Model: PFFY-P18NEMU-E

Model:
PFFY-P18NEMU-E
Job Name:
Schedule Referenece:
Date:
SPECIFICATIONS
Capacity*
Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18,000 Btu/h
Heating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20,000 Btu/h
Power
Power Source . . . . . . . . . . . . . . 208 / 230V, 1 phase, 60Hz
Power Consumption
Cooling (208/230V) . . . . . . . . . . . . . . . . . . . 0.078 / 0.093 kW
Heating (208/230V) . . . . . . . . . . . . . . . . . . . 0.078 / 0.093 kW
Current
Cooling (208/230V) . . . .. . . . .. . . ..... . . . . . . . . 0.38 / 0.42 A
Heating (208/230V) . . . . . . . . . . . . . . ....... . . . . 0.38 / 0.42 A
Minimum Circuit Ampacity (MCA) (208/230V) . . . .0.4 8 / 0.53 A
Maximum Overcurrent Protection (MOCP) . . . . . . . . . . . .15 A
External Finish . . . . . . . . . . . . . . . . . . .Acrylic paint (5Y 8/1)
GENERAL FEATURES
Dual set point functionality (*1)
Compact
Two-speed settings
Controls can be wall-mounted or unit-mounted
in a hidden case
IT Terminal Plug
OPTIONS
External Heater Adapter.…………………...… PAC-YU25HT
Dimensions
Inches . . . . . . . . . . . . .24-13/16 h x 55-17/32 w x 8-11/16 d
mm . . . . . . . . . . . . . . . . . . . . . . . . . .630 h x 1410 w x 220 d
Net Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . .67 lb / 30 kg
Fan
Type x Quantity . . . . . . . . . . . . . . . . . . . . . . .Sirocco fan x 2
Airflow Rate (Low - High) . . . . . . . . . . . . . . 353 – 459 CFM
Motor Type. . . . . . . . . . . . . . . . Single phase induction motor
External Static Pressure...................................... 0" WG
Air Filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Standard
Refrigerant Pipe Dimensions
Liquid . . . . . . . . . . . . . . . . . . . . . . . . . . .1/4" / 6.35 mm flare
Gas . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1/2" / 12.7 mm flare
Drainpipe Dimension . . . . . . . . . . . . .O.D. 1-3/32" / 27 mm
Sound Level (Low - High) . . . . . . . . . . . . . . . . . .38 - 43 dB (A)
* Cooling / Heating capacity indicated at the maximum value at operation under the
following conditions:
Cooling | Indoor: 80° F (27° C) DB / 67° F (19° C) WB, Outdoor 95° F (35° C) DB
Heating | Indoor: 70° F (21° C) DB, Outdoor 47° F (8° C) DB / 43° F (6° C) WB
Note:
Ventilation air to be introduced independent of indoor units.
Please refer to local codes for the required ventilation rates specific to the application.
*1 – All components of the system must be compatible. For more details on system compatibility, please refer to Technical Bulletin 100-151 available on our website.
Notes:
Specifications are subject to change without notice.
© 2014 Mitsubishi Electric Sales Canada Inc.
Page 1 of 2
Form # SB_PFFY-P18NEMU-E_201411
(1-31/32)
50
630(24-13/16)
100(3-15/16)
Model
PFFY-P06NEMU-E
PFFY-P08NEMU-E
PFFY-P12NEMU-E
PFFY-P15NEMU-E
PFFY-P18NEMU-E
PFFY-P24NEMU-E
A
1050(41-11/32)
1050(41-11/32)
1170(46-1/16)
1170(46-1/16)
1410(55-17/32)
1410(55-17/32)
220(8-11/16)
B
640(25-7/32)
640(25-7/32)
760(29-15/16)
760(29-15/16)
1000(39-3/8)
1000(39-3/8)
90(3-9/16)
6(1/4)
35(1-13/32)
35(1-7/16)
( )
(2-3/8)
60
(4-3/4)
120
Strainer
Drain pan
D
610(24-1/16)
610(24-1/16)
730(28-3/4)
730(28-3/4)
970(38-1/4)
970(38-1/4)
25(1)
10(7/16)
Drain hose(accessory)
O.D.27(1-3/32)
top end O.D.20(13/16)
C
600(23-5/8)
600(23-5/8)
720(28-3/8)
720(28-3/8)
960(37-13/16)
960(37-13/16)
Note.On Model :18, you would use flare nut
when connecting the Outdoor
Unit for R22.
Level adjusting screw
4 pcs.(attached)
430 (16-15/16)
20(13/16)
500(19-11/16)
75(3)
Piping
space
170(6-3/4)
220(8-11/16)
(3-1/8)
78
Air filter
(D)
B
A
Air inlet
Air outlet
mm(in.)
B(Floor mounting hole pitch)
45(1-25/32)
15(5/8)
80(3-5/32)
C
15(5/8)
Air supply grille
220(8-11/16)
170(6-3/4)
108(4-5/16)
2X2-12X16(1/2X11/16)
Wall mounting hole
Remote controller
can be built-in.
(Program timer can not be
built-in together.)
2-12X16(1/2X11/16)
Floor mounting hole
10(7/16)
310(12-1/4)
106(4-3/16)
(1-5/8)
40
21(7/8)
)
Floor mounting hole pitch
Page 2 of 2
183.5(7-1/4)
(6-5/16)
160
(
(11-13/16)
300
Form # SB_PFFY-P18NEMU-E_201411
Specifications are subject to change without notice.
www.MitsubishiElectric.ca
© 2014 Mitsubishi Electric Sales Canada Inc.
(6-23/32)
170
Model:
PFFY-P18NEMU-E – DIMENSIONS
Unit : mm(in)