TECHNICAL MANU TECHNICAL MANUAL - Goodman

TECHNICAL MANU
AL
MANUAL
ARPT**14**, ARUF**14**,
ASPT**14**, ASUF**14**
Air Handlers
• Refer to Service Manual RS6200006 for installation, operation & troubleshooting information.
• All safety information must be followed as provided in the Service Manual.
• Refer to the appropriate Parts Catalog for part number information.
• Models listed on page 3.
This manual is to be used by qualified, professionally trained HVAC technicians only. Goodman
does not assume any responsibility for property damage or personal injury due to improper
service procedures or services performed by an unqualified person.
Copyright В© 2012-2014 Goodman Company, L.P.
RT6121003r7
January 2014
PRODUCT IDENTIFICATION
The model number is used for positive identification of component parts used in manufacturing. Please use this number
when requesting service or parts information.
A
R
U
F
18
EXPANSION
DEVICE:
F: Flowrater
T: TXV
(Expansion
Device)
PRODUCT
TYPE:
A: Air Handler
CABINET
FINISH:
P: Painted
U: Unpainted
B
1
4
A
A
MINOR
REVISION*
CABINET
WIDTH
B: 17.5"
C: 21"
D: 24.5"
MAJOR
REVISION*
REFRIGERANT
CHARGE:
4: R-410A only
ELECTRICAL:
1: 208-230V/1ph/60Hz
APPLICATION:
R: Multi-Position PSC Motor
S: Energy Efficient Motor
NOMINAL CAPACITY
RANGE
18: 1-1/2 Tons
24: 2 Tons
30: 2-1/2 Tons
36: 3 Tons
42: 3-1/2 Tons
48: 4 Tons
49: 4 Tons
59: 5 Tons
60: 5 Tons
All Airhandlers use DIRECT DRIVE MOTORS. Power supply is AC 208-230v, 60 hz, 1 phase.
WARNING
HIGH VOLTAGE!
Disconnect ALL power before servicing or installing this unit. Multiple power
sources may be present. Failure to do so may cause property damage, personal
injury or death.
Goodman will not be responsible
for any injury or property damage
arising from improper service or service procedures. If
you install or perform service on this unit, you assume
responsibility for any personal injury or property damage
which may result. Many jurisdictions require a license to
install or service heating and air conditioning equipment.
WARNING
2
Installation and repair of this unit
should be performed ONLY by individuals meeting the requirements of an "entry level technician", at a minimum, as
specified by the Air-Conditioning, Heating, and Refrigeration Institute (AHRI). Attempting to install or repair this
unit without such background may result in product
damage, personal injury or death.
WARNING
PRODUCT IDENTIFICATION
The model number is used for positive identification of component parts used in manufacturing. Please use this number
when requesting service or parts information.
ARPT18B14**
ARPT24B14**
ARPT30B14**
ARPT36C14**
ARPT36D14**
ARPT42D14**
ARPT48D14**
ARPT60D14**
WARNING
ASUF29B14**
ASUF39C14**
ASUF49C14**
ASUF59D14**
ASPT42D14**
ASPT48D14**
ASPT60D14**
ARUF18B14**
ARUF24B14**
ARUF30B14**
ARUF30C14**
ARUF36C14**
ARUF42C14**
ARUF48D14**
ARUF60D14**
ASPT24B14**
ASPT30C14**
ASPT36C14**
ASPT42C14**
ASPT48C14**
The United States Environmental Protection Agency (“EPA”) has issued various regulations regarding the introduction and disposal of refrigerants introduced into this unit. Failure to follow
these regulations may harm the environment and can lead to the imposition of substantial fines.
These regulations may vary by jurisdiction. Should questions arise, contact your local EPA office.
Do not connect or use any device
that is not design certified by
Goodman for use with this unit.
Serious property damage, personal injury, reduced unit
performance and/or hazardous conditions may result
from the use of such non-approved devices.
To prevent the risk of property
damage, personal injury, or death,
do not store combustible materials or use gasoline or
other flammable liquids or vapors in the vicinity of this
appliance.
When installing or servicing this
equipment, safety clothing, including hand and eye protection, is strongly advised. If installing this equipment in an area that has special safety requirements (hard hats etc.), observe these requirements.
To protect the unit when brazing close to the
painted surfaces, the use of a quenching cloth is
strongly advised to prevent scorching or marring of
the equipment finish.
The unit MUST have an uninterrupted, unbroken electrical
ground to minimize the possibility of personal injury if an electrical fault should occur. The electrical ground circuit may consist of an appropriately
sized electrical wire connecting the ground lug in
the unit control box to the building electrical service panel. Other methods of grounding are permitted if performed in accordance with the “National
Electric Code” (NEC)/“American National Standards
Institute” (ANSI)/“National Fire Protection Association” (NFPA) 70 and local/state codes. In Canada,
electrical grounding is to be in accordance with the
Canadian Electric Code CSA C22.1. Failure to observe this warning can result in electrical shock that
can cause personal injury or death.
WARNING
WARNING
WARNING
WARNING
3
PRODUCT DESIGN
If this appliance is installed in
an enclosed area such as a
garage or utility room with any
carbon monoxide (CO) producing appliance (i.e.
automobile, furnace, water-heaters, etc.), ensure
the area is properly ventilated.
WARNING
WARNING
HIGH VOLTAGE
Disconnect ALL power
before servicing or installing this unit. Multiple power sources may be present. Failure
to do so may cause property damage, personal injury or death.
Heating and cooling equipment located in garages, which
may generate a glow, spark or flame capable of igniting flammable vapors, must be installed with the ignition source at
least 18"[46cm] above the floor level.
When more than one appliance is installed in a building it
shall be permanently identified as to the area or space serviced by the equipment.
When this product is installed in the downflow installation in
an unconditioned space, remove the horizontal drain pan and
install the following insulation kit.
MODEL LIST FOR DOWNFLOW KITS
DFK-B
Downflow Kit
DFK-C
Downflow Kit
DFK-D
Downflow Kit
AIR HANDLERS
ARUF18B14**
ARUF30C14**
ARUF48D14**
See Air Handler Specification Sheet for Proper Combinations.
