Electrical Drawings - Nicolini Construction Ltd.

DEPARTMENT OF CORPORATE SERVICES / SERVICES GENERAUX
REAL PROPERTY ASSET MANAGEMENT BRANCH /
DIRECTION DE LA GESTION DES ACTIFS ET DES BIENS IMMOBILIERS
DESIGN AND CONSTRUCTION DIVISION /
DIVISION DE LA CONCEPTION ET DE LA CONSTRUCTION
GREG GEDDES CHIEF CORPORATE SERVICES OFFICER /
CHEF DES SERVICES GÉNÉRAUX
S.A. FINNAMORE, O.A.A. DIRECTOR / DIRECTEUR, O.A.O.
ROBERT VAILLANCOURT, O.A.A. MANAGER / GESTIONNAIRE, O.A.O.
FOR / POUR
CORPORATE SERVICES
REAL PROPERTY ASSET MANAGEMENT
DESIGN & CONSTRUCTION
R
J
J
OS
P
NOT ALL SYMBOLS SHOWN IN LEGEND ARE NECESSARILY USED IN THE DRAWING SET.
P
NOT ALL SYMBOLS SHOWN IN LEGEND ARE NECESSARILY USED IN THE DRAWING SET.
NOT ALL SYMBOLS SHOWN IN LEGEND ARE NECESSARILY USED IN THE DRAWING SET.
3
ISSUED FOR TENDER
2014.04.09
M.X.
2
ISSUED FOR 99% REVIEW
2014.03.11
M.X.
1
ISSUED FOR 30% REVIEW
2014.01.21
M.X.
MILESTONE / FAIT SAILLANT
(Y/M/D)
DATE:
(A/M/J)
INITIALS
INITIALES
NUMBER/
NUMÉRO
M.X.
M.X.
A.X.
1:100
DETAIL NUMBER
1 DRAWING TITLE
A1.1 SCALE:
SHEET NUMBER
THIS DRAWING IS THE PROPERTY OF
THE CITY OF OTTAWA AND ALL
COPYRIGHT IS RESERVED.
DIMENSIONS ON DRAWING ARE FOR
ESTIMATING PURPOSES ONLY. IT IS
THE RESPONSIBLITY OF EACH
CONTRACTOR AND SUB-CONTRACTOR
OR CONSULTANT TO CHECK AND
VERIFY ALL DIMENSIONS AND
CONDITIONS ON SITE. NOTIFY OWNER
OF ANY ERRORS OR OMISSIONS PROIR
TO COMMENCING THE WORK. DO NOT
SCALE THE DRAWINGS.
CE DESSIN CONSTITUE LA PROPRIÉTÉ
DE LA VILLE D'OTTAWA ET TOUT DROIT
D'AUTEUR EST RÉSERVÉ. LES
DIMENSIONS UTILISÉES LE SONT À DES
FINS D'ESTIMATION SEULEMENT. IL
INCOMBE À CHAQUE ENTREPRENEUR,
SOUS-CONTRACTANT OU CONSULTANT
DE VÉRIFIER TOUTES LES DIMENSIONS
ET LES CONDITIONS SUR LE CHANTIER.
VEUILLEZ INFORMER LE PROPRIÉTAIRE
DE TOUTE ERREUR OU OMISSION
AVANT D'ENTAMER LES TRAVAUX. NE
DRESSEZ PAS LES PLANS À L'ÉCHELLE.
ARCHITECT / ARCHITECTE
CONSULTANT / EXPERT-CONSEIL
CONSULTANT / EXPERT-CONSEIL
CONSULTANT / EXPERT-CONSEIL
PROJECT / LOCATION / PROJET / ENDROIT
CITY OF OTTAWA
SANDY HILL ARENA
BUILDING UPGRADES
OTTAWA, ONTARIO
DRAWING / DESSIN
ELECTRICAL
LEGENDS, DRAWING LIST
GENERAL NOTES AND
LIGHT FIXTURE SCHEDULE
FACILITY NO. / NO. DE INSTALLTIONS
PROJECT NO. / PROJET NO.
SHEET NO. / FEUILLE No.
