scaling] ub [Mot Voltage Boost] Pt [Mot cont. mode sel.] uL [Motor rated freq.] uLu [Motor rated voltage] [Motor rated voltage] uLu uL Hz [Motor rated freq.] [Low limit frequency] UL [Upper limit freq] FH Fr-F [Direction] MODE (1) t0.10 [Drive run time 100h] Nbiii [Mdb com stat] Niiii [Drive service alarm] [Past fault] n 50 [Comm. counter 1] N 50 [Comm. counter 2] 1500 [Motor speed rpm] A16.5 [Drive out. rat. cur. A] H 75 [Total motor power] h 85 [Total input power] b 70 (1) LL Fr-F nErr MODE [Mot cont. mode sel.] Pt MON Fr-F = forward direction Fr-r = reverse direction d 50 Hz [PID computed ref.] [PID feedback] Hz MODE uE01 [Memory ver.] [Max frequency] uc01 [CPU MMI ver.] dEC [Deceleration time 1] u101 [CPU CTRL ver.] ACC [Acceleration time 1] 0 il Fr [Local mot. direction] iii tYP [Parameter reset] FM [AO scaling] H 75 [Output power KW] FMSL [AO funct. selection] h 80 [Input power KW] FMOd [Frequency mode sel] L 70 CMOd [Command mode sel] c 90 AU4 [Auto set function] q 60 AU1 [Auto ramp] P100 AUH Submenu [5 LAST PARAM CHANGE] Y100 MODE o60.0 [Relay map] [LOGIC INPUT MAP] Hz % % % % % % C 80 [Motor frequency] [Drive load %] [Torque current] [Motor torque %] [Motor voltage] [Line voltage] [Motor current] Refer to the programming manual for comprehensive menu description F60.0 www.schneider-electric.com 4/4 Hz [Speed reference] S1A53825 - 10/2010
© Copyright 2025 Paperzz