ARUF24B14**
ARUF36C14**
ARUF60D14**
ARUF30B14**
ARUF42C14**
ARPT36D14**
ARPT18B14**
ARPT36C14**
ARPT42D14**
ARPT24B14**
ASUF39C14**
ARPT48D14**
ARPT30B14**
ASUF49C14**
ARPT60D14**
ASUF29B14**
ASPT30C14**
ASUF59D14**
ASPT24B14**
ASPT36C14**
ASPT42D14**
ASPT42C14**
ASPT48D14**
ASPT48C14**
ASPT60D14**
ALL AIR HANDLERS USE DIRECT DRIVE MOTORS. POWER SUPPLY IS 208-230 V, 60 HZ, 1
PHASE.
Installation
Before installing this appliance insure that it is properly sized
and adequate power is available.
This appliance can be installed in the vertical or right horizontal position without modification. The horizontal left and
downflow positions require product modification.
This product is designed for zero inches (0 inches) clearance; however, adequate access for service or replacement
must be considered without removing permanent structure.
This unit can be installed on a platform when deemed necessary.
In an attic installation a secondary drain pan must be provided by the installer and placed under the entire unit with a
separate drain line properly sloped and terminated in an area
visible to the owner. This secondary drain pan is required in
the event that there is a leak or main drain blockage. Closed
cell insulation should be applied to the drain lines in unconditioned spaces where sweating may occur.
Appliances installed in garages, warehouses or other areas
where they may be subjected to mechanical damage must
be suitably guarded against such damage by installing behind protective barriers, being elevated or located out of the
normal path of vehicles. When installed on a base, the base
must also be protected by similar means.
4
This kit is used to prevent sweating on the vertical drain pan.
ARPT, ARUF, ASPT and ASUF air handlers are multi-position, multi-speed with direct drive motors. ARPT and ARUF
are available in 1 1/2 to 5 ton sizes with optional 3 kW to
25kW electric heat kits available for field installation. (See
note below.)
ASPT air handlers are available in 2, 3, 4 and 5 ton sizes
with optional 3 kW to 25kW electric heat kits available for
field installation. (See following note.)
NOTE: Factory-sealed to achieve a 2% or less leakage rate
at 1.0" water gauge external duct static pressure.
Complies with the Factory-sealed Air Handling Credit as
listed in the 2001 Florida Building Code, Chapter 13, Section
610.2.A.2.1.
HKS HEAT KITS
ARPT**14**
ARPT
Heat Kit Applications
Type / model
18B14-A*
24B14-A*
30B14-A*
36C14-A*
36D14-A*
42D14-A*
48D14-A*
60D14-A*
HKSX03XC*
X
X
X
X
X
X
X
X
HKSX05XC*
X
X
X
X
X
X
X
X
HKSX06XC*
X
X
X
X
X
X
X
X
HKSX08XC*
X
X
X
X
X
X
X
X
HKSX10XC*
X
X
X
X
X
X
X
X
HKSC05XC*
X
X
X
X
X
X
X
X
HKSC08XC*
X
X
X
X
X
X
X
X
HKSC10XC*
X
X
X
X
X
X
X
X
HKSC15XA*
X
X
X
X
X
X
HKSC15XB*
X
X
X
X
X
X
HKSC15XF*
X
X
X
X
X
HKSC19CA*
X
HKSC19CB*
X
HKSC20DA*
X
X
X
X
HKSC20DB*
X
X
X
X
X
X
HKSC20XF*
HKSC25DC*
* Revi sion l evel that may or may not be desi gnated
X
X
X
X
X
Re fer to the minimum air flow requirements for each of the heat k it s.
5
HKS HEAT KITS
ARUF**14**
ARUF
Heat Kit Applications
Type / model
18B14-A*
24B14-B*
30B14-A*
3 0C14-B*
36C14-B*
42C14-A*
48 D14-A*
60D14-A*
HKSX03XC*
X
X
X
X
X
X
X
X
HKSX05XC*
X
X
X
X
X
X
X
X
HKSX06XC*
X
X
X
X
X
X
X
X
HKSX08XC*
X
X
X
X
X
X
X
X
HKSX10XC*
X
X
X
X
X
X
X
X
HKSC05XC*
X
X
X
X
X
X
X
X
HKSC08XC*
X
X
X
X
X
X
X
X
HKSC10XC*
X
X
X
X
X
X
X
X
HKSC15XA*
X
X
X
X
X
X
HKSC15XB*
X
X
X
X
X
X
HKSC15XF*
X
X
X
X
X
HKSC19CA*
X
X
X
HKSC19CB*
X
X
X
X
X
HKSC20DA*
HKSC20DB*
HKSC20XF*
X
X
HKSC25DC*
* Revision level that may or may not be designated
X
X
X
X
X
X
Refer to the minimum airflow requirements for each of the heat kits.
HEATER (kW)
*ARUF
ARPT
3
5
6
8
10
18
715
715
715
715
950
24
715
715
715
715
950
30B
715
15
19
20
25
715
715
715
875
875
30C
1170
1170
1170
1170
1345
1345
36
1170
1170
1170
1170
1345
1345
42
1170
1170
1170
1170
1345
1345
48
1590
1590
1590
1590
1715
1715
1715
60
1590
1590
1590
1590
1715
1715
1715
Minimum CFM required for Heater Kits
6
X
X
ASPT**14**
HKS HEAT KITS
AS PT
H e at K it A p p li cat io n s
Ty pe / m o del
2 4 B 1 4 -A *
3 6 C 1 4 -A *
4 2 C 1 4 -A *
4 8 C 1 4 -A *
4 8 D 1 4 -A *
6 0 D 1 4 -A *
H KS X0 3 XC *
X
X
X
X
X
X
H KS X0 5 XC *
X
X
X
X
X
X
H KS X0 6 XC *
X
X
X
X
X
X
H KS X0 8 XC *
X
X
X
X
X
X
H KS X1 0 XC *
X
X
X
X
X
X
H KS C 0 5 XC *
X
X
X
X
X
X
H KS C 0 8 XC *
X
X
X
X
X
X
H KS C 1 0 XC *
X
H KS C 1 5 XA *
X
X
X
X
X
X
X
X
X
X
H KS C 1 5 XB*
X
X
X
X
X
H KS C 1 5 XF *
X
X
X
X
X
H KS C 2 0 D A *
X
X
H KS C 2 0 D B*
X
X
X
X
X
X
H KS C 1 9 C A *
X
X
X
H KS C 1 9 C B*
X
X
X
H KS C 2 0 XF *
X
X
X
H KS C 2 5 D C *
* R e v is i o n l e v e l t h a t m a y o r m a y n o t b e d e s ig n a t e d .