E00
DEPARTMENT OF CORPORATE SERVICES / SERVICES GENERAUX
REAL PROPERTY ASSET MANAGEMENT BRANCH /
DIRECTION DE LA GESTION DES ACTIFS ET DES BIENS IMMOBILIERS
DESIGN AND CONSTRUCTION DIVISION /
DIVISION DE LA CONCEPTION ET DE LA CONSTRUCTION
GREG GEDDES CHIEF CORPORATE SERVICES OFFICER /
S.A. FINNAMORE, O.A.A. DIRECTOR / DIRECTEUR, O.A.O.
ROBERT VAILLANCOURT, O.A.A. MANAGER / GESTIONNAIRE, O.A.O.
FOR / POUR
CORPORATE SERVICES
REAL PROPERTY ASSET MANAGEMENT
DESIGN & CONSTRUCTION
EXISTING PANEL 'PD1'
9
EXISTING RINK LIGHTING PANEL
EXISTING HEATER
TIMERS
10
T
T
EXISTING PANEL '2D'
EXISTING PANEL 'B'
6
EXISTING PANEL 'C'
7
EXISTING PANEL 'D'
1
1
11
11
1
1
11
EXISTING
PANEL 'PD2'
8
K
K
K
K
11
5
2
4
2
13
HD
HD
HD
HD
3
2
4
2
11
12
11
14
3
ISSUED FOR TENDER
2014.04.09
M.X.
2
ISSUED FOR 99% REVIEW
2014.03.11
M.X.
1
ISSUED FOR 30% REVIEW
2014.01.21
M.X.
MILESTONE / FAIT SAILLANT
(Y/M/D)
DATE:
(A/M/J)
INITIALS
INITIALES
NUMBER/
M.X.
M.X.
A.X.
1:100
DETAIL NUMBER
1 DRAWING TITLE
A1.1 SCALE:
SHEET NUMBER
GENERAL NOTES:
1. FLOOR PLANS ARE BASED ON PROVIDED AS-BUILT DRAWINGS. CONTRACTOR TO VERIFY EXISTING SITUATION ON SITE.
2. SEAL ALL PENETRATIONS TO WALL/FLOOR WITH CSA APPROVED FIRE-STOP MATERIALS UNLESS NOTED OTHERWISE.
DRAWING NOTES:
1
TYPICAL OF 4: EXISTING FORCE FLOW HEATER TO BE REMOVED BY MECHANICAL. ELECTRICAL CONTRACTOR TO DISCONNECT THE UNIT AND
REMOVE THE SWITCH, REMOVE WIRES BACK TO BOX AND MAKE SAFE FOR NEW CONNECTION.
2
TYPICAL OF 4: EXISTING HAND DRYER TO BE RELOCATED BY OTHERS. ELECTRICAL CONTRACTOR TO DISCONNECT THE UNIT AND MAKE
WIRES SAFE FOR RECONNECTION.
3
EXISTING EXHAUST FAN SWITCH TO BE RELOCATED. REFER TO DRAWING E03 FOR NEW LOCATION.
4
TYPICAL OF 4: EXISTING LIGHT FIXTURES AND SWITCHES IN WASHROOM TO BE REMOVED. REMOVE WIRES BACK TO J-BOX AND MAKE SAFE
FOR NEW CONNECTIONS.
5
EXISTING GFI RECEPTACLE TO BE RELOCATED. SEE DRAWING E03 FOR NEW LOCATION.
THIS DRAWING IS THE PROPERTY OF
THE CITY OF OTTAWA AND ALL
COPYRIGHT IS RESERVED.
DIMENSIONS ON DRAWING ARE FOR
ESTIMATING PURPOSES ONLY. IT IS
THE RESPONSIBLITY OF EACH
CONTRACTOR AND SUB-CONTRACTOR
OR CONSULTANT TO CHECK AND
VERIFY ALL DIMENSIONS AND
CONDITIONS ON SITE. NOTIFY OWNER
OF ANY ERRORS OR OMISSIONS PROIR
TO COMMENCING THE WORK. DO NOT
SCALE THE DRAWINGS.
DE LA VILLE D'OTTAWA ET TOUT DROIT
FINS D'ESTIMATION SEULEMENT. IL
SOUS-CONTRACTANT OU CONSULTANT
ET LES CONDITIONS SUR LE CHANTIER.
