20.3/35 kV YXC8VZ3V(TSE) N2XSEYFGbY(VDE) 2XSEYFGbY(IEC)

20.3/35 kV
XLPE INSULATED GANAVIZED FLAT STEEL WİRE ARMOURED MEDIUM VOLTAGE POWER CABLES
YXC8VZ3V(TSE)
N2XSEYFGbY(VDE)
2XSEYFGbY(IEC)
Cu/XLPE/CTS/PVC/SWA/PVC(BS)
YXC8VZ3V(TSE), N2XSEYFGbY(VDE), 2XSEYFGbY(IEC), Cu/XLPE/CTS/PVC/SWA/PVC(BS)
TSEK, Teknik Şartname, VDE 0273, IEC 502
Copper conductor,inner semiconductive layer,XLPE insulation,Outer semiconductive layer,semiconductive
tape,copper tape screen,PVC inner sheath,PVC seperation sheath,galvanized steel wires and tape,PVC outer
sheath
Where there is mechanical heavy duties,underground,cable ducts, power distribution cabinets,city
network,industrial builts
Max. operating temperature 90 ° C
Max. permissible short circuit temperature 250 °C, max. for 5 sec.
Min. Bending radius 15*D D: overall diameter
Code
Standarts
Construction
Application
Technical Datas
Dimensions and Weights
Nominal
cross-section
Overall
Diameter
(mm 2)
(mm)
3x35/16 rm
3x50/16 rm
3x70/16 rm
3x95/16 rm
3x120/16 rm
3x150/25 rm
3x185/25 rm
3x240/25 rm
3x300/25 rm
3x400/35 rm
78,0
81,0
85,0
90,0
94,0
97,0
100,0
106,0
113,0
120,0
Net
weight
(kg/
km)
8330
9060
10410
12420
13840
15150
16670
19350
22250
23250
Electrical Information
Standart
delivery
lenght
Standart
delivery
reel size
(m)
(cm)
500
500
500
350
350
350
300
250
250
250
260
260
280
280
280
300
300
300
300
300
Conductor
DC
resistance
at 20 ° C
(ohm/
km)
0,524
0,387
0,268
0,193
0,153
0,124
0,0991
0,0754
0,0601
0,0470
rm:Stranded conductor
107
Per conductor
inductance
(approx.)
(mH/km)
0,47
0,45
0,42
0,40
0,39
0,37
0,36
0,35
0,29
0,28
Operating
apacitance
(approx.)
at 20 °C
(mikrofarad/
km)
0,11
0,12
0,13
0,15
0,16
0,17
0,18
0,20
0,22
0,24
Current carrying capacity
(approx.)
Ground (A)
at 20 0C
181
214
261
313
356
400
441
510
576
650
Air (A)
at 30 0C
176
210
262
319
364
418
478
562
635
731