R e f e r t o t h e m in im u m a ir f lo w r e q u ir e m e n t s f o r e a c h o f t h e h e a t k i t s .
Heater (KW)
3
5
6
ASPT24B14*
715
715
715
ASPT30C14*
730
715
715
ASPT36C14*
NR
1170
1170
ASPT42C14*
NR
1170
1170
ASPT48C14*
NR
1170
1170
ASPT42D14*
NR
1590
1590
ASPT48D14*
NR
1590
1590
ASPT60D14*
NR
1590
1590
MINIMUM CFM REQUIRED FOR HEATER KITS
8
715
715
1170
1170
1170
1590
1590
1590
10
875
950
1170
1170
1170
1590
1590
1590
15
NR
NR
1345
1345
1345
1715
1715
1715
19
NR
NR
1345
1345
1345
NR
NR
NR
20
NR
NR
1345
1345
1345
1715
1715
1715
25
NR
NR
NR
NR
NR
NR
1715
1715
7
HKS HEAT KITS
ASUF**14**
ASUF
Heat Kit Applications
Type / model
29B14-A*
39C14-A*
49C14-A*
59D14-A*
HKSX03XC*
X
X
X
X
HKSX05XC*
X
X
X
X
HKSX06XC*
X
X
X
X
HKSX08XC*
X
X
X
X
HKSX10XC*
X
X
X
X
HKSC05XC*
X
X
X
X
HKSC08XC*
X
X
X
X
HKSC10XC*
X
X
X
X
HKSC15XA*
X
X
X
HKSC15XB*
X
X
X
HKSC15XF*
X
X
X
HKSC19CA*
X
X
HKSC19CB*
X
X
HKSC20DA*
X
HKSC20DB*
X
HKSC20XF*
X
X
X
HKSC25DC*
X
* Revision level that may or may not be designated.
Refer to the minimum airflow requirements for each of the heat kits.
HEATER (kW)
ASUF
3
5
6
8
10
715
715
715
715
875
39
1170
1170
1170
49
1170
1170
1170
59
1590
1590
1590
29
Minimum CFM required for Heater Kits
8
15
19
1170
1345
1345
1170
1345
1345
1590
1715
20
25
1715
1715
PRODUCT DIMENSIONS
ARPT**14**/ARUF**14**/ASPT**14**/ASUF**14**
9
PRODUCT DIMENSIONS
ARPT**14**/ARUF**14**
Model
A
B
C
D
E
F
G
H
ARPT18B14*
45
16 3/8
17 1/2
18
15
14 3/16
8 13/16
11 15/16
ARPT24B14*
45
16 3/8
17 1/2
18
15
14 3/16
8 13/16
11 15/16
ARPT30B14*
45
16 1/8
17 1/2
18
15
14 3/16
8 13/16
11 15/16
ARPT36C14*
49
19 15/16
21
20
17
17 11/16
10 1/2
12 3/8
ARPT36D14*
58
23 5/16
24 1/2
28 3/16
25 3/16
21 3/16
12 5/16
12 3/8
ARPT42D14*
58
23 5/16
24 1/2
28 3/16
25 3/16
21 3/16
12 5/16
12 3/8
ARPT48D14*
58
23 5/16
24 1/2
28 3/16
25 3/16
21 3/16
12 5/16
12 3/8
ARPT60D14*
58
23 5/16
24 1/2
28 3/16
25 3/16
21 3/16
12 5/16
12 3/8
Model
A
B
C
D
E
F
G
H
ARUF18B14*
45
16 3 /8
17 1 /2
18
15
14 3/16
8 13/16
11 15 /16
ARUF24B14*
45
16 /8
1
18
15
14 /16
3
8 /16
ARUF30B14*
45
ARUF30C14*
Dimensions are in inches.
3
17 /2
16 /8
3
17 /2
1
18
15
14 /16
3
8 /16
49
19 15 /16
21
20
17
17 11 /16
10 1 /2
ARUF36C14*
49
19
15
/16
21
20
17
17
11
/16
10 /2
12 /8
ARUF42C14*
49
19 15 /16
21
20
17
17 11 /16
10 1 /2
12 3 /8
ARUF48D14*
58
23 5/ 16
24 1 /2
28 3/16
25 3/16
21 3/16
12 5/16
12 3 /8
ARUF60D14*
58
23 5/ 16
24 1 /2
28 3/16
25 3/16
21 3/16
12 5/16
12 3 /8
Dimensions are in inches.
10
13
11
15
/16
13
11
15
/16
1
12 3 /8
3
PRODUCT DIMENSIONS
Model
ASPT24B14*
ASPT30C14*
ASPT36C14*
ASPT42C14*
ASPT48C14*
ASPT42D14*
ASPT48D14*
ASPT60D14*
A
45
49
49
49
49
58
58
58
B
16в…њ
19¹⁵⁄₁₆
19¹⁵⁄₁₆
19¹⁵⁄₁₆
19¹⁵⁄₁₆
23⁵⁄₁₆
23⁵⁄₁₆
23⁵⁄₁₆
ASPT**14**/ASUF**14**
C
17ВЅ
21
21
21
21
24ВЅ
24ВЅ
24ВЅ
D
18
20
20
20
20
28³⁄₁₆
28³⁄₁₆
28³⁄₁₆
E
15
17
17
17
17
25³⁄₁₆
25³⁄₁₆
25³⁄₁₆
F
14³⁄₁₆
17¹¹⁄₁₆
17¹¹⁄₁₆
17¹¹⁄₁₆
17¹¹⁄₁₆
21³⁄₁₆
21³⁄₁₆
21³⁄₁₆
G
8¹³⁄₁₆
10ВЅ
10ВЅ
10ВЅ
10ВЅ
12⁵⁄₁₆
12⁵⁄₁₆
12⁵⁄₁₆
H
11¹⁵⁄₁₆
12в…њ
12в…њ
12в…њ
12в…њ
12в…њ
12в…њ
12в…њ
Dimensions are in inches.
Model
A
B
C
D
E
F
G
H
ASUF29B14*
45
16 3/8
17 1/2
18
15
14 3/16
8 13/16
11 15/16
ASUF39C14*
49
19 15/16
21
20
17
17 11/16
10 1/2
12 3/8
ASUF49C14*
49
19 15/16
21
20
17
17 11/16
10 1/2
12 3/8
ASUF59D14*
58
23 5/16
24 1/2
28 3/16
25 3/16
21 3/6
12 5/16
12 3/8
Dimensions are in inches.