DE TOUTE ERREUR OU OMISSION
AVANT D'ENTAMER LES TRAVAUX. NE
ARCHITECT / ARCHITECTE
CONSULTANT / EXPERT-CONSEIL
CONSULTANT / EXPERT-CONSEIL
CONSULTANT / EXPERT-CONSEIL
6
ELECTRICAL CONTRACTOR TO VERIFY ON SITE.
7
ELECTRICAL CONTRACTOR TO VERIFY ON SITE.
8
ELECTRICAL CONTRACTOR TO VERIFY ON SITE.
9
DISCONNECT EXISTING FEEDERS FOR HEATERS AT PANEL 'PD1' IN SWITCH ROOM 112 AND MAKE SAFE. UPDATE PANEL DIRECTORY.
10
REMOVE EXISTING TIMERS C/W CONDUITS/WIRES BACK TO PANEL, MAKE IT SAFE.
11
TYPICAL OF 17: EXISTING CEILING MOUNTED LIGHT FIXTURE IN CHANGE ROOM AND TEAM ROOM TO BE RELOCATED. REFER TO DRAWING E03
FOR NEW LOCATIONS.
12
EXISTING WALL MOUNTED LIGHT FIXTURE IN WASHROOM TO BE RELOCATED. SEE DRAWING E03 FOR NEW LOCATION. REMOVE LIGHT SWITCH.
13
TYPICAL: PROTECT EXISTING SMOKE DETECTORS FROM DUST EXPOSURE DURING CONSTRUCTION.
14
EXISTING DISCONNECT TO BE RELOCATED DURING PANEL REPLACEMENT IF REQUIRED.
PROJECT / LOCATION / PROJET / ENDROIT
CITY OF OTTAWA
SANDY HILL ARENA
BUILDING UPGRADES
OTTAWA, ONTARIO
DRAWING / DESSIN
ELECTRICAL
GROUND LEVEL - DEMOLITION
FACILITY NO. / NO. DE INSTALLTIONS
PROJECT NO. / PROJET NO.
SHEET NO. / FEUILLE No.
E01
DEPARTMENT OF CORPORATE SERVICES / SERVICES GENERAUX
REAL PROPERTY ASSET MANAGEMENT BRANCH /
DIRECTION DE LA GESTION DES ACTIFS ET DES BIENS IMMOBILIERS
DESIGN AND CONSTRUCTION DIVISION /
DIVISION DE LA CONCEPTION ET DE LA CONSTRUCTION
GREG GEDDES CHIEF CORPORATE SERVICES OFFICER /
S.A. FINNAMORE, O.A.A. DIRECTOR / DIRECTEUR, O.A.O.
ROBERT VAILLANCOURT, O.A.A. MANAGER / GESTIONNAIRE, O.A.O.
FOR / POUR
CORPORATE SERVICES
REAL PROPERTY ASSET MANAGEMENT
DESIGN & CONSTRUCTION
1
3
2
3
ISSUED FOR TENDER
2014.04.09
M.X.
2
ISSUED FOR 99% REVIEW
2014.03.11
M.X.
1
ISSUED FOR 30% REVIEW
2014.01.21
M.X.
MILESTONE / FAIT SAILLANT
(Y/M/D)
DATE:
(A/M/J)
INITIALS
INITIALES
NUMBER/
M.X.
M.X.
A.X.
1:100
DETAIL NUMBER
1 DRAWING TITLE
A1.1 SCALE:
SHEET NUMBER
GENERAL NOTES:
1. FLOOR PLANS ARE BASED ON PROVIDED AS-BUILT DRAWINGS. CONTRACTOR TO VERIFY EXISTING SITUATION ON SITE.
2. SEAL ALL PENETRATIONS TO WALL/FLOOR WITH CSA APPROVED FIRE-STOP MATERIAL UNLESS NOTED OTHERWISE.
THIS DRAWING IS THE PROPERTY OF
THE CITY OF OTTAWA AND ALL
COPYRIGHT IS RESERVED.
DIMENSIONS ON DRAWING ARE FOR
ESTIMATING PURPOSES ONLY. IT IS
THE RESPONSIBLITY OF EACH
CONTRACTOR AND SUB-CONTRACTOR
OR CONSULTANT TO CHECK AND
VERIFY ALL DIMENSIONS AND
CONDITIONS ON SITE. NOTIFY OWNER
OF ANY ERRORS OR OMISSIONS PROIR
TO COMMENCING THE WORK. DO NOT
SCALE THE DRAWINGS.
