Data sheet EL EX-PROOF ACTUATOR WITH LOCAL CONTROL STATION (FLAME-PROOF Ex d) Sheet No.: 5.207.1 Rev. B Date: February 2012 Description This electric actuator variation for use on an explosion proof actuator has the addition of a local control box, with a single rotary 5 position switch with 5 SPST contacts. 136 98 Local off Remote Remote Local close Local open 86 The switch selects between: “LOCAL OPEN”, “REMOTE”, “OFF”, “REMOTE” and “LOCAL CLOSE”. 165 When in “LOCAL OPEN” or “LOCAL CLOSE” position the actuator can not be operated remotely. EL-O-MATIC Non lockable Local off Remote This local control station is certified flame proof according to EN 60079-0 and EN 60079-1 as an integral part of the base actuator and bears ATEX marking II 2 G Ex db IIB T4. Remote Construction The control station is located on the side of an ATEX II 2 G Ex db IIB T4 flame proof electric actuator and all the connection wiring is contained internally. Local open Local close 98 Specification Switches Type Model Voltage Current Temperature EL-O-MATIC Padlockable Incoming power N L Field wiring 16A Close 1 4 Actuator wiring Open 8A 12 com no TS open no Heater 10W nc Limit switch 3 25 26 27 Blue LS open 2 nc 24 Green nc 23 White Brown TS close no Brown com com no Blue Green * 22 Yellow 10 9 Blue LS close 1 com nc 8 Red 7 White nc * Linked for torque seated valve Yellow www.El-O-matic.com 6 Red Motor 1~ 11 Open com no 14 Note: Valve shown in mid position. Yellow M * Black C 13 Black 5 3 Open Remote Close 2 Close 5A Local LC-Ex :Santon : H1 P-EE1 : Up to 600V : 20A max. (resistive load) :-20°C to +60°C Housing Material Finish :Aluminium : Two component polyurethane Flame proof Marking Certificate nr. Actuator sizes : II 2 G Ex db IIB T4, suitable for ATEX Zones 1, 2 (gas) : DEKRA 12ATEX0001 X : EL 35, EL 55, EL100, EL150, EL200, EL350, EL500 and EL800 Identification Factory Option : Add “+ LC-Ex” (non lockable or “+LCL-Ex” (padlockable) to the basic actuator size eg. EL100 220/50 + LC-Ex Note 1 This option is not supplied as a kit option, only as a factory option 2 Both local/remote and close/stop/open switches are combined into one switch 3 Wiring diagram for EL100-EL800 220V/50Hz + LC-Ex com no nc Limit switch 4 Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained from our website www.El-O-Matic.com or from your nearest Valve Automation Center USA: +1 813 319 0266 Europe: +31 74 256 10 10 Asia-Pacific: +65 6501 4600
© Copyright 2024 Paperzz