11
PRODUCT SPECIFICATIONS
ARPT**14**
ARPT
18B14*
ARPT
24B14*
ARPT
30B14*
ARPT
36C14*
ARPT
36D14*
ARPT
42D14*
ARPT
48D14*
ARPT
60D14*
18,000
24,000
30,000
36,000
36,000
42,000
48,000
60,000
1065
825
560
1065
825
560
1020
775
565
1445
1300
1175
1705
1485
1140
1810
1555
1350
1845
1495
1280
2080
1865
1505
9ВЅ"
9ВЅ"
9ВЅ"
10в…ќ"
10в…ќ"
10в…ќ"
11 /16"
15
11 /16"
Width
6"
6"
6"
8"
10в…ќ"
10в…ќ"
10в…ќ"
10в…ќ"
Coil Drain Connect FPT
Вѕ"
Вѕ"
Вѕ"
Вѕ"
Вѕ"
Вѕ"
Вѕ"
Вѕ"
Liquid
в…њ"
в…њ"
в…њ"
в…њ"
в…њ"
в…њ"
в…њ"
в…њ"
Suction
Вѕ"
Вѕ"
Вѕ"
в…ћ"
в…ћ"
в…ћ"
в…ћ"
в…ћ"
Nominal Ratings
Cooling (Btu/h)
Airflow Rate CFM *
High
Med
Low
Blower
Diameter
15
Refrigerant Line
Connection Size
Electrical Data
Voltage
Min Circuit Ampacity
Max. Overcurrent Device (amps)
Min. / Max VAC
Blower Motor FLA/ HP
Ship Weight (lbs)
*Airflow rate @.3 static
12
208 / 230 208 / 230 208 / 230 208 / 230 208 / 230 208 / 230 208 / 230 208 / 230
3/3
3/3
3/3
4/4
4/4
5/5
5/5
6/6
15 / 15
15 / 15
15 / 15
15 / 15
15 / 15
15 / 15
15 / 15
15 / 15
197 / 253 197 / 253 197 / 253 197 / 253 197 / 253 197 / 253 197 / 253 197 / 253
1.9 / в…“
1.9 / в…“
1.9 / в…“
3.1 / в…“
3.0 / ВЅ
3.5 / ВЅ
3.5/ ВЅ
4.6 / Вѕ
100
100
105
118
155
155
167
167
PRODUCT SPECIFICATIONS
ARUF**14**
ARUF
18B14*
ARUF
24B14*
ARUF
30B14*
ARUF
30C14*
ARUF
36C14*
ARUF
42C14*
ARUF
48D14*
ARUF
60D14*
18,000
24,000
30,000
36,000
36,000
42,000
48,000
60,000
1045
835
565
1045
835
565
1020
775
565
1385
1235
980
1385
1235
980
1465
1290
1000
1810
1555
1350
2125
1885
1455
9ВЅ"
9ВЅ"
9ВЅ"
10в…ќ"
10в…ќ"
10в…ќ"
10в…ќ"
1115/16"
Width
6"
6"
6"
8"
8"
8"
10в…ќ"
10в…ќ"
Coil Drain Connect FPT
Вѕ"
Вѕ"
Вѕ"
Вѕ"
Вѕ"
Вѕ"
Вѕ"
Вѕ"
Liquid
в…њ"
в…њ"
в…њ"
в…њ"
в…њ"
в…њ"
в…њ"
в…њ"
Suction
Вѕ"
Вѕ"
Вѕ"
Вѕ"
Вѕ"
в…ћ"
в…ћ"
в…ћ"
208 / 230
208 / 230
208 / 230
208 / 230
208 / 230
208 / 230
208 / 230
208 / 230
3/3
3/3
3/3
4/4
4/4
4/4
5/5
6/6
15 / 15
15 / 15
15 / 15
15 / 15
15 / 15
15 / 15
15 / 15
15 / 15
197 / 253
197 / 253
197 / 253
197 / 253
197 / 253
197 / 253
197 / 253
197 / 253
1.9 / в…“
1.9 / в…“
1.9 / в…“
3.0 / в…“
3.0 / в…“
3.1 / в…“
3.5 / ВЅ
4.6 / Вѕ
98
98
103
115
115
117
154
154
Nominal Ratings
Cooling (Btu/h)
Airflow rate CFM*
High
Med
Low
Blower
Diameter
Refrigerant Line
Connection Size
Electrical Data
Voltage
Min Circuit Ampacity
Max. Overcurrent Device (amps)
Min. / Max VAC
Blower Motor FLA/ HP
Ship Weight (lbs)
*Airflow rate @.3 static
13
ASPT**14**
PRODUCT SPECIFICATIONS
Nominal Ratings
Cooling (Btu/h)
Airflow Rate CFM *
T1
T2
T3
T4
T5
Blower
Diameter
Width
Coil Drain Connect FPT
Refrigerant Line
Connection Size
Liquid
Suction
Electrical Data
Voltage
Min Circuit Ampacity
Max. Overcurrent Device
Min. / Max VAC
Blower Motor FLA/ HP
Ship Weight (lbs)
ASPT
24B14*
ASPT
30C14*
ASPT
36C14*
ASPT
42C14*
ASPT
48C14*
ASPT
42D14*
ASPT
48D14*
ASPT
60D14*
24,000
30,000
36,000
36,000
42,000
42,000
48,000
60,000
520
600
660
775
975
540
625
720
810
1,400
890
995
1090
1205
1425
865
980
1,070
1,190
1,520
1275
1400
1500
1585
1680
1110
1250
1355
1440
1780
1250
1400
1515
1635
1825
1400
1600
1745
1995
2160
9ВЅ"
6"
Вѕ"
10в…ќ"
8"
Вѕ"
10в…ќ"
8"
Вѕ"
10в…ќ"
10в…ќ"
Вѕ"
10в…ќ"
10в…ќ"
Вѕ"
10в…ќ"
10в…ќ"
Вѕ"
10в…ќ"
10в…ќ"
Вѕ"
11¹⁵⁄₁₆"
10в…ќ"
Вѕ"
в…њ"
Вѕ"
в…њ"
в…ћ"
в…њ"
в…ћ"
в…њ"
в…ћ"
в…њ"
в…ћ"
в…њ"
в…ћ"
в…њ"
в…ћ"
в…њ"
в…ћ"
208 / 230
3/3
15 / 15
197 / 253
2.18/ 3/4
208 / 230
4/4
15 / 15
197 / 253
3.15/ 3/4
208 / 230
4/4
15 / 15
197 / 253
3.15/ 3/4
208 / 230
4/4
15 / 15
197 / 253
3.15/ 3/4
208 / 230
7/7
15/15
197/253
5.4/ 3/4
208 / 230
6/6
15 / 15
197 / 253
4.84/ 3/4
208 / 230
8/8
15 / 15
197 / 253
6.65/ 1
208 / 230
8/8
15 / 15
197 / 253
6.65/ 1
100
118
118
125
125
167
167
167
*Airflow rate @.3 static
Note: Assumes dry coil; SCFM correction for wet coil = 4% (208V / 240V)
14
PRODUCT SPECIFICATIONS
ASUF**14**
ASUF
29B14*
ASUF
39C14*
ASUF
49C14*
ASUF
59D14*
24,000
36,000
49,000
60,000
520
600
660
775
975
890
995
1090
1205
1425
1375
1525
1620