DE LA VILLE D'OTTAWA ET TOUT DROIT
FINS D'ESTIMATION SEULEMENT. IL
SOUS-CONTRACTANT OU CONSULTANT
ET LES CONDITIONS SUR LE CHANTIER.
DE TOUTE ERREUR OU OMISSION
AVANT D'ENTAMER LES TRAVAUX. NE
DRAWING NOTES:
1
TYPICAL OF 32: EXISTING LIGHT FIXTURES OVER ICE AREA TO REMAIN.
2
TYPICAL OF 7: EXISTING LIGHT FIXTURES OVER SEAT TO REMAIN.
3
TYPICAL OF 20: EXISTING ELECTRIC RADIANT HEATERS TO BE REMOVED BY MECHANICAL. ELECTRICAL CONTRACTOR TO
DISCONNECT POWER SUPPLY TO THE HEATERS AND REMOVE WIRES BACK TO PANEL.
ARCHITECT / ARCHITECTE
CONSULTANT / EXPERT-CONSEIL
CONSULTANT / EXPERT-CONSEIL
CONSULTANT / EXPERT-CONSEIL
PROJECT / LOCATION / PROJET / ENDROIT
CITY OF OTTAWA
SANDY HILL ARENA
BUILDING UPGRADES
OTTAWA, ONTARIO
DRAWING / DESSIN
ELECTRICAL
UPPER LEVEL - DEMOLITION
FACILITY NO. / NO. DE INSTALLTIONS
PROJECT NO. / PROJET NO.
SHEET NO. / FEUILLE No.
E02
DEPARTMENT OF CORPORATE SERVICES / SERVICES GENERAUX
REAL PROPERTY ASSET MANAGEMENT BRANCH /
DIRECTION DE LA GESTION DES ACTIFS ET DES BIENS IMMOBILIERS
DESIGN AND CONSTRUCTION DIVISION /
DIVISION DE LA CONCEPTION ET DE LA CONSTRUCTION
GREG GEDDES CHIEF CORPORATE SERVICES OFFICER /
S.A. FINNAMORE, O.A.A. DIRECTOR / DIRECTEUR, O.A.O.
ROBERT VAILLANCOURT, O.A.A. MANAGER / GESTIONNAIRE, O.A.O.
FOR / POUR
CORPORATE SERVICES
REAL PROPERTY ASSET MANAGEMENT
DESIGN & CONSTRUCTION
EXISTING PANEL 'PD1'
EXISTING RINK LIGHTING PANEL
EXISTING PANEL '2D'
NEW PANEL 'B'
1
NEW PANEL 'C'
2
15
GENERAL NOTES:
23
19
4
19
6
19
14
23
23
4
15
19
19
14
23
17
13
16
NEW PANEL 'D'
15
3
EXISTING
PANEL 'PD2'
1. FLOOR PLANS ARE BASED ON PROVIDED AS-BUILT DRAWINGS. CONTRACTOR TO VERIFY EXISTING SITUATION ON SITE.
2. SEAL ALL PENETRATIONS TO WALL/FLOOR WITH CSA APPROVED FIRE-STOP MATERIAL UNLESS NOTED OTHERWISE.
23
OS
OS
C
P
B
B
C
HD
HD
P
HD
OS
C
B
B
P
B
B
OS
C
P
B
4
P
HD
B
HD
C
OS
OS
OS
OS
OS
P
B
8
23
12
14
10
9
8
23
8
23
18
8
23
22
21
14
5
11
OS
12
20
7
14
3
ISSUED FOR TENDER
2014.04.09
M.X.
2
ISSUED FOR 99% REVIEW
2014.03.11
M.X.
1
ISSUED FOR 30% REVIEW
2014.01.21
M.X.
MILESTONE / FAIT SAILLANT
(Y/M/D)
DATE:
(A/M/J)
INITIALS
INITIALES
NUMBER/
M.X.
M.X.
A.X.
