english - AEZ Italy

AMICO
Electronic unit for the automatic management of a generator set in emergency to the main -
ELECTRONIC UNIT WITH CONTROL LOGIC -
PROGRAMMING SWITCH TO ASSURE NORMAL RUNNING EVEN WITH ELECTRONIC FAILURE -
AUTOMATIC BATTERY CHARGER 2° INCLUDED -
FASTON CONNEXION 6,3mm FOR INDUSTRIAL WIRING HARNESS -
POWER RELAY FOR SWITCHING DIRECT COMMAND AMICO
General Features CONTROLS ‐ Programming key switch: 1. Automatic test 2. Automatic running 3. Blocked engine 4. Manual main 5. Manual start 6. Manual gen‐set ‐ Start button ‐ Stop button SIGNALS •
•
•
•
•
•
•
•
Mains presents Mains contactors closed Generator presents Generator contactor closed Battery in nominal value Battery charging Low fuel warning LED tension gen.: +10% / ‐10% VARIOUS FUNCTIONS One‐phase main sensor 4 adjustable start attempts ‐ Main sensor with dissymmetry ‐ Starting delay ‐ One‐phase generator sensor ‐ Adjustable gen‐set delay ‐ Adjustable protection insertion delay Motor cooling delay Mains come‐back delay Programmable stop NO/NC Self‐regulated stop time Electronic regulation prearrangement Emergency Stop prearrangement Automatic test presetting Remote command and control 2A automatic battery charger PROTECTIONS TECHNICAL DATA -
Working tension 100‐500Vac Working frequency 50‐60Hz Supply voltage 12 ± 30% Vcc Operation temperature –20°C / +70°C Max. absorb energy 300mA Commutation relay command with free contacts from 10 to 250Vac Alarm output 100mA max Start relay, stop and services 16A = 250Vac COSTRUCTION DOTAZIONE Schema elettrico manuale di installazione, uso e manutenzione al/pc panel Standard protection degree IP 54 Optional protection degree IP64 Build‐in battery charger 2A, with external supply transformer 30 VA per 12V. -
DIR. EMC 2004/108/CE DIR. BASSA TENSIONE 2006/95/CE -
riserva carburante allarme cumulativo mancato avviamento -
COMPONENTS ¾
AMICO command and control module OPTIONALS ¾
¾
TPA Timer prova automatica ogni 2‐7gg. IR/B3 Units interfaced to the start/stop/starter relays for assembling on a diesel or gasoline engine THE INDICATED DATAS ARE NOT BINDING BUT THEY ARE SUBJECT TO CHANGES WITHOUT NOTICE FOR TECHNICAL IMPROVEMENTS WITHOUT ALTERING THE ENTITY OF THE SUPPLY. AMICO
INDICATIF WIRING DIAGRAM