1715
1800
1400
1600
1745
1995
2160
9ВЅ"
10в…ќ"
10в…ќ"
11 /16"
Width
6"
8"
10в…ќ"
10в…ќ"
Coil Drain Connect FPT
Вѕ"
Вѕ"
Вѕ"
Вѕ"
Liquid
в…њ"
в…њ"
в…њ"
в…њ"
Suction
Вѕ"
в…ћ"
в…ћ"
в…ћ"
Nominal Ratings
Cooling (Btu/h)
Airflow Rate CFM *
T1
T2
T3
T4
T5
Blower
Diameter
15
Refrigerant Line
Connection Size
Electrical Data
Voltage
Min Circuit Ampacity
Max. Overcurrent Device (amps)
Min. / Max VAC
Blower Motor FLA/ HP
Ship Weight (lbs)
208 / 230 208 / 230 208 / 230 208 / 230
3/3
4/4
4/4
6/6
15 / 15
15 / 15
15 / 15
15 / 15
197 / 253 197 / 253 197 / 253 197 / 253
2.7 / Вѕ
3.2 / Вѕ
5.4 / Вѕ
6.7 / 1
100
118
118
167
*Airflow rate @.3 static
15
BLOWER PERFORMANCE DATA
ARPT**14**
Static Pressure (in w.c)
0.3
0.4
0.5
Model Number
Blower
Speed
0.1
0.2
ARPT18B14
High
Medium
Low
1185
900
630
1125
850
605
1065
825
560
1010
785
525
High
Medium
Low
1185
900
630
1125
850
605
1065
825
560
High
Medium
Low
1145
870
615
1085
820
585
High
Medium
Low
1580
1385
1260
High
Medium
Low
High
Medium
ARPT24B14
ARPT30B14
ARPT36C14
ARPT36D14
ARPT42D14
Low
ARPT48D14
High
Medium
ARPT60D14
Low
High
Medium
Low
0.6
0.7
985
715
495
910
670
445
780
610
355
1010
785
525
985
715
495
910
670
445
780
610
355
1020
775
565
950
745
535
900
705
490
845
655
435
765
580
345
1515
1350
1205
1445
1300
1175
1395
1250
1105
1345
1170
1040
1240
1095
975
1155
1005
865
1815
1580
1220
1770
1525
1180
1705
1485
1140
1640
1420
1085
1555
1350
1030
1450
1275
950
1355
1165
865
1990
1655
1480
1915
1605
1420
1810
1555
1350
1765
1480
1290
1690
1295
1185
1585
1200
1100
1435
1060
1045
1960
1600
1395
1905
1545
1340
1845
1495
1280
1780
1435
1220
1715
1360
1150
1645
1290
1090
1570
1215
1020
2205
1985
1600
2140
1935
1555
2080
1865
1505
2010
1815
1455
1945
1755
1405
1870
1695
1345
1795
1635
1295
AIRFLOW DATA (CFM) ARPT**14**
Notes: • Airflow data indicated is at 230V without air filter in place.
• The chart is for information only. For satisfactory operation, external static pressure must not exceed value shown on rating plate. The
shaded area indicates ranges in excess of maximum design external static pressure.
• Use the CFM adjustment factors of 0.98 for horizontal left and 0.96 for horizontal right & downflow orientations.
16
BLOWER PERFORMANCE DATA
Model Number
ARUF18B14*
ARUF24B14*
ARUF30B14*
ARUF30C14*
ARUF36C14*
ARUF42C14AA
ARUF42C14AB
ARUF48D14*
ARUF60D14*
Blower
Speed
High
Medium
Low
High
Medium
Low
High
Medium
Low
High
Medium
Low
High
Medium
Low
High
Medium
Low
High
Medium
Low
High
Medium
Low
High
Medium
Low
ARUF**14**
0.1
1150
890
640
1150
890
640
0.2
1095
855
605
1095
855
605
Static Pressure (in w.c)
0.3
0.4
0.5
1045
1025
950
835
775
715
565
530
485
1045
1025
950
835
775
715
565
530
485
0.6
865
665
440
865
665
440
0.7
775
605
360
775
605
360
1145
870
615
1485
1300
1040
1085
820
585
1435
1270
1015
1020
775
565
1385
1235
980
950
745
535
1345
1195
930
900
705
490
1275
1130
865
845
655
435
1205
1060
790
765
580
345
1125
955
705
1485
1300
1040
1580
1395
1095
1435
1270
1015
1530
1340
1045
1385
1235
980
1465
1290
1000
1345
1195
930
1400
1235
950
1275
1130
865
1330
1170
895
1205
1060
790
1255
1095
820
1125
955
705
1165
1000
725
1655
1435
1115
1990
1655
1480
1590
1370
1040
1915
1605
1420
1515
1300
995
1810
1555
1350
1430
1220
930
1765
1480
1290
1340
1150
845
1690
1295
1185
1225
1025
770
1585
1200
1100
1080
925
675
1435
1060
1045
2235
2030
1615
2175
1970
1535
2125
1885
1455
2050
1800
1355
1960
1690
1270
1825
1600
1185
1720
1495
1090
AIRFLOW DATA (CFM) ARUF**14**
Notes: • Airflow data indicated is at 230V without air filter in place.
• The chart is for information only. For satisfactory operation, external static pressure must not exceed value shown on rating plate. The
shaded area indicates ranges in excess of maximum design external static pressure.
• Use the CFM adjustment factors of 0.98 for horizontal left and 0.96 for horizontal right & downflow orientations.