1:100
DETAIL NUMBER
1 DRAWING TITLE
A1.1 SCALE:
DRAWING NOTES:
SHEET NUMBER
1
WIRES TO SUIT AS REQUIRED. TRACE & VERIFY EXISTING CIRCUITS AND PROVIDE UPDATED PANEL DIRECTORY IN PANEL. EXPAND EXISTING WALL OPENING TO FIT NEW PANEL BY GENERAL CONTRACTOR. COORDINATE WORK WITH GENERAL
CONTRACTOR AND ARENA OPERATOR.
THIS DRAWING IS THE PROPERTY OF
THE CITY OF OTTAWA AND ALL
COPYRIGHT IS RESERVED.
DIMENSIONS ON DRAWING ARE FOR
ESTIMATING PURPOSES ONLY. IT IS
THE RESPONSIBLITY OF EACH
CONTRACTOR AND SUB-CONTRACTOR
OR CONSULTANT TO CHECK AND
VERIFY ALL DIMENSIONS AND
CONDITIONS ON SITE. NOTIFY OWNER
OF ANY ERRORS OR OMISSIONS PROIR
TO COMMENCING THE WORK. DO NOT
SCALE THE DRAWINGS.
2
WIRES TO SUIT AS REQUIRED.TRACE & VERIFY EXISTING CIRCUITS AND PROVIDE UPDATED PANEL DIRECTORY IN PANEL. EXPAND EXISTING WALL OPENING TO FIT NEW PANEL BY GENERAL CONTRACTOR. COORDINATE WORK WITH GENERAL
CONTRACTOR AND ARENA OPERATOR.
3
WIRES TO SUIT AS REQUIRED.TRACE & VERIFY EXISTING CIRCUITS AND PROVIDE UPDATED PANEL DIRECTORY IN PANEL. EXPAND EXISTING WALL OPENING TO FIT NEW PANEL BY GENERAL CONTRACTOR. COORDINATE WORK WITH GENERAL
CONTRACTOR AND ARENA OPERATOR.
4
TYPICAL OF 3
5
RELOCATE GFI RECEPTACLE AS SHOWN. EXTEND WIRES AND CONDUIT TO SUIT NEW LOCATION. LABEL CIRCUIT# ON RECEPTACLE AND ANNOTATE CIRCUIT# ON AS-BUILT DRAWING.
6
TYPICAL OF 4: NEW GFI RECEPTACLE OVER COUNTER MOUNTED ON WALL. WIRE TO CIRCUIT# AS SHOWN ON DRAWING.
7
RE-INSTATE EXISTING DISCONNECT AFTER PANEL REPLACEMENT, LEAVE MIN. 1 METER CLEARANCE FROM PANEL FRONT. CO-ORDIANTE EXACT LOCATION WITH ARENA OPERATOR ON SITE. EXTEND WIRES AND CONDUIT TO SUIT AS REQUIRED.
8
TYPICAL OF 4: NEW FORCE FLOW HEATER FF-1 TO FF-4 C/W DISCONNECT SWITCH BY MECHANICAL, TO BE WIRED TO EXISTING FORCE FLOW HEATER CIRCUIT BY ELECTRICAL. EXTEND WIRES C/W CONDUIT TO SUIT NEW LOCATION AND MAKE CONNECTION.
THERMOSTAT BY MECHANICAL AND WIRED BY ELECTRICAL. SEE MECHANICAL DRAWING FOR EXACT HEATER LOCATION AND MOUNTING HEIGHT. ANNOTATE CIRCUIT# ON AS-BUILT DRAWING.
9
TYPICAL OF 4: RELOCATED HAND DRYER IN CHANGE ROOMS BY OTHERS. ELECTRICAL CONTRACTOR TO EXTEND WIRES AND CONDUIT TO SUIT NEW LOCATION AND MAKE CONNECTION. REFER TO ARCHITECTURAL DRAWING FOR EXACT HAND DRYER
LOCATION AND MOUNTING HEIGHT.
TYPICAL OF 3: EXISTING EXHAUST FAN TO REMAIN.
11
RELOCATE EXISTING WASHROOM WALL LIGHT FIXTURE TO BE MOUNTED AT AFF 8'. WIRE BACK TO ORIGINAL LIGHTING CIRCUIT AND NEW WALL SENSOR SWITCH.
12
TYPICAL OF 10: NEW WALL SWITCH OCCUPANCY SENSOR TO BE DIVERSA #WOSSDU1-P-VW-L C/W FACE PLATE (OR APPROVED EQUIVALENT). WIRE TO EXISTING LIGHTING CIRCUIT AND MAKE CONNECTION TO LIGHT FIXTURES AS SHOWN ON DRAWING.
GFI RECEPTACLE
TEAM RM#1 & 2
13
RELOCATE EXISTING FAN SWITCH AND WIRE BACK TO EXISTING EXHAUST FAN AS SHOWN. EXTEND WIRES AND CONDUIT AS REQUIRED.
GFI RECEPTACLE
TEAM RM#3 & 4
14
TYPICAL: PROVIDE NEW LIGHT FIXTURE, TYPE AS SHOWN ON DRAWING. REFER TO LIGHT FIXTURE SCHEDULE FOR DETAIL. WIRE TO EXISTING NEAREST AVAILABLE LIGHTING CIRCUIT AND ANNOTATE CCT# ON AS BUILT DRAWING.
15
TYPICAL:
REFER TO ARCH DRAWING FOR EXACT PUSH BUTTON LOCATION. COORDINATE WORK WITH HARDWARE CONTRACTOR.
17
PROVIDE NEW MIRCOM CENTRAL MONITORING PANEL CONSISTS OF AN EC-300 CENTRAL CALL RECEIVER MODULE, EC-220A 20 LED ANNUNCIATOR PANEL WITH A DIRECTORY, A 301-2F FRAME HOUSING, A 301-2B BACK BOX FOR 301-2F, A 40VA POWER
SUPPLY AND CAT-5e350 FT6 CABLE.CCT# FOR POWER SUPPLY AS SHOWN ON DRAWING. ELECTRICAL CONTRACTOR TO RUN WIRES C/W CONDUITS IN WALL FROM CENTRAL PANEL TO EACH PULL CORD STATION IN WASHROOM AND DOME LIGHT WITH
BUZZER IN CORRIDOR TO COMPLETE A WORKING SYSTEM AND MAKE TEST. REFER TO MANUFACTURER INSTALLATION INSTRUCTION FOR DETAIL. EXACT LOCATION OF PANEL TO BE DETERMINED ON SITE WITH CLIENT.
18
TYPICAL OF 5: PROVIDE NEW MIRCOM #EC100 PULL CORD STATION MOUNTED AT AFF 1.2M AND CONNECT TO CENTRAL MONITORING PANEL AND PAIRING DOME LIGHT WITH #22 AWG WIRES IN 21MMC EMT. REFER TO ARCHITECTURAL DRAWING FOR EXACT
LOCATION AND MOUNTING HEIGHT. REFER TO MANUFACTURER'S MANUL FOR INSTALLATION DETAIL.
19
TYPICAL OF 5: PROVIDE NEW MIRCOM #EC140 DOME LIGHT WITH BUZZER MOUNTED AT AFF 2.03M AND CONNECT TO CENTRAL MONITORING PANEL AND PAIRING PULL CORD STATION WITH #22 AWG WIRE IN 21MMC EMT. REFER TO MANUFACTURER'S
MAUNAL FOR INSTALLATION DETAIL.
20
THERMOSTAT BY MECHANICAL AND WIRED BY ELECTRICAL.
21
ELECTRICAL CONTRACTOR TO PROVIDE AND INSTALL NEW LINE VOLTAGE PUSH BUTTON CONTROLLER PB-2. CONTROLLER SHALL BE EQUIPPED WITH TIME-OFF-DELAY RELAYS ADJUSTABLE FROM 30 MINUTE TO 90 MINUTE SET AT 60 MINUTE DURATION.
PUSH BUTTON SHALL BE NORMALLY OPEN, RED 120V LED PILOT LIGHT ILLUMINATED 22.5MM WITH METAL COLLAR, CONTROLLER BOX SHALL BE CAPABLE OF CONTROLLING THREE ZONES OF MULTIPLE INFRARED HEATERS. CONTROLLER BOX SHALL HAVE
A NORMALLY OPEN, NON-ILLUMINATED BLACK 22.5MM RESET BUTTON TO SHUT OFF INFRARED HEATERS, COMPLETE WITH ALL POWER AND CONTROL WIRING (2#12+GND-21MMC), ACCESSORIES, AND SUPPLIED WITH METAL ENCLOSURE SIZED TO FIT
REQUIRED ELECTRICAL COMPONENTS. REFER TO DRAWING 2/E04 & 3/E04 FOR WIRING DIAGRAM AND DRAWING 4/E04 FOR CONTROLS ENCLOSURE LAYOUT. EXACT LOCATION TO BE DETERMINED WITH ARENA OPERATOR ON SITE.