17
BLOWER PERFORMANCE DATA
Model Number
ASPT24B14
ASPT30C14
ASPT36C14
ASPT42C14
ASPT48C14
ASPT42D14
ASPT48D14
ASPT60D14
ASPT**14**
Blower
Speed
Tap
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1
1
570
540
520
480
450
415
370
305
270
240
2
650
605
600
570
530
500
460
425
380
330
3
740
690
660
650
615
570
525
480
440
405
4
855
810
775
755
750
720
690
650
620
575
5
1050
1005
975
940
910
900
885
880
845
820
1
610
580
540
445
390
330
285
240
205
160
2
705
670
625
570
545
465
425
385
325
270
3
785
740
720
660
640
580
515
475
440
370
Static Pressure (in w.c)
4
880
845
810
805
740
700
660
595
550
515
5
1440
1440
1400
1380
1350
1330
1295
1275
1245
1205
1
960
905
890
810
760
720
665
620
550
485
2
1060
1010
995
920
875
835
790
745
690
615
3
1150
1100
1090
1025
990
945
905
860
810
750
4
1250
1220
1205
1145
1110
1070
1035
990
940
885
5
1470
1440
1425
1405
1375
1260
1315
1280
1245
1205
1
950
925
865
815
730
675
660
600
545
---
2
1075
1025
980
930
875
785
730
690
650
---
3
1160
1115
1070
1025
975
905
815
770
715
---
4
1275
1235
1190
1145
1100
1040
975
875
835
---
5
1600
1560
1520
1480
1430
1390
1345
1290
1245
---
1
1365
1305
1275
1225
1175
1110
1070
1020
995
---
2
1490
1455
1405
1360
1305
1255
1205
1160
1115
---
3
1580
1540
1500
1455
1400
1350
1300
1260
1210
---
4
1670
1635
1585
1545
1495
1445
1395
1365
1315
---
5
1750
1715
1680
1645
1590
1530
1495
1460
1410
---
1
1230
1180
1110
1060
1000
945
885
810
745
685
2
1365
1310
1250
1190
1140
1090
1030
980
920
855
3
1460
1410
1355
1305
1255
1210
1155
1115
1060
1010
4
1545
1490
1440
1375
1330
1295
1245
1200
1150
1100
5
1865
1825
1780
1745
1695
1645
1610
1570
1520
1475
1
1485
1425
1400
1325
1270
1220
1165
1115
1080
1005
2
1560
1510
1490
1425
1385
1335
1295
1250
1205
1155
3
1675
1625
1600
1530
1485
1435
1390
1345
1295
1245
4
1820
1770
1745
1685
1640
1595
1555
1510
1470
1420
5
2225
2180
2160
2085
2060
2010
1970
1930
1895
1850
1
1485
1425
1400
1325
1270
1220
1165
1115
1080
1005
2
1675
1625
1600
1530
1485
1435
1390
1345
1295
1245
3
1820
1770
1745
1685
1640
1595
1555
1510
1470
1420
4
2060
2010
1995
1925
1880
1845
1800
1760
1720
1680
5
2225
2180
2160
2085
2060
2010
1970
1930
1895
1850
AIRFLOW DATA (CFM) ASPT**14**
Notes: • Airflow data indicated is at 230V without air filter in place.
• The chart is for information only. For satisfactory operation, external static pressure must not exceed value shown on rating plate. The
shaded area indicates ranges in excess of maximum design external static pressure.
• Use the CFM adjustment factors of 0.98 for horizontal left and 0.96 for horizontal right & downflow orientations.
18
ASUF**14**
BLOWER PERFORMANCE DATA
Model Number
ASUF29B14
ASUF39C14
ASUF49C14
ASUF59D14
Blower
Speed
Tap
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1
1
570
540
520
480
450
415
370
305
270
240
2
650
605
600
570
530
500
460
425
380
330
3
740
690
660
650
615
570
525
480
440
405
4
5
1
2
3
4
5
855
1050
810
1005
775
975
755
940
750
910
720
900
690
885
650
880
620
845
575
820
960
1060
1150
1250
1470
905
1010
1100
1220
1440
890
995
1090
1205
1425
810
920
1025
1145
1405
760
875
990
1110
1375
720
835
945
1070
1260
665
790
905
1035
1315
620
745
860
990
1280
550
690
810
940
1245
485
615
750
885
1205
1
1425
1405
1375
1340
1305
1265
1215
1155
1115
1070
2
1560
1545
1525
1490
1455
1410
1380
1325
1275
1225
3
1670
1645
1620
1595
1550
1520
1485
1445
1405
1350
4
5
1760
1845
1745
1820
1715
1800
1685
1775
1655
1740
1625
1705
1585
1675
1550
1640
1515
1605
1470
1575
1
1485
1425
1400
1325
1270
1220
1165
1115
1080
1005
2
1675
1625
1600
1530
1485
1435
1390
1345
1295
1245
3
1820
1770
1745
1685
1640
1595
1555
1510
1470
1420
4
2060
2225
2010
2180
1995
2160
1925
2085
1880
2060
1845
2010
1800
1970
1760
1930
1720
1895
1680
1850
5
Static Pressure (in w.c)
AIRFLOW DATA (CFM) ASUF**14**
Notes: • Airflow data indicated is at 230V without air filter in place.
• The chart is for information only. For satisfactory operation, external static pressure must not exceed value shown on rating plate. The
shaded area indicates ranges in excess of maximum design external static pressure.
• Use the CFM adjustment factors of 0.98 for horizontal left and 0.96 for horizontal right & downflow orientations.
19
WIRING DIAGRAMS
ARPT**14**/ARUF**14**
HIGH VOLTAGE!