22
PROVIDE TWO (2) SWITCHES (SW 1 & SW 2) FOR RADIANT GAS HEATER CIRCUIT, SEE DRAWING 3/E04 FOR WIRING DIAGRAM. EXACT LOCATION TO BE DETERMINED WITH ARENA OPERATOR ON SITE.
23
TYPICAL OF 17: RELOCATE EXISTING CEILING MOUNTED LIGHT FIXTURES IN CHANGE ROOMS AND TEAM ROOMS, WIRE BACK TO ORIGINAL CIRCUIT. COORDINATE EXACT LOCATION ON SITE WITH NEW CONSTRUCTION. EXTEND WIRES AND CONDUIT TO
SUIT AS REQUIRED.
FINS D'ESTIMATION SEULEMENT. IL
SOUS-CONTRACTANT OU CONSULTANT
ET LES CONDITIONS SUR LE CHANTIER.
DE TOUTE ERREUR OU OMISSION
AVANT D'ENTAMER LES TRAVAUX. NE
ARCHITECT / ARCHITECTE
CONSULTANT / EXPERT-CONSEIL
CONSULTANT / EXPERT-CONSEIL
CONSULTANT / EXPERT-CONSEIL
EMERGENCY CALL
MODULE POWER SUPPLY
10
16
DE LA VILLE D'OTTAWA ET TOUT DROIT
RADIANT GAS HEATER
BARRIER-FREE DOOR
OPERATOR TEAM RM#1&2
RADIANT GAS HEATER
BARRIER-FREE DOOR
OPERATOR TEAM RM#3&4
FORCE FLOW HEATER FF-5
BARRIER-FREE DOOR
OPERATOR TEAM RM#5
TRAP SEAL PRIMER
PROJECT / LOCATION / PROJET / ENDROIT
HAND DRYER
TEAM RM#5
CITY OF OTTAWA
SANDY HILL ARENA
BUILDING UPGRADES
OTTAWA, ONTARIO
DRAWING / DESSIN
ELECTRICAL
GROUND LEVEL - NEW
FACILITY NO. / NO. DE INSTALLTIONS
PROJECT NO. / PROJET NO.
SHEET NO. / FEUILLE No.
E03
DEPARTMENT OF CORPORATE SERVICES / SERVICES GENERAUX
REAL PROPERTY ASSET MANAGEMENT BRANCH /
DIRECTION DE LA GESTION DES ACTIFS ET DES BIENS IMMOBILIERS
DESIGN AND CONSTRUCTION DIVISION /
DIVISION DE LA CONCEPTION ET DE LA CONSTRUCTION
GREG GEDDES CHIEF CORPORATE SERVICES OFFICER /
S.A. FINNAMORE, O.A.A. DIRECTOR / DIRECTEUR, O.A.O.
ROBERT VAILLANCOURT, O.A.A. MANAGER / GESTIONNAIRE, O.A.O.
FOR / POUR
CORPORATE SERVICES
REAL PROPERTY ASSET MANAGEMENT
DESIGN & CONSTRUCTION
2
2
A
2
A
2
A
2
A
2
A
A
2
2
2
A
A
A
1
3
3
C#29
RH-1
3
C#29
RH-2
3
C#29
3
C#29
RH-3
RH-4
3
C#31
RH-5
5
3
C#31
RH-6
C#31
RH-7
PB-1
P
4
3
ISSUED FOR TENDER
2014.04.09
M.X.
2
ISSUED FOR 99% REVIEW
2014.03.11
M.X.
1
ISSUED FOR 30% REVIEW
2014.01.21
M.X.
MILESTONE / FAIT SAILLANT
(Y/M/D)
DATE:
(A/M/J)
INITIALS
INITIALES
NUMBER/
PB-2
PB-1
M.X.
M.X.
A.X.
1:100
DETAIL NUMBER
1 DRAWING TITLE
A1.1 SCALE:
SHEET NUMBER
GENERAL NOTES:
1. BUILDING FLOOR PLANS ARE BASED ON PROVIDED AS-BUILT DRAWINGS. CONTRACTOR TO VERIFY EXISTING SITUATION ON SITE.
2. SEAL ALL PENETRATIONS TO WALL/FLOOR WITH CSA APPROVED FIRE-STOP MATERIAL UNLESS NOTED OTHERWISE.
THIS DRAWING IS THE PROPERTY OF
THE CITY OF OTTAWA AND ALL
COPYRIGHT IS RESERVED.
DIMENSIONS ON DRAWING ARE FOR
ESTIMATING PURPOSES ONLY. IT IS
THE RESPONSIBLITY OF EACH
CONTRACTOR AND SUB-CONTRACTOR
OR CONSULTANT TO CHECK AND
VERIFY ALL DIMENSIONS AND
CONDITIONS ON SITE. NOTIFY OWNER
OF ANY ERRORS OR OMISSIONS PROIR
TO COMMENCING THE WORK. DO NOT
SCALE THE DRAWINGS.
DE LA VILLE D'OTTAWA ET TOUT DROIT
FINS D'ESTIMATION SEULEMENT. IL
SOUS-CONTRACTANT OU CONSULTANT
ET LES CONDITIONS SUR LE CHANTIER.
DE TOUTE ERREUR OU OMISSION
AVANT D'ENTAMER LES TRAVAUX. NE
DRAWING NOTES:
1
TYPICAL OF 32: EXISTING LIGHT FIXTURES OVER ICE AREA TO REMAIN.
2
TYPICAL OF 9: NEW LIGHT FIXTURES TO BE J2 iMEK #i63-X6XHL. ELECTRICAL CONTRACTOR TO INSTALL AT THE SAME HEIGHT AS
EXISTING FIXTURES AND MEET OBC SEISMIC REQUIREMENTS. PROVIDE NEW WIRING AND CONDUIT FROM NEW FIXTURE TO
EXISTING JUNCTION BOX (AT CEILING SPACE) AND CONNECT TO EXISTING NEARBY LIGHTING CIRCUIT. (2#10+GND-27mmC)
3
TYPICAL OF 7:
2#10+GND-21MMC WIRES FROM PANEL 'D' UP TO HEATERS, PROVIDE SERVICE SWITCH AT EACH HEATER, CIRCUIT # AS SHOWN
ON DRAWING. PUSH BUTTONS BY ELECTRICAL AND THERMOSTAT BY MECHANICAL, TO BE WIRED BY ELECTRICAL. REFER TO
MECHANICAL DRAWING FOR EXACT LOCATION OF RADIANT HEATER, THERMOSTAT AND PUSHBUTTONS.
4
ELECTRICAL CONTRACTOR TO PROVIDE AND INSTALL NEW REMOTE LINE VOLTAGE PUSH BUTTON CONNECTED TO PB-2 WITH
NORMALLY OPEN, RED 120V LED PILOT LIGHT ILLUMINATED 22.5MM PUSH BUTTON WITH METAL COLLAR, COMPLETE WITH ALL
POWER AND CONTROL WIRING (2#12+GND-21MMC), ACCESSORIES, AND SUPPLIED WITH METAL ENCLOSURE SIZED TO FIT
REQUIRED ELECTRICAL COMPONENTS. REFER TO DRAWING 2/E04 AND 3/E04 FOR WIRING DIAGRAM AND DRAWING 4/E04 FOR
CONTROLS ENCLOSURE LAYOUT.
5
ARCHITECT / ARCHITECTE
CONSULTANT / EXPERT-CONSEIL
CONSULTANT / EXPERT-CONSEIL
CONSULTANT / EXPERT-CONSEIL
THERMOSTAT FOR RADIANT HEATER BY MECHANICAL. TO BE WIRED BY ELECTRICAL.
PROJECT / LOCATION / PROJET / ENDROIT
CITY OF OTTAWA
SANDY HILL ARENA
BUILDING UPGRADES
OTTAWA, ONTARIO
DRAWING / DESSIN
ELECTRICAL
UPPER LEVEL - NEW
FACILITY NO. / NO. DE INSTALLTIONS
PROJECT NO. / PROJET NO.
SHEET NO. / FEUILLE No.
E04