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
FL
FL
FL
FL
HTR2 TL
FL
HTR1 TL
HTR1 TL
BK
BK
RD
FL
HTR1 TL
FL
BK
FL
HTR2 TL
FL
RD
BK
BK
2
HTR3 TL
1
BK
BK
HTR2 TL
RD
HTR3 TL
FL
1
HTR1 TL
YL
HTR4 TL
1
BL
BK
RD
PU
BL
BK
R
YL
PU
BK
M1
M1
M3
4
M2
M4
5
R
WH
BK
BK RD
4
M1
YL
M2
R2
RD
RD
5
BR
M2
BL
M3
M4
M5
M7
M6
M8
R1
WH
6
3
RD
BL
R2
BR
4
5
BK
BK
6
RD
RD
WH
6
7
7
BK
8
M4
2
PU
BL
BK
BK
WH
7
RD
M2
3
RD
BL
M1
R1
6
BK
RD
PU
BL
M3
1
2
YL
BK
3
BL
RD
5
M2
RD
RD
4
M1
BK
2
3
7
YL
8
RD
YL
BK
8
9
RD
9
BL
BK
8
RD
9
9
L1
L2
L1
ONE (1) ELEMENT ROWS
L2
L1
TWO (2) ELEMENT ROWS
L2
L1
L2
THREE (3) ELEMENT ROWS
L1
L2
L1
L2
FOUR (4) ELEMENT ROWS
NOTE: WHEN INSTALLING HEATER KIT, ENSURE SPEED TAP IS NOT BELOW MINIMUM BLOWER SPEED (MBS) SPECIFIED FOR THE AIR HANDLER/HEATER KIT
COMBINATION ON THIS UNITS SERIAL PLATE. AFTER INST ALLING OPTIONAL HEAT KIT, MARK A "X" IN THE
PROVIDED ABOVE. MARK ACCORDING TO THE
NUMBER OF HEATER ELEMENT ROW S INSTALLED. NO MARK INDICATES NO HEAT KIT INSTALLED. 5 ELEMENT ROWS DATA SUPPLIED WITH HEATER KIT.
SEE NOTE 2
L1
L2
BK
RD
PLF
1
2
3
4
5
6
7
8
9
PLM
1
2
3
4
5
6
7
8
9
BK
RD
PU
BL
BR
WH
TERMINAL BLOCK SHOWN
FOR 50HZ MODELS ONLY
BL RD GR WH
BR
SR
EQUIPMENT GROUND
USE COPPER WIRE
208/240 VOLTS
GRD
L1
L2
1 PLF
PLF 2
1 PLM
3
2
EM
RC
SEE
NOTE 4
HI
BR
LO
WH
PLM
1
2
3
4
24V
5
M1
NO
NC
EBTDR
M2
COM
SEE NOTE 1
TR
C
EBTDR R
GR
SEE NOTE 5
RD
G
BL
COM
K1
SPEEDUP
6
C
1
2
3
5
24V
4
RD
240
BK
RD
YL
BL
NC
M1
BL
BL
M2
BK
RD
SEE
NOTE 3
THREE SPEED MOTOR WIRING
(SELECT MODELS ONLY)
SEE NOTE 3
PU
(M2) BL
(TR 1)
BK
LOW
MEDIUM
(M1) BK
IF REPLACEMENT OF THE ORIGINAL WIRES
SUPPLIED WITH THIS ASSEMBLY IS NECESSARY
USE WI RE THAT CONFORMS TO THE
NATIONAL ELECTRIC CODE.
EM
RC
SR
R
EBTDR
NOTES:
(COM) RD
HIGH
PU
BR
PU
RC
RC
BR
EM
3 SPEED
BLACK
GR
PU
RED
YELLOW BR
WH
BLUE
EM
BR
GR
BL
WH BR
COMPONENT CODE
RD
COPPER POWER SUPPLY
(SEE RATING PLATE)
USE MIN. 75В°C FIELD WIRE
WIRING CODE
GREEN
PURPLE
BROWN
WHITE
FACTORY WIRING
HIGH VOLTAGE
LOW VOLTAGE
FIELD WIRING
HIGH VOLTAGE
LOW VOLTAGE
TR
EVAPORATOR MOTOR
RUN CAPACITOR
PLF
STRAIN RELIEF
PLM
FL
RELAY
TL
ELECTRONIC BLOWER TIME
DELAY RELAY
HTR
TRANSFORMER
FEMALE PLUG CONNECTOR
MALE PLUG CONNECTOR
FUSE LINK
THERMAL LIMIT
HEAT ELEMENTS
1) RED WIRES TO BE ON TRANSFORMER TERMINAL "3" FOR 240 VOLTS
AND ON TERMINAL "2" FOR 208 VOLTS.
2) SEE COMPOSITE WIRING DIAGRAMS IN INSTALLATION INSTRUCTIONS
FOR PROPER LOW VOLTAGE WIRING CONNECTIONS.
3) CONFIRM SPEED TAP SELECTED IS APPROPRIATE FOR APPLICATION.
IF SPEED TAP NEEDS TO BE CHANGED, CONNECT APPROPRIATE
MOTOR WIRE (RED FOR LOW, BLUE FOR MEDIUM,AND BLACK FOR
HIGH SPEED) ON "COM" CONNECTION OF THE EBTDR.
INACTIVE MOTOR WIRES SHOULD BE CONNECTED TO "M1 OR M2"
ON EBTDR.
4) BROWN AND WHITE WIRES ARE USED WITH HEAT KITS ONLY.
5) EBTDR HAS A 7 SECOND ON DELAY WHEN "G" IS ENERGIZED
AND A 65 SECOND OFF DELAY WHEN "G" IS DE-ENERGIZED.
0140A00058-B
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
20
G
4 PLF
COLOR CODE
TR
PU
5
EBTDR
SEE NOTE 1
RD
RD
NO
K1
C
BL
RD
PU
EBTDR
R
XFMR-R
XFMR-C
RD
BK
WIRING DIAGRAMS
ASPT**14**/ASUF**14**
HIGH VOLTAGE!
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
FL
FL
FL
TL
HTR 1
FL
BK
BK
HTR1
FL
BK
FL
BK
1
HTR2
RD
FL
BK
1
RD
PU
4
M1
R
RD
6
M3
4
M2
M4
5
7
BK
RD
RD
BL
M3
M4
M2
3
RD
BL
M1
R2
BR
BK
RD
WH
M1
YL
RD
M3
M2
M4
R1
6
M5
M7
M6
M8
3
RD
BL
R2
BR
BK
BK
RD
WH
4
5
6
7
8
YL
BK
8
1
2
YL
7
RD
RD
9
BL
BK
RD
9
9
L1
BK
BL
4
5
7
BK
BK RD
6
BK
8
BL
PU
M2
R1
WH
BK
RD
BK
BL
PU
BK
M1
M1
R
WH
YL
3
BL
BK
5
M2
YL
TL
2
YL
RD
2
3
BL
RD
TL
HTR3
FL
1
HTR4
RD
PU
BK
BK
TL
HTR2
TL
HTR3
BK
RD
2
TL
HTR1
FL
TL
TL
HTR2
FL
TL
TL
HTR1
8
9
L2
L1
L2
L1
L2
L1
L2
L1
ONE (1) ELEMENT ROWS
TWO (2) ELEMENT ROWS
L2
L1 L2
FOUR (4) ELEMENT ROWS
TH REE (3) ELEMENT ROWS
NOTE: W HEN INSTALLING HEATER KIT, ENSURE SPEED TAP DOES NOT EXCEED MINIMUM BLOW ER SPEED (MBS) SPECIFIED FOR THE AIRHANDLER/HEATER KIT COMBINATION ON THIS
UNIT'S S&R PLATE. AFTER INSTALLING OPTIONAL HEAT KIT, MARK A "X" IN THE BOX PROVIDED ABOVE. MARK ACCORDING TO NUMBER OF HEATER ELEMENT ROWS INSTALLED. NO MARK
INDICATES NO HEAT KIT INSTALLED.
208/240 VOLTS
EQUIP MENT GROUND
USE COPPER WIRE
GRD
SEE NOT E 2
R C G W 1 W 2 Y1 Y2 O DH 1 2 3 4 5
L1
L1
L2
PLF
1
2
3
4
5
6
7
8
9
PLM
1
2
3
4
5
6
7
8
9
BK
RD
BL
BR
WH
1
1
RD
GR
L2
PLF
WIRING CODE
5
FACTORY W IRING
HIGH VOLTAGE
LOW VOLTAGE
FIELD W IRING
HIGH VOLTAGE
LOW VOLTAGE
PLF 2
EM
PLM
LGN
PLM
SEE
NOTE 4
2
2
1
3
SEE NOTE 1
BR
WH
1
2
3
4
24V
5
4
CR
TR
PLF
PLM
FL
TL
HTR
ALTERNATE HEAT RELAY
1
BL
TR
RD
WH
CR
BK
7
RD
GR
4
1
A
B
RD
SEE
NOTE 1
BK
WH
C
RD
1
2
3
5
24V
4
FUSE
HOLDER
PU
6
5
B
A
4
7
240
TR
R C G W1 W2 Y1 Y2 O DH 1 2 3 4 5
BL
BL
BL
BL
BL
RD
RD
COPPER POWER SUPPLY
(USE RATING PLATE)
USE MIN. 75В° C FIELD WIRE
WH PU
FUSE
HOLDER
OR BR YL
1 2 34 5
EM
PU
4
IF REPLACEMENT OF THE ORIGINAL WIRES
SUPPLIED WITH THIS ASSEMBLY IS NECESSARY,
USE WIRE THAT CONFORMS TO THE NATIONAL
ELECTRIC CODE.
RD
2
5
GR
1
3
C LGN
WH
BL
ALTERNATE HEAT RELAY
RD BK
BL
NOTES:
1) RED WIRES TO BE ON TRANSFORMER TERMINAL "3" FOR 240 VOLTS AND ON
TERMINAL "2" FOR 280 VOLTS.
1
2
3
4
5
EM
BK
RD
YL
BL
BLACK
GR GREEN
RED
PU PURPLE
YELLOW BR BROWN
BLUE
WH WHITE
C
C OMPONENT CODE
EM
TB
R
CR
EBTDR
EVAPORATOR MOTOR
TERM INAL BOARD
RELAY
CONTROL RELAY
ELECTR ONIC BLOWER TIME
DELAY RELAY
2) SEE COMPLETE WIRING DIAGRAMS IN INSTALLATIO N INSTRUCTIONS FOR
PROPER LOW VOLTAGE WIRIN G CONNECTIONS.
3) CONFIRM SPEED TAP SELECTIO N IS APPROPRIATE FOR APPLICATION. IF
SPEED TAP NEEDS TO BE CHANGED, CONNECT PURPLE WIRE FROM TERMINAL 4 OF CR
RELAY TO APPROPRIATE TAP AT TB.
4) BROWN AND WHITE WIRES ARE USED FOR HEAT KITS ONLY.
BL
COLOR CODE
CR
4 P LM
TRANSFORMER
FEMALE PLUG CONNECTOR
MALE PLUG CON NECTOR
FUSE LINK
THERMAL LIMIT
HEAT ELEMENTS
0140A00063-A
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
21
WIRING DIAGRAMS
HIGH VOLTAGE!
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
3-Phase Heat Kit
25kW Heat Kit
TL
HTR1
TL
HTR2
TL
BK
FL
COMPONENT CODE
RD
FL
M10
R3
M9
HTR3
TL
YL
FL
HTR4
BK
FL
TL
PU
PC
HTR5
RD
BL
BL
FL
BK
1
BL
2
PU
BK RD
M2
YL
PU
M4
M1
WH
BL
M3
R1
M6
M5
4
M8
R2
BR
5
BK
RD
WH
6
7
YL
BL
BK
RD
CB3
L1
CB1
L2
L1
L1
9
BK = BLACK
BL = BLUE
BR = BROWN
GR = GREEN
OR = ORANGE
PK = PINK
PU = PURPLE
RD = RED
WH = WHITE
YL = YELLOW
PU
NOTE: WHEN INSTALLING HEATER KIT, ENSURE SPEED TAP MUST EXCEED OR
EQUAL THE MINIMUM BLOWER SPEED (MBS) SPECIFIED FOR THE AIRHANDLER /
HEATER KIT COMBINATION ON THIS UNIT'S SERIAL PLATE. AFTER INSTALLING
OPTIONAL HEAT KIT, MARK AN "X" IN THE
PROVIDED BELOW.
NO MARK INDICATES NO HEAT KIT INSTALLED.
FIVE (5) ELEMENT ROWS
NOTE:THIS LABEL MUST BE ATTACHED ON THE
AIRHANDLER IN A PROMINENT LOCATION
CB2
L2
8
COLOR CODE
HIGH VOLTAGE
LOW
VOLTAGE
3
RD
BL
M7
PC = 9 PIN CONNECTOR
HTR = HEATER ELEMENT
TL = THERMAL LMT
RS = RELAY/SEQUENCER
TB = TERMINAL BLOCK
CB = CIRCUIT BREAKER
CC = CONTACTOR
FL = FUSE LINK
EM = EVAPORATOR MOTOR
EBTDR = ELEC. BLOWER TIME DELAY
RC = RUN CAPACITOR
TR = TRANSFORMER
SR = STRAIN RELIEF
WIRING CODE:
L2
BK
BK RD
RD
CB4
L1
L2
0140M00274-A
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
22